| 1 | Excavating in trenches not exc 1.5m wide and not exc 1.5m deep and getting out in soft / loose soil complete all as specified and directed |
| 2 | Returning, filling in soft/loose soil, including, spreading, levelling, watering and well ramming in layers not exc. 25cm complete all as specified and directed. |
| 3 | Removing excavated materials (soils) to a distance not exc 50.00 mtr and depositing where directed at a level not exc 1.50 mtr above the starting point , complete all as specified and as directed. |
| 4 | M&L for HDPE Double wall corrugated pipe of size 63/50 mm as per IS: 16098 Part-II-2013 and ISO 21138 & BSEN 13476-1TO 3 laid in trenches/wall for protection cables complete all as specified and directed. |
| 5 | S&F Double wall corrugated pipe coupler for pipe size 63/50 mm all as directed by Engr-in-Charge. |
| 6 | M&L for boring under roads or any other specified location by reqd T&P without disturbing the top surface of the road for insertion of GI Pipe of 50 to 100 mm dia etc complete all as specified and directed. |
| 7 | M&L for tubes 50 mm bore light grade galvanized with all fittings laid in trenches/ wall/ pole through MS flat (25X3 mm), nut, bolt & washers [ where ever reqd ] of proper sizes for protection cables complete all as specified and directed. |
| 8 | Supply, laying, connecting and testing XLPE insulated, PVC sheathed, armoured LT electric power UG cable of size 120 sqmm 3.5 core (heavy duty), aluminium stranded conductor 1100 volts grade, laid through duct/ pipe / in trench etc. including cable glands & lugs complete all as specified and directed. |
| 9 | Supply, laying connecting and testing XLPE insulated, PVC sheathed, armoured LT electric power UG cable of size 16 sqmm 4 core (heavy duty), aluminium stranded conductor 1100 volts grade, laid through duct/ pipe / in trench etc. including cable glands & lugs complete all as specified and directed. |
| 10 | Supply, laying connecting and testing XLPE insulated, PVC sheathed, armoured LT electric power UG cable of size 35 sqmm 4 core (heavy duty), aluminium stranded conductor 1100 volts grade, laid through duct/ pipe / in trench etc. including cable glands & lugs complete all as specified and directed. |
| 11 | Supply, laying connecting and testing XLPE insulated, PVC sheathed, armoured LT electric power UG cable of size 70 sqmm 4 core (heavy duty), aluminium stranded conductor 1100 volts grade, laid through duct/ pipe / in trench etc. including cable glands & lugs complete all as specified and directed. |
| 12 | M&L for cable jointing kit for 1.1KV grade for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core PVC/XLPE armoured aluminium conductor cable of size 70-150 sqmm complete all as specified and as directed. |
| 13 | S&F On-Load Manual Change Over Switch (in sheet steel enclosure) 100 Amps 415 Volts, 4 pole after disconnecting all electrical connection incl. taking down old unsv one complete all as specified and directed. |
| 14 | M&L for earthing complete with copper earth plate electrode 600x600x3.15 mm thick buried directly in ground (earth pit not less than 2.25 m depth below ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to copper strip 20x3mm mm dia by means of brass nut. bolt, washer & protection pipe for earth strip from the earthing plate to the equipments/Panel, (40 mm bore, Light grade), watering pipe from plate to earthing pit (20 mm bore, medium grade), funnel with wiremesh. The earthing pit made up of PCC 1:3:6 type Cl and pit cover made up of 40 mm thick pre cast RCC 1:2:4 type B1 reinforced with 6 mm dia TMT rod and suitable handle of 8mm dia TMT rod incl necessary earth work as shown in SSR Part 1 plate no 5 as specified & directed. |
| 15 | Note: a) The copper strip and protection pipe beyond 7.5 m length shall be measured and paid separately However, earthwork for the same is deemed to be included in this rate. b) The desired value of earth resistance is less than 5 Ohm, on testing after completion if the desired earth resistance is not obtained: the earthing will be redone at no extra cost, otherwise it will not be measured and paid to the contractor. c) Form work of size 0 9m x 0.6m or pouring charcoal & salt is deemed to be included in this rate d) During earth work if surface water found at site. the cost for dewatering through pumpset is deemed to be included in this rate. |
