| 1 | Permanent restoration of 33 KV Pampore B.K Pora Line. |
| 2 | Supply and Erection of 11 Mtr. Long Steel Tubular Pole with welded steel base plate (of Designation 410 SP56) and top cap including excavation of pit and back filling by boulders as per REC construction Standard (with latest amendments if any). |
| 3 | Providing and fixing of fabricated GI V cross arm with top bracket, Channel X-arm including belting, clamps and braces angle iron as per site reqirement. |
| 4 | Providng,Laying,stringing ,tensioning and binding of 200 Sqmm ACSR Conductor as per REC construction standard (with latest amendments if any). |
| 5 | Providing and fixing of PG Clamps for 2000 mm² ACSR Conductor. |
| 6 | Supply,installation,testing and commissioning of 33 kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
| 7 | Supply,installation,testing and commissioning of 33 kV Polymeric composite Disc Insulator 36KV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm with fitting |
| 8 | Providing and fixing of Gavanized Nuts & Bolts with washers of sorts as per site requirements. |
| 9 | Providing and fixing of Danger Plates with clamps of standard make |
| 10 | Providing and fixing of Anti Climbing Devices with clamps of standard make |
| 11 | Providing and fixing of Earthing of ST poles Complete by by GI pipe 40mm 3 mtr long through GI strip 25x3mm, as per REC standards. |
| 12 | Providing and painting of ST Poles with One coat of Red Oxide and two coates of Aluminium Paint to give even shade (reputed brand) |
| 13 | Providing and laying of Cement bottoming of 11 mtrs long ST Poles in mix of 1:2:4 using 20mm crushed stone aggregate including shuttering, form work etc as per REC standards 0.66cum/pole. |
| 14 | Supply, Installation, Testing & Commissioning of 33kV Isolator with Earthing Blade (36kV,800A,Outdoor,3 poles,25kA) OF REPUTED MAKE AS PER REC STANDARDS. |
| 15 | Restringing of the existing conductor including opening, tensioning and binding etc complete job |
| 16 | Supply, Installation, Testing & Commissioning of 33 kV Lightening Arrestor Stn. Type (33kV,10kA,Station class,ZnO,Polymer) |
| 17 | Dsmentalling of poles along with allied material and loading, transportation, unloading and stacking at divisional stores Karannagar |
| 18 | Note:The material utilized/works executed shall be stritctly as per REC Standards with Latest amendments there off and the quantity in item no. 15 shall vary as per site requirement Please Enable Macros to View BoQ information |