| 1 | Excavation of trenches in soft/loose soil n.exc 1.5 metre wide and n.exc 1.5 metre depth and getting out complete all as specified and directed. |
| 2 | Returning filling in approved earth, including spreading leveling watering and well ramming in layers not exceeding 25cm in soft/loose soil complete all as specified and directed |
| 3 | Removing excavated surplus soil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.50metre above the starting point complete all as specified and directed. |
| 4 | Taking out old U/S underground LT cable of any size, any position from trenches, floors and walls, complete all as specified and directed. |
| 5 | Supply, fixing ,Testing and commissioning XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables ( heavy duty) with stranded aluminum conductor, 1100Volt grade with fixing acessories of 10 Sqmm, 2 Core complete all as specified and directed. |
| 6 | All as per item No. 5 above but for size of cable 10 sqmm, 4 core complete all as specified and directed. |
| 7 | All as per item No. 5 above but for size of cable 16 sqmm, 4 core complete all as specified and directed. |
| 8 | M&L sand cushioning (dry) in trenches for protection of UG cables (below, above and around the cable laid in trenches) of 230mm spreding thickness and consolidated ( punned) upto 180mm thickness, complete all as specified and as directed. |
| 9 | Supply & laying in trenches GI pipe 50 mm bore light grade for protection of U/G cable complete all as specified and as directed. |
| 10 | Supply & Laying Sub-Class old size B Bricks, well burnt, laid breadth wise along the length of cable laid in trenches over sand cushion laid for UG cable protection, complete all as specified and directed. |
| 11 | S&F of energy saving and environment friendly long life 90 W or next higher available rating, CT>=5700 K, LED street light made up of pressure die-cast aluminium housing with acrylic cover as diffuser with IP 66 protection and impact resistance not less than IK-07 complete with integrated type, with high efficiency electronic driver, built-in- surge suppressor / SPD of 10 KV or more and high brightness LEDs, luminaire efficacy > 110 lumens/Watt, power factor >=0.90, operating range – 140 to 270 V, 50 Hz complete including suitable necessary MS clamps, nuts, bolts etc. complete all as specified and as directed. |
| 12 | All as per item No. 11 above but of 60 W capacity LED Street light complete all as specified and directed. |
| 13 | All as per item No. 11 above but of 45 W capacity LED Street light complete all as specified and directed.. |
| 14 | All as per item No. 11 above but of 30 W capacity LED Street light complete all as specified and directed. |
| 15 | Supply, fixing energy saving, environmental friendly, long life, exclusive innovative die-cast aluminium IP65 flood light with high power LEDs as light source connecting and testing LED Flood lights of 200 watts capacity and unique peanut lens to ensure uniform distribution, complete all as specified and directed by the Engr-in-charge. |
| 16 | All as per item No. 15 above but of 120 W capacity LED Flood light complete all as specified and directed.. |
| 17 | All as per item No. 15 above but of 70 W capacity LED Flood light complete all as specified and directed. |
| 18 | All as per item No. 15 above but of 50 W capacity LED Flood light complete all as specified and directed. |
| 19 | S & F in replacement 8W LED outdoor new generation landscape lighting fitting Bamboo type with 1mtr length IP 65/66 protection including base to stand alone complete all as specified and directed. |
| 20 | S & F in replacement 8W LED outdoor new generation landscape lighting fitting Cone type with IP 65 protection including base to stand alone complete all as specified and directed. |
| 21 | S & F in replacement 35 W LED outdoor New generation, energy saving, environmental friendly, long life aesthetically designed with symmetrical light distribution, spun aluminum landscape luminaries with high power COB LEDs as light source with IP 65/66 , IK-07 protection complete all as specified and directed. |
| 22 | S & F in replacement 45 W LED outdoor New generation, Circular LED post-top, energy saving, environmental friendly, long life aesthetically designed with symmetrical light distribution, spun aluminum landscape luminaries with high power LEDs as light source with IP 65/66 , IK-07 protection complete all as specified and directed. |