| 16 | Supply, installation, testing and commissioning of isolation transformer outdoor of capacity 100 KVA, three phase, 50Hz copper wound, oil cooled, class of insulation A, metallic body powder coated designed for input voltage range 415 ± 5 % and output voltage range 415 ± 5 %, ratio 1:1, vector group: Dyn 11, efficiency more than 95%, separate neutral bushing shall be brought out for earthing. Potential difference between neutral to earth less than one volt with all standard fittings like, digital temperature meter, lifting hooks one set, Earthing terminals two nos complete all as specified and directed by Engr-in Charge. |
| 17 | M&L for shifting charges for Transporting of Voltage stabilizer 200 KVA capacity from one Location to another Location within 1 KM radius through required T&P at 14 BRD location |
| 18 | Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc, complete all as specified and directed by Engr-in-charge |
| 19 | Material and labour for point wiring for the One light/fan point controlled by one, one way switch with 1.5 Sqmm single core, PVC FRLS insulated unsheathed, multistranded copper conductor drawn through and including PVC casing and caping including necessary accessories like bends, tees, PVC square and elbow etc fixed on wall/ceiling with 1.5 Sqmm PVC FRLSH insulated unsheathed multi stranded copper conductor cable as earth conitinuity (green in colour) connected to common earth dolly including sunken type pressed steel terminal boxes of suitable sizes with plastic laminated white/coloured top sheet cover 3 mm thick complete all as specified and directed. |
| 20 | All as per serial item No 18.00 here in before but for one 3 pin 5 Amp socket outlet on independent board. |
| 21 | All as per serial item No 18.00 here in before but for one 3 pin 5 Amp socket outlet on same board. |
| 22 | Material and labour for Point wiring with 4.0 sqmm FR PVC insulated and sheathed multi stranded (FRLSH) copper conductor cable drawn in PVC casing and Caping on surface wall, ceiling with sunk cast iron/pressed steel terminal boxes of adequate size with suitable thickness plastic laminated sheet, cover for one 3 pin socket outlet 15Amp on independent board including continuous 4.0 sqmm copper conductor cable (FRLSH) (multistranded) PVC insulated and unsheathed Cable as earth wire to common earth dolly, complete all as specified and directed by Engr-in-Charge |
| 23 | Supply and fixing LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete. |
| 24 | Supply and fix DB 8 way MCB SPN double door, glazed type, IP 43 protection,Glazed door, isolated neutral bar,insulated bus bar assembly,mechanical strength of IK09, complete all as specified and directed. |
| 25 | Supply and fix DB 4 way MCB TPN double door, glazed type, IP 43 protection,Glazed door, isolated neutral bar,insulated bus bar assembly,mechanical strength of IK09, complete all as specified and directed. |
| 26 | Supply and fix vertical type ,factory made, sheet enclosure, double door,TPN, 415 V, 8 Way DB, IP54, IK-09 fixed on wall complete with 200 Amps rated copper bus bar, neutral link, dinrail suitable for mounting MCB'S & MCCB'S complete all as specified and directed. |
| 27 | Supply and fix MCCB 125 Amps 415 volts four pole, 10 KA, adjustable overload setting complete all as specified and directed. |
| 28 | Supply & fix in repair of MCB TPN 63 Amps 'C' Series 10 KA, 415 volts complete all as specified and directed. |
| 29 | Supply & fix MCBs single pole (SPN) 6 to 32 Amps with 10 KA breaking capacity of 'C' series in distribution boards confirming to IS/IEC 60898-1 (ISI marked) complete all as specified and directed. |
| 30 | Supply & fix MCBs single pole (SP) 6 to 32 Amps with 10 KA breaking capacity of 'C' series in distribution boards confirming to IS/IEC 60898-1 (ISI marked) complete all as specified and directed. |
| 31 | M&L for Type 1+2 AC Surge Protection Device TP+N (4 Pole), 320 volt, 40KA, withou Remote Signaling, fitted in IP65/66 weather proof Box complete all as specified and directed. |
| 32 | S&F in Replacement of existing sub main wiring with two run of single core (FRLS) PVC insulated and unsheathed cable with copper conductor (Multi strand) having nominal area 4.0 Sqmm drawing into and including PVC casing and caping of adequate size and making electric connections including one run (FRLS) PVC insulated single core copper conductor cable 4.0 Sqmm as a earth continuity conductor(green colour) in and including in non metallic rigid PVC conduit, including cutting chases in brick wall, replastering and making good to match the existing specifications complete all as specified and directed by Engineer-in-Charge. Make: KEI/Havells/Anchor/polycab Note : (i) Rates are deemed to be included chases of sinking for boxes cutting and making holes in wall/floor for passing in or through conduit. (ii) Two run of 4.00 sqmm single core (FRLS) PVC insulated copper conductor cable one run of 4.0 sqmm copper conductor cable (FRLS) as a earth lead and one run of PVC casing caping of suitable size will be measured as one unit. |
