Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Electrical Work Related Items |
| 2 | Supply, Installation, Testing & Commissioning of SS 316 Niche Light 12V 15Watt RGBW (3watt x 5Nos Led) With Niche Standard etc., complete |
| 3 | Supply, Installation, Testing & Commissioning of Power Supply, |
| 4 | Supply, Installation, Testing & Commissioning of RGBW Controller, |
| 5 | Supply, installation, testing and commissioning of single stage/Horizontal Openwell submersible pump 5HP |
| 6 | Supply, installation, testing and commissioning of single stage/Horizontal Openwell submersible pump 1HP |
| 7 | 415V LT PANELS : - Design, fabrication, assembling, wiring & supply, installation, testing & commissioning of MV Panels fabricated out of 2mm thick for structural members (Load bearing members) and 1.6mm thick for door and covers (Non load bearing members) CRCA painted sheet steel in cubicle formation with reinforcement of suitable size angle iron, channels, T irons, flats wherever necessary for large meter boards. Cable gland plates shall be provided at top and bottom both and windows for meter reading, locking arrangement (pad-lock & seal) with wiring upto KWH meter & meter to MCB shall be done by using adequately rated flexible single core copper wire. The boards shall be treated with all anticorrosive process before painting as per standards with final approved shade of powder coated as approved, 2 nos. earthing terminals shall be provided for all panels. The boards shall be suitable for 415 V, 3 phase, 4 wire, 50 Hz supply system. Boards shall be fabricated in length, height, depth etc to match with site conditions. An approval shall be taken for each panel before manufacturing. Galvanised hardwares with zinc passivation shall be used in fabrication of boards. Note: The following provisions shall be required to be made in the switchboard detailed below. The Switchboard shall have provision for entry of all PVCA cables from the top/bottom as required. All live accessible parts shall |
| 8 | be shrouded and all equipment shall be finger touch proof. The busbar insulation shall be with heat shrinkable sleeves. SMC/DMC shrouds and busbar supports shall be used. Suitable tinned copper extension links for incoming/outgoing cables shall be provided wherever required. Control circuits includes breaker control switch, auto manual selector switch, anti pumping relay, spring charging trip indication, TIMER, control wiring, Auxiliary contactors MCB’s as required at site. Positive isolation of all breakers. All fault level breaking capacity indicates shall be IC.S value at 415 volts (ICS = ICU = ICW = 100%). Space Heater/ light/air filter shall be provided for each vertical compartment. Padlocking facility shall be provided on all outgoing feeders. All ACB’s shall have all standard accessories such as CT’s, Arc Chute, Safety Shutters etc. All inter Panel wiring from PLC to DG / Transformer / Bus Couplers as required. Link and drops from ACB/MCCB shall be designed for full rated current of ACB/MCCB ratings at same current density as of Main Bus Bar 2 nos. GI earth strip throughout the panel. |
| 9 | MAIN LT Panel CUM CHANGE OVER PANEL (35 kA)630 KVA TRANSFORMER - INCOMER#1: - 1000 amps 4 pole EDO type air circuit breaker with microprocessor release unit for short circuit, over current and earth fault protection with adjustable setting as per specification. (From Transformer. 1500A, TPN Al. Bus Bar of suitable length having Current density 1Amp/sq.mm & having high conductivity electrical grade suitable to withstand symmetrical fault level of 35 kA. Neutral busbar shall be of 100% capacity. 3 Nos. Cast resin CTs of dual ratio 1000 / 5 Amps CL:1 ( For Metering) , 5P20( For protection) , 15 VA. 3 Nos. Cast resin CTs of dual ratio 1000 / 5A Amps CL:PS for REF protection R-Y-B indication Lamp , Trip Circuit Healty and Breaker ON-OFF - Trip Indication Lamp Over Voltage relay (59) And Under Voltage relay (27) with time delay Instantaneous Over current relay (50)Time delay earth fault relay (51) Instantaneous earth fault relay (50N)Time delay phase over current relay (51N), Energy Analyser having 30 Days Memory, Digital voltmeter with inbuilt selector switch- 2 set, Digital Ammeter with inbuilt selector switch- 2 set, Digital Frequency Meter, Power factor Meter, Trip Circuit Supervision Relay , Master Trip Relay, REF relay , 24 V DC Shunt trip coil. - 2Set, 1000/5A CT for APFCR- 2set, Breaker control switch (TNC), Auxiliary contacts required for necessary interlocking of breakers. 32A |
| 10 | TP MCCB for OLTC, 20A TP MCCB with 5 KVAR fixed type capacitor and Annunciation with test and reset for fault indication, 500KVA DG Set 1- INCOMER#2 (With AMF Logic & Control):- 1 Nos. 1000 amps 4 pole EDO type air circuit breaker with microprocessor release unit for short circuit, over current and earth fault protection with adjustable setting as per specification and each with following accessories: 3 Nos. Cast resin CTs of ratio 1000 / 5 Amps CL:1 ( For Metering) , 5P20( For protection) , 15 VA., R-Y-B indication Lamp , Trip Circuit Healty and Breaker ON-OFF - Trip Indication Lamp , Instantaneous Over current relay (50)Time delay earth fault relay (51), Over Voltage relay (59) And Under Voltage relay (27) with time delay, Instantaneous Over current relay (50) Voltage control Time delay over current relay (51V), Multi Function meter for measurement of Voltage, Currents, PF,Energy Power & Harmonics, Trip Circuit Supervision Relay (95), Reverse Power Relay, 24 V DC Shunt trip coil. - 1 Set, Breaker control switch (TNC), Auxiliary contacts required for necessary interlocking of breakers. Battery Charger for DG batteries with DC meters , selector switches etc as required, 8 Window Annunciation with push Buttons as required Micro PLC without display for interlocking of breakers. The features of AMF logic, Auto/manual/test, start/stop, EM stop operation including 3 attempt start feature, idle running timer, |
| 11 | resumption of power supply after some time when EB supply has come back, shall be provided and integrated in the DG breaker cubicle. Set of relays, timer, Aux. Contactor etc as required for meeting the requirement of successful AMF shall be provided. , 180KVA DG Set 2- INCOMER#3 (With AMF Logic & Control), 1 Nos. 630 amps 4 pole EDO type air circuit breaker with microprocessor release unit for short circuit, over current and earth fault protection with adjustable setting as per specification and each with following accessories: 3 Nos. Cast resin CTs of ratio 630 / 5 Amps CL:1 ( For Metering) , 5P20( For protection) , 15 VA. R-Y-B indication Lamp , Trip Circuit Healty and Breaker ON-OFF - Trip Indication Lamp. Over Voltage relay (59) And Under Voltage relay (27) with time delay. Instantaneous Over current relay (50)Time delay earth fault relay (51). Instantaneous Over current relay (50) Voltage control Time delay over current relay (51V). Multi Function meter for measurement of Voltage, Currents, PF,Energy Power & Harmonics. Trip Circuit Supervision Relay (95). Reverse Power relay. 24 V DC Shunt trip coil. - 1 Set. Breaker control switch (TNC). Auxiliary contacts required for necessary interlocking of breakers. Battery Charger for DG batteries with DC meters , selector switches etc as required. 8 Window Annunciation with push Buttons as required . Micro PLC ( without display) shall be used for necessary interlocking breakers |
| 12 | The features of AMF logic, Auto/manual/test, start/stop, EM stop operation including 3 attempt start feature, idle running timer, resumption of power supply after some time when EB supply has come back, shall be provided and integrated in the DG breaker cubicle. Set of relays, timer, Aux. Contactor etc as required for meeting the requirement of successful AMF shall be provided. BUS COUPLER: - 1 Nos. 1000 amps 4 pole EDO type air circuit breaker with microprocessor release unit for short circuit, over current and earth fault protection with adjustable setting as per specification and with following accessories: Breaker ON/ OFF/ TRIP indicating lamps, 24 V DC Shunt trip coil. - 1 Set, 240 V AC under voltage release. - 1 Set, Breaker control switch (TNC), Auxiliary contacts required for necessary interlocking of breakers.. Bus Bar section -I : 1500A, TPN Al. Bus Bar of suitable length having Current density 1Amp/sq.mm & having high conductivity electrical grade suitable to withstand symmetrical fault level of 35 kA. Neutral busbar shall be of 100% capacity.. Outgoings section-I: - 1 No. 630 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release unit for short circuit and over current and with Dual type Tarrif Meter for measuring DG and Elec board power saparately and with CTs and Control MCB as required. 1 No. 630 Amps TP |
| 13 | Moulded Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release unit for short circuit and over current and with CTs and Control MCB as required for Capacitor Panel.. , 3 Nos. 400 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release unit for short circuit and over current and with Dual type Tarrif Meter for measuring DG and Elec board power saparately and with CTs and Control MCB as required. 3 Nos. 160 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release unit for short circuit and over current and with Dual type Tarrif Meter for measuring DG and Elec board power saparately and with CTs and Control MCB as required. 3 Nos. 100 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release unit for short circuit and over current and with Dual type Tarrif Meter for measuring DG and Elec board power saparately and with CTs and Control MCB as required. Bus Bar section -II : : - 1500A, TPN Al. Bus Bar of suitable length having Current density 1Amp/sq.mm & having high conductivity electrical grade suitable to withstand symmetrical fault level of 50 kA. Neutral busbar shall be of 100% capacity. |
| 14 | Outgoings section-II: - 1 No. 630 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release release unit for short circuit and over current and with Dual type Tarrif Meter for measuring DG and Elec board power saparately and with CTs and Control MCB as required, 1 No. 400 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release unit for short circuit and over current and with Dual type Tarrif Meter for measuring DG and Elec board power saparately and with CTs and Control MCB as require, 2 Nos. 160 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release unit for short circuit and over current and with Dual type Tarrif Meter for measuring DG and Elec board power saparately and with CTs and Control MCB as require, 5 No. 100 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release unit for short circuit and over current and with Dual type Tarrif Meter for measuring DG and Elec board power saparately and with CTs and Control MCB as require. Main LT Panel Cum Change Over Panel as described above complete with specifications and enclosed SLD |
| 15 | CAPACITOR PANEL 225 kVAR ( 35kA) Incoming: - 1 Nos. 630 amps 3 pole MDO type air circuit breaker and complete with :- 3 Set of 630 /5A for , CL-1.0, 15VA measuring CTs for Metering . Square flush mounted digital Ammeter of 96 mm sq. scaled 0-630 amps with 3 way and OFF selector switch, 1 Set of phase indicating lamps with MCB., Terminals to receive XLPE insulated cable. 14 step APFCR relay microprocessor based to sense and monitor the system power factor and provide impulses for operation of 6 sequential capacitors circuits. Power factor meter ( digital ) Bus bars: - |