| 23 | Supply, fixing energy saving, environmental friendly, long life, exclusive innovative die-cast aluminium IP65 2 way decorative light with high power LEDs as light source connecting and testing LED Spike lights of 6 watts capacity and unique peanut lens to ensure uniform distribution, complete all as specified and directed by the Engr-in-charge. |
| 24 | Supply, fixing energy saving, environmental friendly, long life, exclusive innovative die-cast aluminium IP65 Spike light with high power LEDs as light source connecting and testing LED Spike lights of 25 watts capacity and unique peanut lens to ensure uniform distribution, complete all as specified and directed by the Engr-in-charge. |
| 25 | S & F in replacement 25 W LED outdoor New generation, post-top, energy saving, environmental friendly, long life aesthetically designed with symmetrical light distribution, spun aluminum landscape luminaries with high power LEDs as light source with IP 65/66 , IK-07 protection complete all as specified and directed. |
| 26 | Supply and fixing of OUTDOOR/FACADE LED strip light of 230 V AC, wall mount/plug in, bobust design(IP 65), precise light distribution for illumination of Top crown and area of the building or as required at site complete all as specified and as directed by Engr in charge. |
| 27 | S & F of Powered by inbuilt, isolated electronic LED driver (SMPS based constant current supply) for street lights/ flood lights 70 to 120 watt site selectable with lower THD, Output Open /Short Circuit protection, Phase to Phase protection, Over Voltage protection, Surge Voltage protection including taking down old unserviceable LED driver complete all as specified and directed. |
| 28 | All as in Item No- 27, but for 45 to 60 watt, complete all as specified and directed. |
| 29 | Taking down carefully old unserviceable street light bracket with clamps of size 25/40/50mm from street tubular pole (light fitting) complete all as specified and as directed. |
| 30 | S&F street light bracket made out of GI tubing medium grade 1.50 Mtr long bend to required shape as in bracket for street light fittings fixed with two pair or MS flat iron 50 mm x 6mm size and 30cm long clamp of required shape with bolts nuts and washers suitable for steel tubular pole including painting of mild steel flat iron surfaces with two coats of synthetic enamel paint over a coat of red oxide primer complete of size 32 mm. complete all as specified and directed. |
| 31 | All items as per Ser No 30 above but 25 mm complete all as specified and directed. |
| 32 | M&L Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6.00 mm thick burried in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level, connected to GI wire 4mm as earthing lead by means of bolts, nuts, check nuts and washers of GI or steel, GI strip proected by 40 mm bore light grade GI pipe and other end connected to earth test point as directed including funnel with watering pipe 20 mm bore light grade galvanised iron, wire mesh, charcoal or coke common salt laid in alternative layer of 15 cm (complete thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1, 50 mm thick pre-cast RCC (1:2:4) type B-1 normal mix cover slab reinforced with 8 mm dia TMT bar 10 cm c/c bothways and single handle of 10 mm dia round bar including necessary excavation, earth work etc. in soft / loose soil and disposal pf soil to a distance n. exc. 50 m and necessary testing on completion all as shown in electrical plate No. 3 MES Schedule Part-I complete all as specified and as directed. |
| 33 | Supply and fix in replacement 3 core 1.5 sqmm multistranded PVC insulated flexible copper cable FRLS grade including required PVC Conduit to protect the cable complete all as specified and directed. |
| 34 | S&F MCB Single pole and neutral 'C' curve 240 Volt 20 to 40 Amp capacity complete all as specified and directed. |
| 35 | S&F MCB Single pole 240 Volt 6 to 32 Amp capacity complete all as specified and directed. |
| 36 | S&F MCB TPN 415 Volt 6 to 32 Amp capacity complete all as specified and directed. |
| 37 | Supply and fixing of street light thermoplastic cable junction box of size 200 x 160 x 98 mm IP 66, weather proof for outdoor installation with TPN terminal and MCB SP 6-20 A. complete all as specified and directed. Make - Hensel / Syntex |
