| 1 | Permanent restoration of 33KV GIS Tengpora KP Bagh Line at Kursoo across river Jehlum |
| 2 | Supply and Erection of 13 Mtr. Long Steel Tubular Pole with welded steel base plate (of Designation 410 SP69) and top cap including excavation of pit and back filling by boulders as per REC construction Standard (with latest amendments if any). |
| 3 | Providing and fixing of fabricated GI V cross arm with top bracket, Channel X-arm including belting, clamps and braces angle iron as per site reqirement. |
| 4 | Providng,Laying,stringing ,tensioning and binding of 100 Sqmm ACSR Conductor as per REC construction standard (with latest amendments if any). |
| 5 | Providing and fixing of PG Clamps for 100 mm² ACSR Conductor. |
| 6 | Supply,installation,testing and commissioning of 33 kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm, |
| 7 | Supply,installation,testing and commissioning of 33 kV Polymeric composite Disc Insulator 36KV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm with fitting |
| 8 | Providing and fixing of Gavanized Nuts & Bolts with washers of sorts as per site requirements. |
| 9 | Providing and fixing of Danger Plates with clamps of standard make |
| 10 | Providing and fixing of Anti Climbing Devices with clamps of standard make |
| 11 | Providing and fixing of Earthing of ST poles Complete by by GI pipe 40mm 3 mtr long through GI strip 25x3mm, as per REC standards. |
| 12 | Restringing of the existing conductor including opening, tensioning and binding etc complete job |
| 13 | Dismentalling of poles along with allied material and loading, transportation, unloading and stacking at divisional stores Karannagar |
| 14 | Earth work in excavation by manual means over areas including disposal of excavated earth upto 1 meter from cutting edge ,disposed earth to be levelled and neatly dressed in ordinary |
| 15 | Providing & laying in position cement conc. of specified grade excld. Cost of centering & shuttering- all work upto plinth level in 1:4:8 (1 cement :4 coarse sand :8 graded stone agg. 40 mm nominal size (Crushed) |
| 16 | Providing & laying in position cement conc. of specified grade excld. Cost of centering & shuttering- all work upto plinth level in 1:2:4 (1 cement :2 coarse sand :4 graded stone agg. 40 mm nominal size (Crushed) M-15 Grade PCC |
| 17 | Centering and shuttering including strutting, propping etc. and removal of form work for Foundations, strip raft, plinth band, septic tank, stairs,cable truch wall, plinth protection |
| 18 | Providing and painting of ST Poles with One coat of Red Oxide and two coates of Aluminium Paint to give even shade (reputed brand) |
| 19 | Providing and fixing of Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator (2Nos.), anchor plate (300x 300 x 8 mm), nutbolts,2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete |
| 20 | Note:The material utilized/works executed shall be stritctly as per REC Standards with Latest amendments there off and the quantity in item no. 13 shall vary as per site requirement Please Enable Macros to View BoQ information |