| 16 | 800A, TPN Al. Bus Bar of suitable length having Current density 1Amp/sq.mm & having high conductivity electrical grade suitable to withstand symmetrical fault level of 50 kA. Neutral busbar shall be of 100% capacity. Outgoings : - 2 Nos 125 A TP MCCB each complete with 150A AC 3 duty TP contactor ( suitable for automatic switching of 50 kVAR Capacitor bank) with indicating lamps to give status of circuit , 50 kVAR Hermetically sealed MPP-H type capacitors with fuse protection , discharge resistors , interconnections , set of push buttons red and green for mannual operation of capacitor units , A/M selectors switch etc. as required. 5 Nos 63 A TP MCCB each complete with 80A AC 3 duty TP contactor ( suitable for automatic switching of 25 kVAR Capacitor bank) with indicating lamps to give status of circuit , 25 kVAR Hermetically sealed MPP-H type capacitors with fuse protection , discharge resistors , interconnections , set of push buttons red and green for mannual operation of capacitor units , A/M selectors switch etc. as required. 220 kVAR Capacitor Panel as described above complete with specifications and enclosed SLD. |
| 17 | MDB-1 Incoming: - 1 Nos. 400A, TPN MCCB (35KA) with thermal magnetic release having overload and short circuit protection. (Ics=100% Icu) and with following:- Metering & Indication: - 6 - Parameter Energy Analyser having 30 Days Memory with 3 No. 63/5A cast resin type CL: 1.0 CTs and MCB, R-Y-B and ON/OFF indication lamps for incomer with control MCB. Bus Bar:: - 500A, TPN Al. Bus Bar of suitable length having Current density 1Amp/sq.mm & having high conductivity electrical grade suitable to withstand symmetrical fault level of 35 kA. Neutral busbar shall be of 100% capacity. Outgoings:: - 20 Nos. 25 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release unit for short circuit and over current , 2 Nos. 60 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release unit for short circuit and over current. 3 Nos. 40 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release unit for short circuit and over current, 18 Nos.DOL Starters, suitable for suitable motor, complete with thermal range as per Type-II co-ordination chart. (Ventilation Fans), 1 No.Star Delta Starters, suitable for suitable motor, complete with thermal range as per Type-II co-ordination chart. (Ventilation Fans). MDB-1( Ventilation Fans) as described above and complete as per enclosed SLD. |
| 18 | MDB-2 : - 1 Nos. 160A, TPN MCCB (25KA) with thermal magnetic release having overload and short circuit protection. (Ics=100% Icu) and with following:- Metering & Indication : - 6 - Parameter Energy Analyser having 30 Days Memory with 3 No. 100/5A cast resin type CL: 1.0 CTs and MCB, R-Y-B and ON/OFF indication lamps for incomer with control MCB. Bus Bar:: - 200A, TPN Al. Bus Bar of suitable length having Current density 1Amp/sq.mm & having high conductivity electrical grade suitable to withstand symmetrical fault level of 25 kA. Neutral busbar shall be of 100% capacity. Outgoings:- 2 Nos. 25 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release unit for short circuit and over current, 6 Nos. 63 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release unit for short circuit and over current, 4 Nos. 63 Amps 4P Moulded Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release unit for short circuit and over current with 63A 4P RCCB's, 2 Nos. DOL Starters, suitable for suitable motor, complete with thermal range as per Type-II co-ordination chart. (Ventilation Fans). MDB-2 (Ground, Floor) as described above and complete as per enclosed SLD, |
| 19 | MDB-3 :Incoming: - 1 Nos. 160A, TPN MCCB (25KA) with thermal magnetic release having overload and short circuit protection. (Ics=100% Icu) and with following:- Metering & Indication : - 6 - Parameter Energy Analyser having 30 Days Memory with 3 No. 160/5A cast resin type CL: 1.0 CTs and MCB, R-Y-B and ON/OFF indication lamps for incomer with control MCB. Bus Bar:: - 200A, TPN Al. Bus Bar of suitable length having Current density 1Amp/sq.mm & having high conductivity electrical grade suitable to withstand symmetrical fault level of 25kA. Neutral busbar shall be of 100% capacity. Outgoings:: - 1 Nos. 100 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release unit for short circuit and over current , 5 Nos. 63 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release unit for short circuit and over current , 2 Nos. 25 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release unit for short circuit and over current , 2 Nos. DOL Starters, suitable for suitable 5.5 Kw motor, complete with thermal range as per Type-II co-ordination chart. (Ventilation Fans). MDB-3 (First Floor) as described above and complete as per enclosed SLD. |
| 20 | SDB-3.1 (Second Floor) Incoming: - 1 Nos. 100A, TPN MCCB (25KA) with thermal magnetic release having overload and short circuit protection. (Ics=100% Icu) and with following:- Metering & Indication : - 6 - Parameter Energy Analyser having 30 Days Memory with 3 No. 250/5A cast resin type CL: 1.0 CTs and MCB, R-Y-B and ON/OFF indication lamps for incomer with control MCB. Bus Bar: - 150A, TPN Al. Bus Bar of suitable length having Current density 1Amp/sq.mm & having high conductivity electrical grade suitable to withstand symmetrical fault level of 25 kA. Neutral busbar shall be of 100% capacity. Outgoings: 5 Nos. 60 Amps TPN Moulde Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release unit for short circuit and over current, 2 Nos. 25 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release unit for short circuit and over current , 2 Nos. DOL Starters, suitable for suitable 5.5Kw motor, complete with thermal range as per Type-II co-ordination chart. (Ventilation Fans). SDB-3.1 (Second Floor) as described above and complete as per enclosed SLD. |
| 21 | MDB-4 (Third Floor) Incoming : - 1 Nos. 160A, TPN MCCB (25KA) with thermal magnetic release having overload and short circuit protection. (Ics=100% Icu) and with following:- Metering & Indication: - 6 - Parameter Energy Analyser having 30 Days Memory with 3 No. 250/5A cast resin type CL: 1.0 CTs and MCB, R-Y-B and ON/OFF indication lamps for incomer with control MCB. Bus Bar: 200A, TPN Al. Bus Bar of suitable length having Current density 1Amp/sq.mm & having high conductivity electrical grade suitable to withstand symmetrical fault level of 25 kA. Neutral busbar shall be of 100% capacity. Outgoings: 5 Nos. 60 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release unit for short circuit and over current, 1 Nos. 100 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release unit for short circuit and over current, 2 Nos. 25 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release unit for short circuit and over current, 2 Nos. DOL Starters, suitable for suitable 5.5Kw motor, complete with thermal range as per Type-II co-ordination chart. (Ventilation Fans). MDB-4 (Third Floor) as described above and complete as per enclosed SLD. |
| 22 | SDB-4.1 (Fourth Floor) Incoming: - 1 No. 100A, TPN MCCB (25KA) with thermal magnetic release having overload and short circuit protection. (Ics=100% Icu) and with following:- Metering & Indication : - 6 - Parameter Energy Analyser having 30 Days Memory with 3 No. 200/5A cast resin type CL: 1.0 CTs and MCB, R-Y-B and ON/OFF indication lamps for incomer with control MCB. Bus Bar: - 150A, TPN Al. Bus Bar of suitable length having Current density 1Amp/sq.mm & having high conductivity electrical grade suitable to withstand symmetrical fault level of 25 kA. Neutral busbar shall be of 100% capacity. Outgoings: - 5 Nos. 60 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release unit for short circuit and over current, 2 Nos. 25Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release unit for short circuit and over current, 2 Nos. DOL Starters, suitable for suitable 5.5Kw motor, complete with thermal range as per Type-II co-ordination chart. (Ventilation Fans). SDB-4.1 (Fourth Floor) as described above and complete as per enclosed SLD |
| 23 | MDB-Lift Panel: Incoming: - 1No. 125A 4 pole manual change over switch. 1Nos. 125A, TPN MCCB with thermal magnetic release having overload and short circuit protection. (Ics=100% Icu) and with following: - Metering & Indication : - 6 - Parameter Energy Analyser having 30 Days Memory with 3 No. 250/5A cast resin type CL: 1.0 CTs and MCB, R-Y-B and ON/OFF indication lamps for incomer with control MCB. Bus Bar:: - 200A, TPN Al. Bus Bar of suitable length having Current density 1Amp/sq.mm & having high conductivity electrical grade suitable to withstand symmetrical fault level of 25 kA. Neutral busbar shall be of 100% capacity. Outgoings:: - 4 Nos. 60 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release unit for short circuit and over current. 1 No. 40 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in Thermal Magnetic based release unit for short circuit and over current. MDB-Lift Panel as described above and complete as per enclosed SLD. |
| 24 | MDB-UPS (Basement UPS Room) Incoming: - 2 Nos. 125A, FP MCCB with thermal magnetic release having overload and short circuit protection. (Ics=100% Icu) and with following:- Metering & Indication , 6 - Parameter Energy Analyser having 30 Days Memory with 3 No. 250/5A cast resin type CL: 1.0 CTs and MCB (2 set), R-Y-B and ON/OFF indication lamps for incomer with control MCB (2 set). Bus coupler: 1 No. 125A, FP MCCB with thermal magnetic release having overload and short circuit protection. (Ics=100% Icu) with both Bus with mechanical Interlocking. Bus Bar:- 20A, TPN Al. Bus Bar of suitable length having Current density 1Amp/sq.mm & having high conductivity electrical grade suitable to withstand symmetrical fault level of 25 kA. Neutral busbar shall be of 100% capacity. Outgoings:- 18Nos. 63A, FP MCCB with thermal magnetic release having overload and short circuit protection. (Ics=100% Icu) and with following:- MDB-8 UPS as described above and complete as per enclosed SLD |
| 25 | EXTERNAL LIGHTING FEEDER PILLAR (10 kA): - Design, fabrication, supply of Feeder Pillar fabricated out of 2mm thick for structural members (Load bearing members) and 1.6mm thick for door and covers (Non load bearing members) CRCA sheet in cubicle compartmentalize free standing floor mounted, dust and vermin proof outdoor type double door with reinforcement of suitable size angle iron, channel 'T' irons and / or flats wherever necessary. Cable gland plates shall be provided at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications with 2 coats of PU paint primer and final approved shade of PU paint coating. 2 Nos. earthing terminals shall be provided for all distribution panels. Panels shall be suitable for 415V, 3-phase, 4-wire, 50Hz supply system and with 15% spare space, lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel before fabrication. Galvanized hardwares with zinc passivation shall be used in fabrication of panels. INCOMING: - 1 no. 63 Amp TPN MCCB, 10 KA with thermal magnetic protective releases. 1 no 24 hrs programmable timer & contactor complete for automatic operation of external lighting. 1 set of phase indicating lamps with MCB. BUSBAR : - 100 Amp FP aluminium busbars (Current Density 1A/Sq.mm) with 100% neutral. OUTGOING : - 12 nos. 20A/25A amp DP MCB, 10 KA with thermal magnetic protective releases. |