| 33 | All as per Sr. Item No. 31.00 here in before but but with 2 run of 6.0 Sqmm and one run of 6.0 Sqmm as earth continuity conductor (green colour) complete all as specified & directed. Note :- (i) Rates are deemed to be included chases of sinking for boxes cutting and making holes in wall/floor for passing in or through conduit (ii) Two run of 6.00 sqmm single core (FRLS) PVC insulated copper conductor cable one run of 6.0 sqmm copper conductor cable (FRLS) as a earth lead and one run of PVC casing caping of suitable size will be measured as one unit. |
| 34 | M&L for Earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried directly in ground (Earth pit not less than 2.25 Metre deep below ground level) with top edge of the plate not less than 1.5 metre below normal ground level, connected to galvanized earth lead wire 4.0 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No.5 of SSR Part-I (2009) including filling of charcoal dust , common salt all around Earth plate upto 150mm, 20mm bore GI medium grade watering pipe, 15 mm bore light grade earth lead protection pipe upto main board, funnel with wiremesh, 40mm thick RCC 1:2:4 type B-1 using 20 mm graded crushed stone aggregate reinforced with suitable handle and angle iron frame and necessary excavation and earth work in any type of soil etc. complete all as specified and as directed including testing on completion. Note: The rate quoted shall inclusive of GI wire 4 mm dia with GI pipe protection 15 mm, light grade up to 7.5 m. |
| 35 | S&F Metal flush Box 3 Module, complete all as specified and directed by Engr-in-charge |
| 36 | S&F Metal flush Box 6 Module, complete all as specified and directed by Engr-in-charge |
| 37 | S&F Metal flush Box 8 Module, complete all as specified and directed by Engr-in-charge |
| 38 | S&F Modular Plate 3 module White cover plate with frame, complete all as specified and directed by Engr-in-charge |
| 39 | S&F Modular Plate 6 module White cover plate with frame, complete all as specified and directed by Engr-in-charge |
| 40 | S&F Modular Plate 8 module White cover plate with frame, complete all as specified and directed by Engr-in-charge |
| 41 | M&L for Modular switch 6 A One way switch white, complete all as specified and directed by Engr-in-charge |
| 42 | M&L for Modular 6 A, 5 pin socket, complete all as specified and directed by Engr-in-charge |
| 43 | M&L for Modular 6 A/16 A socket, complete all as specified and directed by Engr-in-charge |
| 44 | M&L for Modular 16 Amp One way switch white, complete all as specified and directed by Engr-in-charge |
| 45 | M&L for Dummy Plate - 1 Module Oro (White), complete all as specified and directed by Engr-in-charge |
| 46 | S&F Multi compartment cable duct made of stainless steel material (18 SWG) having size in Width (200 MM), base height (40MM), cover Height (200 mm) with suitable coupler plates with allied hardware all as directed by Engr-in Charge. |
| 47 | Supply, installation, testing and commissioning of isolation transformer of capacity 2 KVA single phase, 50 Hz, indoor type, copper wound, Air cooled, class of insulation A, metallic body powder coated designed for input voltage range 240 ± 5 % and output voltage range 240 ± 5 %, ratio 1:1, efficiency more than 95%, Potential difference between neutral to earth less than one volt with all standard fittings like, digital temperature meter, complete all as specified and directed by Engr-in Charge. |
| 48 | Material & labour for Sub main wiring with two runs of single core 1.5 Sqmm (Nominal Area) FRLS PVC insulated and unsheathed multi standed copper conductor cable LT 1100 volts grade drawn thorugh into PVC non metallic rigid conduit concealeed including PVC insulated stranded copper conductor nominal cross section area as under as contineous earth continuity wire complete all as specified. Two run of 1.5 Sqmm cable one runs of 1.5 Sqmm earth continuity wire and one run of conduit for connection to DBs/dolly shall be deemed to be included in this item and shall be measured as one run complete all as specified and directed. |
| 49 | S&F for Energy saving, environmental friendly, long life, exclusive innovative die-casting aluminium IP66 Highbay light of 55/50 watt capacity with suitable hook/clamp mounting on ceiling/wall, suitable for highlighting architectural facade and general purpose lighting complete Make : Havells Cat No-EMBERROULTRAHBP055WLED757PWBTORLBLK equivalent make in Wipro/Orient. Please Enable Macros to View BoQ information |