| 38 | M & L for lowering of high mast carriage carefully from 20 mtr high structure for repairing light luminaries and raising latern carriage after repairing the light luminarises and adjust to its proper postion serving to winch mechanism pulleys steel wire ropes end terminal of SWR and greasing drain gearbox oil and toping up complete all as specified and directed. Note : Defective parts shall be measured and paid supply only under respective items of sch 'A'. |
| 39 | Detecting the fault of line system of high Mast by providing skilled tradesman and helper with necessary safty tools and rectify the defects on top priority basis including testing complete all as specified and directed. |
| 40 | S&F in repair analog timer switch , surface mounting as per sample for automatic operation of street light complete all as specified and directed. |
| 41 | S&F contactor modular type with ON/OFF indicator and label holder 3 pole 230 V 40-63 Amps coil operating voltage 230 volt as per sample complete all as specified and directed. |
| 42 | S&F contactor modular type with ON/OFF indicator and label holder 4 pole 230 V 40-63 Amps coil operating voltage 230 volt complete all as specified and directed. |
| 43 | S&F Air termination single pointed Aluminum rod 12mm dia and 300 mm long complete all as specified and directed. |
| 44 | S&F Aluminum strip 25x3.15mm with saddles fixing scrcub etc for roof conductors down conductors above Ground by providing shaddle / insulator distance not more than 0.5 mcomplete all as specified and directed. |
| 45 | S&F G.I Strip 32 x 6mm burried in Ground complete all as specified and directed. |
| 46 | M & L in repairs Copper strip 20 x 3.15 mm with saddles and fixing screws etc. for roof conductors and down conductors above ground complete all as specified and directed |
| 47 | S&F Test point terminal block made of gun metal or phosphorus bronze size 75x75x25 mm drilled and screwed including 3 Nos 8 mm dia 25mm long hex head screw complete all as specified and directed. |
| 48 | M&L Earthing complete with GI pipe electrode, 40mm bore, medium grade, 2.5m length burried directly in ground vertically with top edge not less than 1.25 m below ground level connected to galvanised iron earth strip 32x6 mm by means of bolts, nuts, check nuts and washers protected by 15mm bore light grade GI pipe, funnel with 20mm bore GI medium grade pipe for watering, wire mesh, including concrete pit in PCC (1:3:6) type C-1, pre-cast RCC 1:2:4 type B-1 cover slab of size 350x350x50mm reinforced with 8mm dia TMT steel bars @15cm centre to centre in both direction and 10mm dia MS handle of suitable size, charcoal or coke and salt in alternative layers,necessary earth work in soft/loose soil all as shown in Electrical Plate No 4 of MES Schedule Part I and testing complete inclduing taking down old one complete all as specified and as directed. |
| 49 | Supply and fixing in replacement of Automatic street light control switch Panel complete with, complete all as specified and directed.a) Infrared sensor based Nature Switch for automatic switching of street lights (Asto. Nature switch operation should be based on Natural light Lux level. Required luminance level for switching ON is less or equal to 30 Lux and for switching OFF 10 Lux. The sensor should also have part night operation facility of minimum 4 hrs to maximum 12 hrs. - 01 No.Make Of Sensor: L&T/SIEMENS/ HPL/Bajaj/ABBb) Power contactor two pole, 230 volts, 63 Amp capacity, confirming to IEC-60947-4-1. - 01 No.Make:- L&T/Schneider/ABB/Bajajc) The sensor along with suitable power contactor and incoming outgoing MCBs should be enclosed in a pole/ wall mountable rust proof, electric shock proof, termite proof and FR grade Thermoplastic polycarbonate enclosure (with hinged lid) confirming to IP66 protection class 2 of suitable size to accommodate all panel accessories. -01 Job.d) MCB SP 63 Amp, C Curve, Confirming to IEC-60898/IS8828. -02 Nos.Make: Hager/Schneider/L&T/ABBe) All control cable wiring inside the panel should be of copper conductor, multistandard, PVC insulated, FRLS, 1100 volts grade, of size 10 sq mm, single core, followed by colour coding and lugs/thimbles.Make: Finolex/Polycab/Plaza. (All ISI marked)f) All equipments are mounted on suitable size insulators. |
| 50 | NOTES:1. The amount of schedule of credit shall be deducted from the total of this BOQ for arriving at contract sum. Please Enable Macros to View BoQ information |