| 26 | Installation, testing and commissioning External lighting Feeder Pillars as mentioned in item No. 1 above fabricated out of 2mm thick for structural members (Load bearing members) and 1.6mm thick for door and covers (Non load bearing members) CRCA sheet in cubicle compartmentalize free standing floor mounted, dust and vermin proof outdoor type double door including providing & making brick masonry foundation (including plastering etc.) of suitable size with all fixing accessories as required. |
| 27 | TELEPHONE, DATA and TV:: - Providing, fixing, connecting and testing of following pair solderless telephonetag block, with powder coated box (Krone make ) of required size box with hinged lockable cover and clamps for dressing of wires etc as required. |
| 28 | 100 Pair box |
| 29 | 50 Pair box |
| 30 | 10 Pair box |
| 31 | Supply and laying of following 0.61mm dia annealed tinned copper conductor PVC insulated and PVC sheathed unarmoured telephone cable in existing conduit in concealed/ surface system complete as required |
| 32 | 100 pair Cable |
| 33 | 50 pair Cable |
| 34 | 10 pair Cable |
| 35 | Providing, fixing, connecting, testing and commisssioning of zinc passivated box with moulded plate in recess or on surface moulded type with following including all necessary materials etc. as required. |
| 36 | Computer terminal (RJ-45) |
| 37 | 2 Pair telephone cord outlet (RJ-11) |
| 38 | TV antina Socket outlet |
| 39 | FIRE ALARM SYSTEM (ADDRESSABLE TYPE)- |
| 40 | Supply, Installation , Testing & Commissioning of Microprocessor based (1 +1 reduntant) panel , Networkable analogue addressable type single cabinet fire alarm control panel with Touch screen/ LCD display with with minimum history of 2 X 1000 event. The panel shall be equipped with sufficient numbers of loop with 10-20% spare capacity with each loop and shall have a capacity of 99/99 of analogue detector /devices in one loop. The panel shall have dedicated control for controlling of dampers, smoke curtains, AHUs, pressurization fans, ventilation fans at fire pump room, monitoring of fire sprinkler and fire hydrant pump, 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working conditions as required in EN standard and respective NBC. The Panel shall have BACKNET & MODBUS CARD integration . The complete panel assembly shall come with 1+1 redundancy at all level loop cards, CPU, network card, display, power supply as well as shall have integrated voice evacuation . Panel shall be EN complied VDS /LPCB/BRE approved or NFPA complied UL/FM. 4 loop. Make:- Noburn/Wrexham/Pyrotynex |
| 41 | Supply, Installation , Testing & Commissioning of Automatic Analog addressable VDS/LPCB/UL/FM approved with respective standard of Smoke detector, having fault Isolators integrated in detector for maintaining operational availability of all elements in the loop, even in the event of a short circuit & detector shall have sensitivity as automatic drift compensation type at variable environment, with mounting based LED, Address Switch / electronic address to programme the detectors, complete as required.In case detector isnot with inbuilt fault isolator, Fault isolator module shall be provided with each and individual detector.Make : Autronica Hampton/Gamewell/Notifier-3030 series |
| 42 | Supply, Installation , Testing & Commissioning of Automatic Analog addressable VDS/LPCB/UL/FM approved with respective standard of Heat detector, having fault Isolators integrated in detector for maintaining operational availability of all elements in the loop, even in the event of a short circuit & detector shall have sensitivity as automatic drift compensation type at variable environment, with mounting based LED, Address Switch / electronic address to programme the detectors, complete as required. In case detector isnot with inbuilt fault isolator, Fault isolator module shall be provided with each and individual detector.Make : Autronica Utc/Hampton/Gamewell /Notifier-3030 series |
| 43 | Supply, Installation, Testing and Commissioning of Beam Detector. The beam detector shall be used for High Ceiling application with a detection range upto 50- 70 mtrs sensitive settings. Make : Autronica Utc/Hampton/Gamewell/Notifier-3030 series |
| 44 | Supply, Installation , Testing & Commissioning of Response Indicator which consists of steady glowing LED. This LED shall be mounted within a box and connected in parallel to the built in indicator of the detector as per specifications. The RI shall come \\"ON\\" as soon as the detector activates complete in all respects as per specification.The RI shall be of same make as of panel. Make : Autronica Utc/Hampton/Gamewell/Notifier-3030 series |
| 45 | Supply, Installation , Testing & Commissioning of Addressable type VDS/LPCB/UL/FM approved with respective standard of addressable manual call (pull type) Station with inbuilt fault isolator complete with all accessories as per specifications. In case device isnot with inbuilt fault isolator, Fault isolator module shall be provided with each and individual device. Make : Autronica Utc/Hampton/Gamewell/Notifier-3030 series |
| 46 | Supply, Installation, Testing & Commissioning of VDS/LPCB/UL/FM approved with respective standard of loop powered addressable Sounders cum flasher with inbuilt fault isolator base at 90-100db .to notify Occupants for fast & safe Evacuation as specified.In case if sounder cum flasher isnot loop powered, the cable and its acessories required to provide power supply to sounder cum flasher shall be inclusive. Make : Autronica Utc/Hampton /Gamewell/Notifier-3030 series |
| 47 | Supplying and installation of Exit Signs: photo luminescent safety signage made up of photo luminescent material of rare earth aluminates, non radioactive working on the principle of high processed on 1.2 mm thick aluminum sheet including arrangement for fixing on wall / ceiling etc. complete as required (single sided) (size 150 mm x 300 mm). Make:- Evenlite/Hampton/Verbatim |
| 48 | Supplying and fixing of following sizes of STEEL conduit alonwith the accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. Make:- AKG/BEC |
| 49 | 20mm dia |
| 50 | 25mm dia |
| 51 | 32mm dia |
| 52 | Supplying and drawing of following sizes of Low Smoke Zero Halogen Silicon Insulated Fire Survival Cable with Drain Wire, solid copper conducter cable approved by LPCB as per BSEN 50200:2015 PH 120 (Fire, Mech Shock & Water 120 Minutes @ 830 deg Celcius, Fire & Mech Shock every 5 Min for 2 Hours- Both test conducted on same sample) and BS-6387 CWZ The cable shall sustain 950 deg. C. The cable shall be approved for. The cable shall be BS EN 60332-1-2:2004 for Bunched Flame Retardancy (installed as a single or bunched cable self extinguishes leaving the upper cable sheath unaffected showing the cable does not propagate fire). Cable shall be guaranteed for 10 years from the date of manufacture marked on the cable. 2 X 1.5 sq. mm Make:- Noburn/Wrexham/Pyrotynex |
| 53 | PUBLIC ADDRESS SYSTEM |
| 54 | Supplying, installing, testing and commissioning of Voice Evacuation Master controller with built in Amplifier. The System have Built in 500W Amplifier and it should be capable for the EVAC, Paging, PA and BGM functions. The Controller have SD card option to store the EVAC and Alert Voice Message. The Controller have Speaker line supervision record out and amplifier auto changeover. The Controller have following features: Separate Zone volume control at the front side of panel, Status indications on the Panel for EVAC,Fault ,AC,DC ,Fault, ALERT & Fireman mic, Zone capacity up to 96 Zones, 8 programmable Control Input and output, Fireman Microphone with High Priority, Frequency response 80Hz - 20kHz, 25V/70V/100V Class-AB Speaker Output. In capacity of individual or sum of amplifier wattage shall be 500W.The acessories required to sum of these amplifier to 500W shall also be inclusive in this. Make : Autronica Utc/Hampton/Gamewell/Notifier-DAA series |
| 55 | Supplying, installation, testing & commissioning of 1.5/3/6W metal box ceiling/wall speakers complete as required. Make : Autronica Utc/Hampton /Gamewell /Notifier-L serires |
| 56 | Supplying, installing, testing and commissioning of 12 zone paging microphone (call station) with necessary Zone wise, Group Zones and all call facility. The Microphone should have LED Indication, Can be Expand with additional units, Compress function through microphone input to avoid distortion, Auxiliary input which supply local background music. Power 24V DC, Microphone should be able to Control the Music also. Microphone Should supply with all accessaries and with standard specification, complete. Make : Autronica Utc/Hampton/Gamewell/Notifier-3030 series |
| 57 | Supplying and drawing of following sizes of Low Smoke Zero Halogen Silicon Insulated Fire Survival Cable with Drain Wire, solid copper conducter cable approved by LPCB as per BSEN 50200:2015 PH 120 (Fire, Mech Shock & Water 120 Minutes @ 830 deg Celcius, Fire & Mech Shock every 5 Min for 2 Hours- Both test conducted on same sample) and BS-6387 CWZ The cable shall sustain 950 deg. C. The cable shall be approved for. The cable shall be BS EN 60332-1-2:2004 for Bunched Flame Retardancy (installed as a single or bunched cable self extinguishes leaving the upper cable sheath unaffected showing the cable does not propagate fire). Cable shall be guaranteed for 10 years from the date of manufacture marked on the cable. 2 X 1.5 sq. mm. Make:- Noburn /Wrexham/Pyrotynex |
| 58 | Supply and laying 32mmX5 MM GI strip at 0.50 meter below ground as strip earth electride including soldering etc as required |
| 59 | Supply and laying 32mmX6 MM GI strip at 0.50 meter below ground as strip earth electride including soldering etc as required |
| 60 | Providing and fixing 25 mm X 6 mm GI strip on surface or in recess for down conductor for lightning system. as required. |
| 61 | Providing and fixing 25mm X 3mm G.I. strip on surface or in recess on Terrace for Lightning etc. as required. |
| 62 | Providing and fixing of Single core 35 sqmm dia Cu. Green colour cable. |
| 63 | Providing and fixing of Single core 16 sqmm dia Cu. Green colour cable. |
| 64 | Supply ans laying of GI pipe under road/paved area crossing etc. including excavation back filling ramming and making good. |
| 65 | 100mm Dia pipe |
| 66 | 150mm Dia pipe |
| 67 | Providing and fixing earth bus of 50mmX 5mm copper strip on surface for connections etc. as required, Impulse current (10/350 micro sec) = 103 KA, Charge (Q) = 54.9 A.s, Specific Energy (W/R) = 2.5 MJ/Ω. |
| 68 | Suppy , installation, testing, Design, manufacture, supply inspection, handling, assembling, affecting proper connections, testing and commissioning of 2mm CRCA sheet steel fabricated cubical type Main L.T. Panel floor mounting, dust & vermin proof, front operated construction, enclosure class - IP 52, TTA Type, with proper treatment with 9 tank process with top/bottom removable gland plates, as required, double compression type cable glands, earth bus, hinged and lockable doors to achieve dust and vermin proof complete with all inter connections small wiring by min. 2.5 sq. mm. FRLS copper wires, ckt labels etc. The panel feeders shall be suitable for terminating suitable nos. 3.5 / 4 core armoured aluminium cable as required. Panel Should Be Internal Arc tested at 50ka for .3 sec as per IEC61641. |
| 69 | (Under no case temperature of main LT panel shall be more at any point of the panel. To avoid heating necessary exhaust fans shall have to be provided along with top louvers). |
| 70 | Degree of protection IP-42 |
| 71 | The internal control wiring shall fuse less. All control wiring and metering protection shall be by MCB's. |
| 72 | Colour: Siemens Gray Powder Coated or as per approved shade. |
| 73 | INCOMER FROM 160 KVA OUTDOOR TRANSFORMER - 1 Nos each having following |
| 74 | 1 Nos. 400 amps four pole MCCB of fault breaking capacity 50 KA (Ics=Icu) fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicator and frame earthing contact ,confiming to IS 13947-2 1993 as amended upto date complete with following Accessories. |
| 75 | 1 set of 3 CT's of ratio 400/5A, Class 1.0 accuracy 15 VA burden for APFCR. |
| 76 | Independent manual spring closing mechanism - 1 No. |
| 77 | Microprocessor release (EMI and EMC certified) for over current, earth fault and short circuit protection - 1Set . |
| 78 | Multifunction meter with selector switch with suitable CT's and back up MCBs. |
| 79 | The instrument chamber shall be separate and shall comprise of flush type ammeter, voltmeter, selector switches, cast resin type CT's & PT's, etc. Separate CT's shall be provided for protective and measuring system and for APFCR of capacitor bank with suitable VA. |
| 80 | 3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB , circuits as per standatd practice , auxiallry contact for positive interlocking of the breakers as required. |
| 81 | Shunt trip coil 220 Volt AC. |
| 82 | INCOMER FROM DG SET (62.5 KVA) - 1 Nos each having following only switchgear provision in LT Panel if DG Set required |
| 83 | 1 Nos. 200 amps four pole MCCB of fault breaking capacity 50 KA (Ics=Icu) fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicator and frame earthing contact ,confiming to IS 13947-2 1993 as amended upto date complete with following Accessories. |
| 84 | 1 set of 3 CT's of ratio 200/5A, Class 1.0 |
| 85 | Independent manual spring closing mechanism - 1 No. |
| 86 | Microprocessor release (EMI and EMC certified) for over current, earth fault and short circuit protection - 1Set . |
| 87 | Multifunction meter with selector switch with suitable CT's and back up MCBs. |
| 88 | Protection releases with LSIG and Over voltage ,under voltage,Reverse power protection Relay & Metering & Accessories for each D G set incomers |
| 89 | 3 Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB , circuits as per standatd practice , auxiallry contact for positive interlocking of the breakers as required . |
| 90 | Shunt trip coil 220 Volt AC. |
| 91 | 1 nos battery charger with DC voltmeter and ammeter suitable for the DG sets (62.5 KVA) |
| 92 | INTERLOCKING |
| 93 | Interlocking logic electrical Interlocking between incomers and bus coupler and it should have auto start and auto trip facility for Automatic Operation of The Breakers With Manual Over Rid Facility. |
| 94 | BUS COUPLER |
| 95 | One Number 400A 4 pole edo ACB as Bus Coupler with ON/OFF Indication. |
| 96 | BUS BAR |
| 97 | 500A TPN Aluminium bus bar with heat Shrink Sleeve |
| 98 | OUTGOING |
| 99 | ALL THE MCCB'S SHALL BE EQUIPPED/ PROVIDED WITH ALL ACCESSORIES & IN BUILT PROTECTION RELEASES |
| 100 | 1 Nos. 160 AMPS TP+N MCCB |
| 101 | 4 No. 125A 50KA 4P MCCB with Microprocessor Based Releases, ON Indication, with selector switch, matching cast resin CT's. |
| 102 | 1 No. 200A 50KA 4P MCCB with Microprocessor Based Releases, ON Indication, with selector switch, matching cast resin CT's. |
| 103 | 1 No. 200A 50KA 4P MCCB (Spare) |
| 104 | 1 No. 125A 50KA 4P MCCB (Spare) |
| 105 | Other items such as |
| 106 | 1 set of control wiring |
| 107 | 1 Set of designation plates |
| 108 | NOTE :- Adequate Quantity of Fire Suppression system with Pneumatic gas cylinder and Heat Sensitive Pneumatic tubing to be used in panel as per the current fire norms & SURGE PROTECTION DEVICES Type 1 ( Class B), 4 Mode, spar type suitable for 10/350µs surge, 3Nos. phase to earth and 1Nos. neutral to earth with impulse Current Iimp. ≥ 50KA Per mode & In ≥ 25kA per Mode. |
| 109 | Complete Panel as Above |
| 110 | FLOOR DISTRIBUTION PANELS |
| 111 | SITC of cubicle Panel suitable for 415V, 3 phase, 4 wire 50 HZ Ac supply system, fabricated in conmpartmentalized (preferbly) design from CRCA sheet of 2mm thick for frame work and covers, 3mm thick for gland, plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having suitable Amp capacity extensible type TPN aluminium alloy bus bars of high conductivity, DMC/SMC bus bar supports, , bottom base channel of MS section not less than 50mm x 50mm x 5mm thick, entire pannel shall have a common copper earth bar 25mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of AI. bus bars and control wiring with 2.5 sq.mm. FRLS PVC insulated copper conducter S/C cable, cable alleys, cable gland plates in two half. i/c providing following switch gears :- |
| 112 | INCOMER : 125 AMP 25KA FP MCCB |
| 113 | BUS BAR : 160 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. |
| 114 | digital voltmeter with selecter switch 1 no., digital Am meter with slecter switch required C/T, LED indicating lamp (RYB)- 1no. |
| 115 | OUT GOINGS : |
| 116 | 10 Nos 63 AMP 4P MCB Including 1 set of Indication Lamp |
| 117 | 3 Nos 40 AMP DP MCB Including 1 set of Indication Lamp |
| 118 | complete panel as above and complete |
| 119 | MAIN LIFT PANEL |
| 120 | Design, manufacture, supply, installation, testing and commissioning of Floor Mounting Panel cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. |
| 121 | INCOMER : 200 AMP FP MCCB |
| 122 | BUS BAR : 250 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm /amp. |
| 123 | The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. |
| 124 | OUT GOINGS : |
| 125 | 2 No. 100A 25KA 4P MCCB |
| 126 | 1 No. 100A 25KA 4P MCCB |
| 127 | complete panel as above and complete |
| 128 | LIFT PANEL (TYPICAL) |
| 129 | Design, manufacture, supply, installation, testing and commissioning of Floor Mounting Panel cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. |
| 130 | INCOMER : 100 AMP FP MCCB |
| 131 | BUS BAR : 125 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm /amp. |
| 132 | The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. |
| 133 | OUT GOINGS : |
| 134 | 1 No 63 AMP 4P MCB Including Indication Lights (Lift) |
| 135 | 1 No 40 AMP DP MCB Including Indication Lights (Machine Room DB) |
| 136 | 1 No 40 AMP DP MCB (Spare) |
| 137 | 1 No 63 AMP 4P MCB (Spare) |
| 138 | complete panel as above and complete |
| 139 | complete panel as above and complete |
| 140 | EXTERNAL LIGHT FEEDER PILLAR |
| 141 | Design, Manufacture, Supply, Installation, Testing and Commissioning of Panel Fabricated out of 16 SWG CRCA sheet steel, IP 54, wall / floor mounting type with rain canopy The sheet steel shall undergo minimum 7 tank treatment followed by finishing powder coating of min 60 micron thickness. the board includes 415 /240 V electrolitic Aluminium Bus Bar, removable gland plates, cable glands, including connection with outgoing feeders complete in all respect, Panel Should Have Double Earthing Provision Which Connected to the Nearest Earth Grid. |
| 142 | INCOMER: |
| 143 | 1 no. 125A, 50KA 4P MCCB with microprocessor based releases, ON indication, 1 no. multifunction meter (showing all power parameters), with Selector Switch, Matching Cast Resin CT's. + 3 Nos 63A DP MCB For each Phase.with 3 Nos Astronomical Weekly programmable time switch (SST- 1min) ON Phase for automaitc switching of landscape light fixtures at sun set and sun rise or twilight (auto on/ auto off and auto mode) with manual override faiclity with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site. |
| 144 | BUS BAR |
| 145 | TPN Aluminium bus bar with heat Shrink Sleeve rated for 125A. |
| 146 | OUTGOING |
| 147 | 18 nos 20A SPN MCB |
| 148 | 2 nos 63A 4P MCB |
| 149 | 2 nos 40A 4P MCB |
| 150 | Other items such as |
| 151 | 1 Set of control wiring |
| 152 | 1 Set of designation plates |
| 153 | complete panel as above and complete |
| 154 | Supply of H.T. Cable |
| 155 | Supply & Testing of following 11 KV (E) grade multicore Aluminium conductor XLPE insulated cable, insulation screening with extruded semi conducting compound in combination with copper tape armoured cores laid up, inner sheath of PVC tape, galvanised steel flat strip armoured and overall PVC sheathed cable conforming to IS: 7098 (Part - II) and complete with all latest amendments etc. complete as required. |
| 156 | Supply, Installation, Testing & Commissioning of UK Style (Square) Keystone-Type Shuttered Faceplates, 1, 2 & 4 port configurations, White Color, Elegant 2 Piece (2 Plate) design for better aesthetics , Cover and Base Plastic Material ABS-UL94-V2, 86 x 86mm |
| 157 | Supply , Installation , Testing and commissioning of CAT 6 UTP cable 23 AWG LSZH as per ANSI/TIA 568 C.2 and ISO/ IEC 11801–2nd Edition, ROHS Compliant, solid copper conductors, tested @250 Mhz, with HDPE insulation of individual conductor and over all Dia of 5.8mm for Connectivity of Hub room to End Point. |
| 158 | Supply, Installation, Testing & Commissioning of 3MP IP Network TDN Low-Light IR Rugged Indoor / outdoor Dome Camera, 1/2.8\\" CMOS or better, 3MP (2304 x 1296) @ 25fps or better, triple stream at various resolution up to 25fps, Min. Illumination required 0.005 lux @ F1.6 (color), 0 Lux IR On, 4 IR LEDs Smart IR with upto 50m IR distance, Auto ICR (Infrared Cut Filter) 120dB True WDR, S/N Ratio 50db, Shutter Speed 1/8 - 1/30,000; Adavance Video Compression technology such as H.265 & H.264 High Profile & MJPEG , Triple stream, 2.7 to 13.5mm 5X motorized focus & zoom lens, Field of View FoV H:88°-24°, BLC, HLC, 3DNR White Balance, Minimum Edge Intelligence Video Analytics : Motion Detection, Tampering, 4 Privacy Mask, 8 Region Of Intreset, TLS1.2, AES-128/256, SSH/Telnet closed, Stream Encryption, 256GB SD card support, PoE (802.3 af) and 12V DC, Max 6W, IP 66/67, IK 10 vandal proof with Die Cast Aluminium Housing, Having Operating temp range : –40°C to 60° C. Certifications: ONVIF Profile S/G/T compliant, UL/CSA 62368-1, CE (EN 50130-4), FCC Part 15, EN 55032 & RoHS (EN63000) compliant |
| 159 | Supply, Installation, Testing & Commissioning of 3MP IP Network TDN Low-Light IR Rugged indoor/ outdoor Bullet Camera, 1/2.8\\" CMOS or better, 3MP (2304 x 1296) @ 25fps or better, triple stream at various resolution up to 25fps, Min. Illumination required 0.005 lux @ F1.6 (color), 0 Lux IR On, 4 IR LEDs Smart IR with upto 60m IR distance, Auto ICR (Infrared Cut Filter) 120dB True WDR, S/N Ratio 50db, Shutter Speed 1/8 - 1/30,000; Adavance Video Compression technology such as H.265 & H.264 High Profile & MJPEG , Triple stream, 2.7 to 13.5mm 5X motorized focus & zoom lens, Field of View FoV H:85°-24°, BLC, HLC, 3DNR White Balance, Minimum Edge Intelligence Video Analytics : Motion Detection, Tampering, 4 Privacy Mask, 8 Region Of Intreset, TLS1.2, AES-128/256, SSH/Telnet closed, Stream Encryption, 256GB SD card support, PoE (802.3 af) and 12V DC, Max 6W, IP 66/67, IK 10 vandal proof with Die Cast Aluminium Housing, Having Operating temp range : –40°C to 60° C. Certifications: ONVIF Profile S/G/T compliant, UL/CSA 62368-1, CE (EN 50130-4), FCC Part 15, EN 55032 & RoHS (EN63000) compliant. |
| 160 | Supply, Installation, Testing & Commissioning of IP Network TDN Low-Light 2MP 40 X IP IR PTZ Camera, 1/2.8\\" CMOS, 2MP@ 50fps, H.265, H.264, Min. Illumination required 0.1 lux (color), 0 Lux B/W IR on, 120dB True WDR, HLC, BLC, triple stream, Lens wide 4 to 5mm - Tele 160 to 200mm, 40X motorized focus & zoom lens, Inbuilt/Externla IR uo to 200 Meters, Built in Video Analytics such as Video Motion Detection, Camera Tampering & Auto Tracking, 3DNR, Defog, Electronic Image Stabilization, 24 Privacy Mask, shutter speed 1/1 to 1/10,000 second, PAN Speed upto 400°/s, PAN Range 360° Endless, Tilt Speed upto 400°/s, Tilt Range -20° to +90° (Auto Flip ), 256 Presets, Dual channel Audio G.711a/G.711u/G726, 256GB SD card support, Alarm: 2 In, 1out, High-PoE (UPOE) and 24VAC, IP 66, IK 10 vandal proof, Inbuilt Heater, Operating temp range : –40°C to 60° C. Certifications: ONVIF Profile S & G compliant, UL, CE, EN, FCC, NDAA Section 889 & RoHS compliant. |
| 161 | Supply , Installation , Testing and commissioning of 16/32/64 Channel NVR (Network Vedio Recorder), for recording upto 64CH @ 1080P with 08 nos. SATA HDDs minimum 64TB storage or more (recording requirement all cameras recording at 2MP, 25fps for 30 days),H.265/H.264/MJPEG/MPEG4 codec decoding, Front Control Pannel with LEDs Indication, 3 nos. USB, iPhone; iPad; Android based Mobile clients, Video Export feature on USB, Search Mode: Time/Date; Alarm; Motion Detection (MD); Exact Search (accurate to a second); Smart Search, Dual HDMI Output, Alarm Input (16 nos.), Alarm Output (6 nos.), 16 POE Ports, eSATA Device, 320Mbps each Incoiming & Outgping throughput, Operating Temperature –10°C to 55°CCertification : CE, FCC & UL including fixing accessories and cable termination with required connectors/Jack, complete in all respect as per instruction of engineer in-charge. |
| 162 | Supplying, installation, testing & commissioning of 2MP Fixed Dome Network Camera High quality image 1/2.8\\" CMOS sensor 1920*1080)@30/25fps; 720P (1280*720)@30/25fps Ultra 265, H.265, H.264 Smart IR, up to 30m (98ft) IR distance Day/night, Adjustment angle Rotate: 0° ~ 360°, DWDR, Privacy Mask Up to 4 areas, White Balance Auto/Outdoor/Fine Tune/ Sodium Lamp/Locked/Auto2, Digital noise reduction 2D/3D DNR, Flip Normal/Vertical/Horizontal/180°, HLC Supported BLC Supported, Network 10/100M Base-TX Ethernet, CE: EN 60950-1 UL: UL60950-1 FCC: FCC Part 15. |
| 163 | Supply, Installation, Testing and commissioning of Managable 24 port Switch with Power on Ethernet (PoE) enabled, 10/100, RJ45 Access ports with PoE complete as required. |
| 164 | Supply, installation, testing and commissioning of of 8 TB HDD all accessories complete as required. |
| 165 | Supply installation and commissioning of 55 inch LED monitor for display of camera. |
| 166 | Supply, Installation, Testing and Commissioning of Full HD 55\\" LED Professional Display Panel. |
| 167 | Supply, Installation, Testing & Commissioning of L2+ managed industrial PoE switch with 24*10/100/1000M RJ45 ports and 4*1/10G SFP+ fiber slot ports, Port 1-24 can support IEEE 802.3af/at PoE standard, switching capaticy of 598 Gbps, forwarding performance 95.23 Mpps, maximum PoE output power is 400W(at-600W), with 32K MAC address. Should have Static Routing , system logging, Telnet, SSH2.0, SNMP V1/V2C/V3, Network Time Protocol (NTP), FTP, TFTP, Xmodem. |
| 168 | Supply, Installation, Testing and Commissioning of Workstation PC: Intel(R) Core(TM) i7-3770 Processor (8M Cache, up to 3.90 GHz); RAM: 8GB (1x8GB) Non-ECC DDR3 1600MHz ; Keyboard: 12 function keys; Chassis: Tower/Workstation; DVD: 8X Slimline DVD+/-RW, Data Only; Dual Graphics Card; Network interface card: Integrated Intel(R) 82579LM Gigabit1 Ethernet LAN 10/100/1000; Hard disk: 250GB, 7200 RPM 3.5\\" SATA 6Gb/s Hard Drive; Operating system: Windows 7 Professional 64 Bit or latest. |
| 169 | Supply, Installation, Testing and Commissioning of energy saving high volume low speed ceiling mounted fan consisting of 8 airfoil blades, 14 feet diameter (sweep), VFD (variable frequency drive) operated with inbuilt protective module with maximum speed 80 rpm, air delivery 7550 cum/min, maximum power 0.4 kW, noise limit 43 dB suitable for operation on 230 V, 50 Hz ac supply including making connection with suitable size wire (as prescribed OEM) upto length of 30 m, inclusive of fixing materials etc. complete as required. |
| 170 | SANITARY INSTALLATIONS |
| 171 | Providing and fixing CP brass single lever low flow Sink mixer with 15 mm CP brass single lever pillar cock with pop up and waste complete including cutting and making good the walls where required.ROCA make (Model -RT5A3060C00) or Equivalent. |
| 172 | Providing and fixing C.P concealed four way diverter with thermostatic mixer with shut off valve and diverter, including cutting and making good the walls, wherever required. (Make:- Jaquar - Four way diverterKUB-35421, Thermostatic mixer 35671 or Equilent) |
| 173 | Providing,Fixing satin finish stainless steel AISI 316 grade wall mounted coat hook on door complete. The rate include cost of all material & labour involved in the item complete and all as per direction of engineer incharge. MAKE JAQUAR MODEL NO.- ACN-1161N or EQUIVALENT. |
| 174 | Providing, fixing, testing and commissioning of UPVC SWR pipe type 'B' conforms to IS : 13592-1992 with all fittings such as bends, tees, elbow, 'Y', offset, cleaning pipe door, clamps etc. conforming to IS:14735-1999 and steel structural supports etc. including cutting the floors, walls and making good the same in cement concrete 1:2:4 & cement mortar 1:4. The wall thickness of pipe and technical characteristic conforms to IS : 13592-1992 type 'B'. The fitting dimension conforming to IS : 14735-1999. The jointing to be completed with rubber ring joint/solvent weld joint as required/applicable. 110 mm (OD) |
| 175 | Providing, fixing, testing and commissioning of UPVC 'P' trap/floor trap/urinal trap of self cleansing design having 50 mm water seal with or without horn conforming to IS : 14735-1999 including setting with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 hard stone ballast 20 mm nominal size) including cost of cutting and making good the walls & floors wherever required. 110 mm inlet x110 mm outlet. |
| 176 | Providing, fixing, testing and commissioning of UPVC inlet fittings (hopper) receive waste from fixture waste with maximum 3 inlets 40, 50 & 63 mm OD size, fabricated from 110 OD UPVC SWR pipe, UPVC sockets, fixed to UPVC traps including solvent weld joint/rubber ring joint, complete with all civil work set in cement concreate 1:2:4 as required including cost of cutting and making good the walls & floors wherever required. |
| 177 | Providing, fixing, testing and commissioning of UPVC waste Pipe conforming to IS : 4985-2000 class III including all moulding fittings conforming to IS : 7834 (Part-1 - Part -7) 1987 such as tees, bends, reducers, coupling, adopters etc. solvent welded joint as per manufacturer recommendation including cutting and making good the walls, floors, R.C.C. work etc. (For fixtures waste). |
| 178 | 40 mm (OD) |
| 179 | 50 mm (OD) |
| 180 | Providing and fixing UPVC floor drain including all fitting and accessories fixed in cement mortar complete in all respect. 110 mm OD x 63 mm OD |
| 181 | Providing, fixing, testing and commissioning of UPVC rain water pipes (IS : 4985-1983 class-III ) including injection moulded fittings (heavy duty) (plain or door) e.g. bends, junction, cowls, tees, offsets, access pieces etc. Clamps/Supports jointing with rubber ring/solvent cement joints including cutting chase or holes in walls and floors and making good as required at Site [For Balcony Drain + Terrace Rain Water Downtake Pipe]. 160 OD |
| 182 | Providing, laying, Jointing, Testing and commissioning of uPVC pressure pipes of 10Kg/Sqcm pressure rating class 5 (IS : 4985-2000) including fittings, tees, bends, clamps, coupling and adaptors supports, and jointing with solvent joint, testing and necessary earth work in excavation, backfilling, disposal of surplus earth with a lead upto 50m complete, compaction and consolidation Including laying cement concrete 1:2:4 alround UPVC pipe including bed concrete and thrust blocks at bends as per standard design.32 OD mm. |
| 183 | Supplying, installation, testing and commissioning of weather proof M.S cabinet size 1200 mm x 2100 mm x 600mm deep fabricated from 1.6mm thick M.S. sheets and M.S angle 40mmx40mmx6mm complete with glass, locking arrangements to accommodate the following. |
| 184 | Gunmetal single headed Hydrant valve - 1 No. |
| 185 | Fire Hoses 63mm, 15 M long with accessories - 2 Nos. |
| 186 | Short branch - 1 No. |
| 187 | First Aid hose Reel - 1 No. |
| 188 | Fire Extinguisher - 2 Nos. |
| 189 | Fireman's Axe - 1 No. |
| 190 | Pressure Gauge - 1 No. |
| 191 | The cabinet shall be painted with one coat of primer and 2 coats of synthetic enamel paint of approved shade. |
| 192 | Providing & fixing double flanged Metallic expansion with M.S. fixed flanges (PN-1.6) joint (suitable for system test pressure) of standard length as per manufacturers specs including rubber gaskets, flanges, nuts, bolts and washers complete as required as per specifications.150 mm dia |
| 193 | Supplying and fixing of Fire Man's axe with heavy insulated rubber as per standard conforming to IS 926. |
| 194 | (FIRE EXTINGUISHERS) |
| 195 | Powder Fire Extinguisher (Stored Pressure type) Capacity 09 Kg duly ISI marked conforming to IS: 15683:2006, with IS 14609, ISI marked ABC powder complete with squeeze grip release valve, discharge pipe locking arrangement, pressure gauge, operation manual and bracket. Operating Temperature: - 10ºC to + 55ºC. Brand LIFEGUARD |
| 196 | Providing and fixing fire extinguisher of carbon dioxide type consisting of brand new high pressure steel cylinder bearing IS: 7285 mark and having the approval of controller of explosives Nagpur, wheel type valve bearing IS:3224 mark internal discharge tube, 1 meter long high pressure discharge hose, non conducting horn, suspension bracket, fully charged bearing IS: making fixed to wall as directed conforming IS : 15683:2006 4.5kg capacity cylinder |
| 197 | Providing and fixing in position approved make fire bucket of 24 gauge, galvanized steel, standard 9 liters capacity and of round bottom shape, panted white inside and red outside and black on bottom dome with letters ‘FIRE’ in black and gold with all mounting bracket and screws. |
| 198 | Providing and fixing of fire Bucket Stand including sheet metal (16 gauge) shade for 2 buckets. Platform and associated civil works complete. |
| 199 | (MOTOR CONTROL PANELS) |
| 200 | Supplying, assembling, erecting, connecting, testing and commissioning of Outdoor type fire fighting double door lockable type with epoxy paint. This panel shall be mounting on MS/brick pedestal support upto 400 mm high from ground level,cubical, dust, vermin proof and outdoor type (IP65) fabricated as per specification laid in document with following incomming and outgoing feeders including making connections/inter-connections testing and earthing etc. required with necessary interlocking with existing panel as shown in drawing as per specification and mounted with the followings. |
| 201 | Incoming |
| 202 | 1 No. - 630A 4P ATS |
| 203 | 1 No. - 630A TPN MCCB of fault breaking capacity 50 kA (Ics = Icu upto 500V), fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact, conforming to IS-13947-2 1993 as amended up-to-date complete with following accessories for each MCCB. |
| 204 | Independent electrical/manual spring closing mechanism - 1 No. |
| 205 | Microprocessor releases based relay(EMI & EMC certified) for over current, earth fault & short circuit protections with trip indications for each - 1 set. |
| 206 | Dual core calibrated digital Multifunctional meter of class 1.0 to record demand (KVA), energy (KWH & KVAH), power factor, current (in each phase and the neutral), voltage (between phases and between each phase and neutral) and 3 Nos. dual core CT of A Class 1.0 accuracy and 15 VA burden. |
| 207 | Following indicating lamps and push buttons for each MCCB with back up 2A SP MCB . |
| 208 | 3 No. Phase indicating Lamps . |
| 209 | Indicating Lamps for the following; |
| 210 | Bus Bar |
| 211 | 800 Amp. 50 kA, TPN Al. Bus Bar |
| 212 | Outgoings: |
| 213 | Following rated 420V,50KA MCCB's with overcurrent and short circuit releases Microprocessor based with ON,Trip indications, front operating handle & door interlock along with 2A SP MCB backup protection and control terminals & wiring as required. etc. complete in all respects as mentioned in specifications and as required For each outgoing: |
| 214 | 125 Amp. TP MCCB -4 Nos.(4 spare) |
| 215 | 16 Amp. TP MCCB -2 Nos.(2 spare) |
| 216 | Fully automatic Star Delta starter suitable for operating 2280 lpm (50 HP) motors/fan capacity, complete with contactors,Timer, overload protection relay, current sensing type single phase preventer, ON indications, push buttons, auto / manual / off selector switch,other accessories. complete as required. - 4 set. |
| 217 | Fully automatic DOL starter suitable for operating 180 lpm (4.0 HP) HP motors/fan capacity, complete with contactors,Timer, overload protection relay, current sensing type single phase preventer, ON indications, push buttons, auto / manual / off selector switch,other accessories. complete as required. - 2 set. |
| 218 | The Panel shall have necessary arrangement to start the pumps at automatic mode in following sequence. a) The Jockey Pump is start to maintain the drop in pressure in pipe line and also in case of opening of any hydrant to maintain the required pressure. b) The main fire pump will start in case of jockey doesnot able to maintain the required pressure due to opening of any fire hydrant. c) To start the diesel engine operated fire pump in case of failure of power supply or in case of minimum fire pump is not able to required pressure. |
| 219 | (d) Diesel Engine Control |
| 220 | Control for Diesel Engine comprising:- |
| 221 | (i) Auto/Manual selector switch & 3 attempt starting device, timers and relays as required, push buttons, start/stop in manual mode. |
| 222 | (ii) Indication lamp for High Water Temp. and Engine on indication and suitable tripping devices, overload, earth fault protection relays etc as required. |
| 223 | (iii)Battery charger suitable for 12 V/24 V DC with boost and tickle selector switch 0-15V/0-30V DC meter 0-20A DC Ammeter. |
| 224 | (iv) All standard relays and accessories for automatic operation of diesel engine. |
| 225 | (e) System Controller |
| 226 | Designing, Supply, Installation, Testing and commissioning of system controller to control operation of Main Fire Pump, Pressurization Pump in sequence as per specification consisting of relays, timers, sensor, annunciation window for fault indication, complete as per specification. |
| 227 | Fire panel as above |
| 228 | Supplying & Fixing Modular Type Computer jack RJ 45 ISI mark 1 Module on existing Mounting plate and box Complete with all accessories as required. |
| 229 | Supply & Installation, testing and commissioning of 9-15W LED Bracket Light fitting suitable for 9-15 Watt LED Light with all accessories as required. (Havells Cat no LHFOECE1TZ1O01/ Philips model no 31425/wipro make/ similar to BAJAJ make) |
| 230 | MAIN LT PANEL, HT PANELS & SUB DISTRIBUTION PANELS |
| 231 | 11KV SINGLE PANEL HT VCB (INDOOR)- ONE INCOMER CUM OUTGOING IN IP-4X ENCLOSURE |
| 232 | Design, Manufacture and Supply of 1 Panel, 11 kV HT VCB Switch Board with Following Accessories : |
| 233 | Incoming |
| 234 | 800A, 11kV, 350MVA for 3 Sec., TP, Horizontally isolated, horizontally drawout type, motorised spring charged, closing mechanism, motor voltage 230V AC, shunt tripping & Closing coil Voltage 24V DC, Electrically Operated, Trip Free, Dust & Vermin Proof, Vacuum Circuit Breaker(VCB) With Mechanical & Electrical OFF/ON Indicators & Provided with Following - 1 No. |
| 235 | CT chamber with double wound single phase, cast resin CT, 15VA burden with core-1 for metering (CL-1) and core-2 for protection (CL-5P10) and of 100/5/5A ratio - 3 Nos. |
| 236 | IDMT relay with 3 elements for over current (50-200%) and 1 element for earth fault protection(10-40%). - 1 Set |
| 237 | Anti Pumping Relay - 1 Set |
| 238 | Master Trip Relay - 1 Set |
| 239 | Trip circuit supervision relay - 1 Set |
| 240 | Potential Transformers, 3 Phase, 3 Limb, Drawout Type, Resin Cast 11000/(Root 3)/110/(Root 3) Ratio Class 1 Accuracy, 100 VA Burden, with HV fuse on primary side and MCB / MPCB on secondary side. - 1 Set |
| 241 | 6 Windows Annunciator with Hooter - 1 Set |
| 242 | 1 Window for over current trip - 1 Set |
| 243 | 1 Window for earth fault trip - 1 Set |
| 244 | 1 Window for master trip relay - 1 Set |
| 245 | 1 Window for Emergency Stop Push Button - 1 Set |
| 246 | 2 Windows Spare - 1 Set |
| 247 | Digital Ammeter with inbuilt selector switch - 1 Set |
| 248 | Digital Voltmeter with inbuilt selector switch - 1 Set |
| 249 | A set of breaker ON/OFF/Trip/DC control supply healthy/Trip circuit healthy/ Spring Charged VCB in test / VCB in service & R,Y,B phase indication lamps. - 1 Set |
| 250 | Emergency stop push button - 1 Set |
| 251 | Limit switches with 4 NO/ 4 NC breaker auxiliary contacts - 1 Set |
| 252 | Control:- T-N-C (Trip, Neutral, Close) breaker control switch with indication arrangement. - 1 Set |
| 253 | All control wiring with protection & test terminal block as required. - 1 Set |
| 254 | Strip heater with thermostat for moisture absorption. - 1 Set |
| 255 | Suitable for connection to 3C x 240 sq.mm. Cross linked polythelene(XLPE) 11kV cables or as called for. - 1 Set |
| 256 | Cable box for 3C x 240 sq.mm 11kV XLPE Al. conductor cable. - 1 Set |
| 257 | HT Danger Plate - 1 Set |
| 258 | Incoming as described above. 1 Sets |
| 259 | Powerpack as Required to Be Included (220V/24V DC), 7AH Battery for Each Breaker Module. |
| 260 | SINGLE PANEL 11KV HT VCB PANEL AS DESCRIBED ABOVE |
| 261 | 11KV THREE PANEL HT VCB (INDOOR)-ONE INCOMER, & TWO OUTGOINGS IN IP-4X ENCLOSURE |
| 262 | Design, Manufacture and Supply of 3 Panel, 11 kV HT VCB Switch Board with Following Accessories : |
| 263 | Incoming |
| 264 | 800A, 11kV, 350MVA for 3 Sec., TP, Horizontally isolated, horizontally drawout type, motorised spring charged, closing mechanism, motor voltage 230V AC, shunt tripping & Closing coil Voltage 24V DC, Electrically Operated, Trip Free, Dust & Vermin Proof, Vacuum Circuit Breaker(VCB) With Mechanical & Electrical OFF/ON Indicators & Provided with Following - 1 No. |
| 265 | CT chamber with double wound single phase, cast resin CT, 15VA burden with core-1 for metering (CL-1) and core-2 for protection (CL-5P10) and of 100/5/5A ratio - 3 Nos. |
| 266 | IDMT relay with 3 elements for over current (50-200%) and 1 element for earth fault protection(10-40%). - 1 Set |
| 267 | Anti Pumping Relay - 1 Set |
| 268 | Master Trip Relay - 1 Set |
| 269 | Trip circuit supervision relay - 1 Set |
| 270 | Potential Transformers, 3 Phase, 3 Limb, Drawout Type, Resin Cast 11000/(Root 3)/110/(Root 3) Ratio Class 1 Accuracy, 100 VA Burden, with HV fuse on primary side and MCB / MPCB on secondary side. - 1 Set |
| 271 | 6 Windows Annunciator with Hooter - 1 Set |
| 272 | 1 Window for over current trip - 1 Set |
| 273 | 1 Window for earth fault trip - 1 Set |
| 274 | 1 Window for master trip relay - 1 Set |
| 275 | 1 Window for Emergency Stop Push Button - 1 Set |
| 276 | 2 Windows Spare - 1 Set |
| 277 | Digital Ammeter with inbuilt selector switch - 1 Set |
| 278 | Digital Voltmeter with inbuilt selector switch - 1 Set |
| 279 | A set of breaker ON/OFF/Trip/DC control supply healthy/Trip circuit healthy/ Spring Charged VCB in test / VCB in service & R,Y,B phase indication lamps. - 1 Set |
| 280 | Emergency stop push button - 1 Set |
| 281 | Limit switches with 4 NO/ 4 NC breaker auxiliary contacts - 1 Set |
| 282 | Control:- T-N-C (Trip, Neutral, Close) breaker control switch with indication arrangement. - 1 Set |
| 283 | All control wiring with protection & test terminal block as required. - 1 Set |
| 284 | Strip heater with thermostat for moisture absorption. - 1 Set |
| 285 | Suitable for connection to 3C x 240 sq.mm. Cross linked polythelene(XLPE) 11kV cables or as called for. - 1 Set |
| 286 | Cable box for 3C x 240 sq.mm 11kV XLPE Al. conductor cable. - 1 Set |
| 287 | HT Danger Plate - 1 Set |
| 288 | Incoming as described above. 1 Sets |
| 289 | Bus Bars: |
| 290 | 800A TP 11KV AL. Busbars With Heat Shrinkable Insulation Sleeves |
| 291 | Outgoings : |
| 292 | 630A, 11kV, 350MVA for 3 Sec., TP, Horizontally Isolated, Horizontally Drawout Type, Motorised Spring Charged, Closing Mechanism, Motor Voltage 230V AC, Shunt Tripping & Closing Coil Voltage 24V DC, Electrically Operated, Trip Free, Dust & Vermin Proof, Vacuum circuit breaker(VCB) with mechanical & Electrical OFF/ON indicators & provided with following - 1 No. |
| 293 | CT chamber with double wound single phase, cast resin CT, 15VA burden with core-1 for metering (CL-1) and core-2 for protection (CL-5P10) and of 50/5/5A ratio. - 3 Nos. |
| 294 | Digital Ammeter with inbuilt selector switch - 1 Set |
| 295 | IDMT Relay with 3 Elements for Over Current (50-200%) and 1 Element for Earth Fault Protection(10-40%) With High Set. 1 Set |
| 296 | Anti Pumping Relay - 1 Set |
| 297 | Master Trip Relay - 1 Set |
| 298 | Trip circuit supervision relay - 1 Set |
| 299 | A Set of Breaker ON/OFF/Trip/DC Control Supply Healthy /Trip Circuit Healthy/ Spring Charged VCB in Test / VCB in Service. 1 Set |
| 300 | Auxiliary Relays for Transformer Faults WTI, OTI and Bucholz Relay. (To be Checked With the Requirement of Transformer i.e. For ONAN or Dry Type) For Alarm & Trip. 1 Set |
| 301 | 12 windows annunciator with hooter: |
| 302 | 1 window for over current trip |
| 303 | 1 window for earth fault trip |
| 304 | 1 window for winding temperature alarm |
| 305 | 1 window for winding temperature trip |
| 306 | 1 window for Oil temperature alarm |
| 307 | 1 window for Oil temperature trip |
| 308 | 1 window for Buchloz alarm |
| 309 | 1 window for Buchloz trip |
| 310 | 1 window for master trip relay |
| 311 | 1 window for emergency stop push button |
| 312 | 2 windows spare |
| 313 | Emergency Stop Push Button - 1 Set |
| 314 | Limit Switches With 4 NO/ 4 NC Breaker Auxiliary Contacts - 1 Set |
| 315 | Control:- T-N-C (Trip, Neutral, Close) Breaker Control Switch With Indication Arrangement. - 1 Set |
| 316 | All control wiring with protection & test terminal block as required. - 1 Set |
| 317 | Strip heater with thermostat for moisture absorption. - 1 Set |
| 318 | Cable box for 3C x 240 sq.mm 11kV XLPE Al. conductor cable. - 1 Set |
| 319 | HT Danger Plate - 1 Set |
| 320 | Outgoing as described above. - 2 Set |
| 321 | Powerpack as Required to Be Included (220V/24V DC), 7AH Battery for Each Breaker Module. |
| 322 | THREE PANEL 11KV HT VCB PANEL AS DESCRIBED ABOVE |
| 323 | MAIN LT PANEL |
| 324 | NOTE:- MCCB's Wherever Specified shall have Rotary Handle. |
| 325 | Suppy , installation, testing, Design, manufacture, supply inspection, handling, assembling, affecting proper connections, testing and commissioning of 2mm CRCA sheet steel fabricated cubical type Main L.T. Panel with PLC based load manager. floor mounting, dust & vermin proof, front operated construction, enclosure class - IP 52, TTA Type(IEC 61439), with proper treatment with 9 tank process with top/bottom removable gland plates, as required, double compression type cable glands, earth bus, hinged and lockable doors to achieve dust and vermin proof complete with all inter connections small wiring by min. 2.5 sq. mm. FRLS copper wires, ckt labels etc. The panel feeders shall be suitable for terminating suitable nos. 3.5 / 4 core armoured aluminium cable as required. Panel Should Be Internal Arc tested at 50ka for .3 sec as per IEC61641. |
| 326 | All Incoming / bus coupler / Outgoings ACB's shall have inbuilt current, volatage metering, ZSI (for discrimination) with trip history. All four pole ACB's shall have neutral protection at 50% and 100% . All ACB Shall have common frame till 3200 Amp. |
| 327 | All incoming & outgoing MCCB's shall be microprocessor based with O/L & S/C and E/F protection with inbuilt trip history (Faulty phase, type of fault and interupted Current). |
| 328 | All MCCB's shall be Ics = 100% Icu, with rotary handle & pad locking arrangement. All TP MCCB shall be with heavy duty solid isolable neutral link. All four pole MCCB's shall have neutral protection at 50% and 100%. All MCCB shall be Single Fram till 250A. |
| 329 | (Under no case temperature of main LT panel shall be more at any point of the panel. To avoid heating necessary exhaust fans shall have to be provided along with top louvers). |
| 330 | Degree of protection IP-42 |
| 331 | The internal control wiring shall fuse less. All control wiring and metering protection shall be by MCB's. |
| 332 | Colour: Siemens Gray Powder Coated or as per approved shade. |
| 333 | INCOMER FROM 630 KVA OUTDOOR TRANSFORMER - 2 Nos each having following |
| 334 | 1 Nos. 1000 amps Four Pole EDO ACB of fault breaking capacity 50 KA (Ics=Icu) fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated Position Indicator and Frame Earthing Contact ,Confiming to IS 13947-2 1993 as Amended upto Date Complete with Following Accessories. |
| 335 | 1 set of 3 CT's of ratio 1000/5A, Class 1.0 accuracy 15 VA burden for APFCR. |
| 336 | Independent manual spring closing mechanism - 1 No. |
| 337 | Microprocessor release (EMI and EMC certified) for over current, earth fault and short circuit protection - 1Set . |
| 338 | Multifunction meter with selector switch with suitable CT's and back up MCBs. |
| 339 | The instrument chamber shall be separate and shall comprise of flush type ammeter, voltmeter, selector switches, cast resin type CT's & PT's, etc. Separate CT's shall be provided for protective and measuring system and for APFCR of capacitor bank with suitable VA. |
| 340 | 3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB , circuits as per standatd practice , auxiallry contact for positive interlocking of the breakers as required. |
| 341 | Shunt trip coil 220 Volt AC. |
| 342 | INCOMER FROM DG SET (500 KVA) - 2 Nos each having following |
| 343 | 1 Nos. 800 amps four pole EDO ACB of fault breaking capacity 50 KA (Ics=Icu) fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicator and frame earthing contact ,confiming to IS 13947-2 1993 as amended upto date complete with following Accessories. |
| 344 | 1 set of 3 CT's of ratio 800/5A, Class 1.0 |
| 345 | Independent manual spring closing mechanism - 1 No. |
| 346 | Microprocessor release (EMI and EMC certified) for over current, earth fault and short circuit protection - 1Set . |
| 347 | Multifunction meter with selector switch with suitable CT's and back up MCBs. |
| 348 | Protection releases with LSIG and Over voltage ,under voltage,Reverse power protection Relay & Metering & Accessories for each D G set incomers |
| 349 | 3 Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB , circuits as per standatd practice , auxiallry contact for positive interlocking of the breakers as required . |
| 350 | Shunt trip coil 220 Volt AC. |
| 351 | 1 nos battery charger with DC voltmeter and ammeter suitable for the DG sets (500 KVA) |
| 352 | INTERLOCKING |
| 353 | Interlocking logic electrical Interlocking between incomers and bus coupler and it should have auto start and auto trip facility for Automatic Operation of The Breakers With Manual Over Rid Facility. |
| 354 | BUS COUPLER |
| 355 | One Number 1000A 4 pole ACB as Bus Coupler with ON/OFF Indication. |
| 356 | BUS BAR |
| 357 | 1250A TPN Aluminium bus bar with heat Shrink Sleeve |
| 358 | OUTGOING |
| 359 | All outgoing feeder shall be provide with ON / OFF / Trip indication lamp with protection MCB's, Dual Source energy Meter. |
| 360 | All MCCB's shall be equipped/provided with all accessories & In Built Protection Releases |
| 361 | 2 Nos. 630A TP+N MCCB |
| 362 | 1 Nos 160A FP MCCB |
| 363 | 2 Nos 400A 50kA FP MCCB |
| 364 | 1 Nos 400A 50kA FP MCCB |
| 365 | 1 Nos 630A 50kA FP MCCB |
| 366 | 1 Nos 160A FP MCCB |
| 367 | 6 No. 125A FP MCCB |
| 368 | 1 No. 250A FP MCCB |
| 369 | 4 No. 125A FP MCCB |
| 370 | 2 No. 630A 50KA FP MCCB (Spare) |
| 371 | 2 No. 400A 50KA FP MCCB (Spare) |
| 372 | 2 No. 250A 50KA FP MCCB (Spare) |
| 373 | 2 No. 125A 35KA FP MCCB (Spare) |
| 374 | Other items such as |
| 375 | 1 set of control wiring |
| 376 | 1 Set of designation plates |
| 377 | NOTE :- Adequate Quantity of Fire Suppression system with Pneumatic gas cylinder and Heat Sensitive Pneumatic tubing to be used in panel as per the current fire norms & SURGE PROTECTION DEVICES Type 1 ( Class B), 4 Mode, spar type suitable for 10/350µs surge, 3Nos. phase to earth and 1Nos. neutral to earth with impulse Current Iimp. ≥ 50KA Per mode & In ≥ 25kA per Mode. |
| 378 | Complete Panel as Above |
| 379 | FEEDER PILLAR (TYPICAL) |
| 380 | Design, Manufacture, Supply, Installation, Testing and Commissioning of Feeder Pillar Fabricated out of 16 SWG CRCA sheet steel, IP 54, wall / floor mounting type with rain canopy The sheet steel shall undergo minimum 7 tank treatment followed by finishing powder coating of min 60 micron thickness. the board includes 415 /240 V electrolitic Aluminium Bus Bar, removable gland plates, cable glands, including connection with outgoing feeders complete in all respect, Panel Should Have Double Earthing Provision Which Connected to the Nearest Earth Grid. |
| 381 | INCOMER : 125 AMP FP MCCB |
| 382 | BUS BAR : 160AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. |
| 383 | digital voltmeter with selecter switch 1 no. digital Am meter with selector switch required C/T, LED indicating lamp (RYB)- 1no. |
| 384 | OUT GOINGS : |
| 385 | 30 Nos 40 AMP DP MCB Including 1 set of Indication Lamp |
| 386 | complete panel as above and complete |
| 387 | FEEDER PILLAR (TYPICAL) |
| 388 | Design, Manufacture, Supply, Installation, Testing and Commissioning of Feeder Pillar Fabricated out of 16 SWG CRCA sheet steel, IP 54, wall / floor mounting type with rain canopy The sheet steel shall undergo minimum 7 tank treatment followed by finishing powder coating of min 60 micron thickness. the board includes 415 /240 V electrolitic Aluminium Bus Bar, removable gland plates, cable glands, including connection with outgoing feeders complete in all respect, Panel Should Have Double Earthing Provision Which Connected to the Nearest Earth Grid. |
| 389 | INCOMER : 125 AMP FP MCCB |
| 390 | BUS BAR : 160AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. |
| 391 | digital voltmeter with selecter switch 1 no. digital Am meter with slecter switch required C/T, LED indicating lamp (RYB)- 1no. |
| 392 | OUT GOINGS : |
| 393 | 25 Nos 40 AMP DP MCB Including 1 set of Indication Lamp |
| 394 | complete panel as above and complete |
| 395 | MAIN LIFT PANEL |
| 396 | SITC of cubicle Panel suitable for 415V, 3 phase, 4 wire 50 HZ Ac supply system, fabricated in conmpartmentalized (preferbly) design from CRCA sheet of 2mm thick for frame work and covers, 3mm thick for gland, plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having suitable Amp capacity extensible type TPN aluminium alloy bus bars of high conductivity, DMC/SMC bus bar supports, , bottom base channel of MS section not less than 50mm x 50mm x 5mm thick, entire pannel shall have a common copper earth bar 25mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of AI. bus bars and control wiring with 2.5 sq.mm. FRLS PVC insulated copper conducter S/C cable, cable alleys, cable gland plates in two half. i/c providing following switch gears :- |
| 397 | INCOMER : 160 AMP 25KA FP MCCB |
| 398 | BUS BAR : 200 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. |
| 399 | digital voltmeter with selecter switch 1 no. digital Am meter with slecter switch required C/T, LED indicating lamp (RYB)- 1no. |
| 400 | OUT GOINGS : |
| 401 | 3 Nos 100 AMP 4P MCCB Including 1 set of Indication Lamp |
| 402 | complete panel as above and complete |
| 403 | LIFT PANEL 1 & 2 |
| 404 | SITC of cubicle Panel suitable for 415V, 3 phase, 4 wire 50 HZ Ac supply system, fabricated in conmpartmentalized (preferbly) design from CRCA sheet of 2mm thick for frame work and covers, 3mm thick for gland, plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having suitable Amp capacity extensible type TPN aluminium alloy bus bars of high conductivity, DMC/SMC bus bar supports, , bottom base channel of MS section not less than 50mm x 50mm x 5mm thick, entire pannel shall have a common copper earth bar 25mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of AI. bus bars and control wiring with 2.5 sq.mm. FRLS PVC insulated copper conducter S/C cable, cable alleys, cable gland plates in two half. i/c providing following switch gears :- |
| 405 | INCOMER : 100 AMP 25KA FP MCCB |
| 406 | BUS BAR : 125 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. |
| 407 | digital voltmeter with selecter switch 1 no. digital Am meter with slecter switch required C/T, LED indicating lamp (RYB)- 1no. |
| 408 | OUT GOINGS : |
| 409 | 1 No 63 AMP 4P MCB Including Indication Lights (Lift 1) |
| 410 | 1 No 63 AMP 4P MCB Including Indication Lights (Lift 2) |
| 411 | 1 No 40 AMP DP MCB Including Indication Lights (Machine Room DB) |
| 412 | 1 No 63 AMP 4P MCB (Spare) |
| 413 | complete panel as above and complete |
| 414 | EXHIBITION HALL DISTRIBUTION PANEL |
| 415 | SITC of cubicle Panel suitable for 415V, 3 phase, 4 wire 50 HZ Ac supply system, fabricated in conmpartmentalized (preferbly) design from CRCA sheet of 2mm thick for frame work and covers, 3mm thick for gland, plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having suitable Amp capacity extensible type TPN aluminium alloy bus bars of high conductivity, DMC/SMC bus bar supports, , bottom base channel of MS section not less than 50mm x 50mm x 5mm thick, entire pannel shall have a common copper earth bar 25mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of AI. bus bars and control wiring with 2.5 sq.mm. FRLS PVC insulated copper conducter S/C cable, cable alleys, cable gland plates in two half. i/c providing following switch gears :- |
| 416 | INCOMER : 160 AMP 50KA FP MCCB |
| 417 | BUS BAR : 200AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. |
| 418 | The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. |
| 419 | OUT GOINGS : |
| 420 | 10 Nos 63 AMP 4P MCB Including 1 set of Indication Lamp |
| 421 | 2 Nos 40 AMP DP MCB Including 1 set of Indication Lamp |
| 422 | complete panel as above and complete |
| 423 | EXTERNAL LIGHT FEEDER PILLAR |
| 424 | Design, Manufacture, Supply, Installation, Testing and Commissioning of Panel Fabricated out of 16 SWG CRCA sheet steel, IP 54, wall / floor mounting type with rain canopy The sheet steel shall undergo minimum 7 tank treatment followed by finishing powder coating of min 60 micron thickness. the board includes 415 /240 V electrolitic Aluminium Bus Bar, removable gland plates, cable glands, including connection with outgoing feeders complete in all respect, Panel Should Have Double Earthing Provision Which Connected to the Nearest Earth Grid. |
| 425 | INCOMER: |
| 426 | 1 no. 125A, 25KA 4P MCCB with microprocessor based releases, ON indication, 1 no. multifunction meter (showing all power parameters), with Selector Switch, Matching Cast Resin CT's. + 3 Nos 63A DP MCB For each Phase.with 3 Nos Astronomical Weekly programmable time switch (SST- 1min) ON Phase for automaitc switching of landscape light fixtures at sun set and sun rise or twilight (auto on/ auto off and auto mode) with manual override faiclity with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site. |
| 427 | BUS BAR |
| 428 | TPN Aluminium bus bar with heat Shrink Sleeve rated for 160A. |
| 429 | OUTGOING |
| 430 | 18 nos 20A SPN MCB |
| 431 | 4 nos 63A 4P MCB |
| 432 | 6 nos 40A 4P MCB |
| 433 | Other items such as |
| 434 | 1 Set of control wiring |
| 435 | 1 Set of designation plates |
| 436 | complete panel as above and complete |
| 437 | Supply & Testing of following 11 KV (E) grade multicore Aluminium conductor XLPE insulated cable, insulation screening with extruded semi conducting compound in combination with copper tape armoured cores laid up, inner sheath of PVC tape, galvanised steel flat strip armoured and overall PVC sheathed cable conforming to IS: 7098 (Part - II) and complete with all latest amendments etc. complete as required. 3 C x 240 Sq. mm 11 KV (E) |
| 438 | Providing and laying 1.6 mm thick pregalvanized GI factory fabricated raceways of the following sizes including 2 mm thick GI covers, providing knock out holes and all required fixing accessories including 6 SWG GI earth wire complete as required including floor /wall supports, bends, access boxes and tap off boxes as per specification and cross over as per site requirement. Note:- Blue & Orange colour shall be considered for Power & Data raceway respectively. The item shall include the cost of chipping, cutting the floor for laying the raceway and making good the finish including chicken mesh complete as required as per site requirement. |
| 439 | 50x40x15x1.6mm & Cover 2mm |
| 440 | 100x40x15x1.6mm & Cover 2mm |
| 441 | 200x40x15x1.6mm & Cover 2mm |
| 442 | 300x40x15x1.6mm & Cover 2mm |
| 443 | SITC of VAK make decorative Column light in 3000mm height suitable for 60W LED, IP65. Column light made of MS sheet of 220x220mm and have height 3mtr above ground level with three spot light of 20W each for area illumination and column with mid predesigned laser cut to illuminate the surroundings with noticeable mode. Column is coated with epoxy zinc phosphate primer and niched using environmentally stable PU paint. Diffused symmetric light without glare. Light output of LED source is more than 110lm/ watt, CRI>80, Surge protection 4k, operating voltage 220-270V, wired with Branded LEDs and driver with efficiency>85%, power factor>0.9, THD<=10%. The CCT of led will be 3000/4000/5000 as required by the project. Proper thermal management for longer life of fixture. Led burning of 50,000 hours. The Service door shall be provided at bottom part of the pole which equipped with a C clamp with sliding nuts to accommodate a built-in connection box. The control gear tray is prewired with MCB, terminal connectors for loop in loop out arrangement. The base plate of the pole is design with elongated foundation holes for fine alignment of the pole during installation.Fitting is complete in all aspects with all accessories except foundation bolt. |
| 444 | SITC of Spot light ‘DIGO’ in 20W for landscape lighting. Fitting is made of high corrosion resistant die cast aluminium with CCT-3000K, CRI>80. This luminaire contains built-in LED modules. Driver efficiency >80% (integral), power factor >0.90, THD <10%, Surge protection 3KV. All exterior parts are made of stainless steel. Silicone rubber gasket are provided for water protection. Light output of led source is more than 110lm/W. Fitting is IP66,wired with Branded OSRAM or equivalent make LED and equivalent constant current driver. Proper thermal management for longer life of fixture. Led burning of 50,000 hours. Fitting is complete in all aspects with all accessories. |
| 445 | SITC of VAK make Ground Burial light in 9W for landscape lighting. Fitting is made of die cast aluminium and silicon rubber gasket with CCT 3000K/4000K/65000K depend as per project, CRI>80. This luminaire contains built-in LED modules. Driver efficiency >80% (integral), power factor >0.90, THD <10%, Surge protection 2kv. All exterior parts are made of stainless steel. Silicone rubber gasket are provided for water protection. Light output of source is more than 110lm/W. Fitting is IP67, wired with Branded OSRAM or equivalent make LED and equivalent constant current driver. Proper thermal management for longer life of fixture. Led burning of 50,000 hours. Fitting is complete in all aspects with all accessories. |
| 446 | SITC of VAK make'Dio' Step light suitable for 7w LEDLight. Recessed mounting wall fitting made of hight corrosion resistant die cast aluminium. Diffuser made of high impact polycarbonate.Light output of source is more than 110lm/W. Fitting is IP66, wired with Branded OSRAM or equivalent make LED and equivalent constant current driver. Proper thermal management for longer life of fixture. Led burning of 50,000 hours IP65 with CCT 3000K/4000K/65000K depend as per projec.Fitting is Complete all aspects with all accessorie. |
| 447 | Supply, Installation, Testing & Commissioning of UK Style (Square) Keystone-Type Shuttered Faceplates, 1, 2 & 4 port configurations, White Color, Elegant 2 Piece (2 Plate) design for better aesthetics , Cover and Base Plastic Material ABS-UL94-V2, 86 x 86mm |
| 448 | Supply, Installation, Testing & Commissioning of Appliance based customised ITAM for asset inventory management with ability to map physical locations and exact rack elevations for audit and support control. Appliance shall be Intel x86 based device with secure intranet server with Linux Based operating system and relational databases for long term storage. Appliance includes license for 100 units under control. |
| 449 | Supply, Installation, Testing & Commissioning of Firewall 2x10/100/1000 Base T ports with 2x 100/1000 SFP Ports in Combo ,Mion 1 x10 Gbps ports either in Copper or Fiber , Min 4 Gbps L2/L3 Throughput, Min concurrent session 2 million, Min 1 x set of Bypass Ports , Min 1x USB ports , Should have dual AC power supply from day 1 . Firewall, Switches, Wireless Components , Fiber module should be from the same OEM for seamless integration. |
| 450 | Supply, Installation, Testing & Commissioning of UK Style (Square) Keystone-Type Shuttered Faceplates, 1, 2 & 4 port configurations, White Color, Elegant 2 Piece (2 Plate) design for better aesthetics , Cover and Base Plastic Material ABS-UL94-V2, 86 x 86mm |
| 451 | Supply, Installation, Testing & Commissioning of 1, 2 and 4 port face plate, British Style with Shutter, 2 Plate system clear finish with transparent labelling, ABS-UL94-V2, ROHS Compliant, in accorandce with standards like ANSI/TIA-568-C.2, ISO/IEC 11801:2002 AMMD.2:2010, YD/T 926.3-2009 & ISO/IEC 60603-7 white for I/O fixing at user side. |
| 452 | Supply, Installation, Testing and Commissioning of Full HD 55\\" LED Professional Display Panel. |
| 453 | Supply, Installation, Testing & Commissioning of L2+ managed industrial PoE switch with 24*10/100/1000M RJ45 ports and 4*1/10G SFP+ fiber slot ports, Port 1-24 can support IEEE 802.3af/at PoE standard, switching capaticy of 598 Gbps, forwarding performance 95.23 Mpps, maximum PoE output power is 400W(at-600W), with 32K MAC address. Should have Static Routing , system logging, Telnet, SSH2.0, SNMP V1/V2C/V3, Network Time Protocol (NTP), FTP, TFTP, Xmodem |
| 454 | Supply, Installation, Testing and Commissioning of Workstation PC: Intel(R) Core(TM) i7-3770 Processor (8M Cache, up to 3.90 GHz); RAM: 8GB (1x8GB) Non-ECC DDR3 1600MHz ; Keyboard: 12 function keys; Chassis: Tower/Workstation; DVD: 8X Slimline DVD+/-RW, Data Only; Dual Graphics Card; Network interface card: Integrated Intel(R) 82579LM Gigabit1 Ethernet LAN 10/100/1000; Hard disk: 250GB, 7200 RPM 3.5\\" SATA 6Gb/s Hard Drive; Operating system: Windows 7 Professional 64 Bit or latest. |
| 455 | Supply, installation, testing and commissioning of Joystick with 5' LCD Display. |
| 456 | Supplying, installing, testing and commissioning approved make Addressable Power Supply Unit: 24V DC for Notification Appliances. The PSU shall be UL Listed, supervised by Fire Panel & of the same make as Fire Alarm System |
| 457 | Supply, installation, testing and commissioning of automatic electromechanical boom barrier suitable road width 5-7 mtrs for intensive applications, high speed with 4-6 second opening/closing time with Aluminium housing & aluminium boom with fork rest, IP 67 Protection etc. (for Gate Entry/Exit) |
| 458 | Supply , Installation , Testing and Commissioning of a set of Entry/Exit push buttons for manual open and closing of barriers etc. complete as required.(for Gate Entry/Exit). |
| 459 | Supply, Installation, Testing and Commissioning of Photocell based safety device to avoid closing of the barrier when a Vehicle is crossing the barrier.(Anti Fall Protection) |
| 460 | Supply installation, testing and commissioning of Remote & Receiver. |
| 461 | Supply , Installation , Testing and Commissioning of Loop detector for closing of the barrier when a Vehicle crosses the barrier. |
| 462 | Supply, Installation, Testing & Commissioning of Long Range RFID reader with controller 10-12 mtr read range with suitable mounting arrangement for Outdoor Application and shall be compatible with boom barrier integration |
| 463 | Supply Installation Testing & Commissioning of 3mtr pole for mounting of RFID reader with all accessories complete as required. |
| 464 | Supply and programming of Wigand Proximity Cards/RFID Tagsa with credibility of having integrated 50 Readers integrated with Booms as a unified solution along with facility code as per specifications |
| 465 | PLUMBING WORKS |
| 466 | Providing and Fixing electrical/battery operated concealed automatic flushing system for urinals, including front S.S plate 125 x 125mm (Sensing Range :-10 – 20 cm Intelligent Technology) having pre & post flushing with water (250 ml & 500 ml consumption) chrome sensor with CP brass body, ball valve etc., complete in all respect including cutting and making good the walls wherever required complete in all respects as per direction of the engineer-in-charge. |
| 467 | Providing and fixing CP brass single lever low flow Sink mixer with 15 mm CP brass single lever pillar cock with pop up and waste complete including cutting and making good the walls where required.ROCA make (Model -RT5A3060C00) or Equivalent. |
| 468 | Providing and fixing C.P concealed four way diverter with thermostatic mixer with shut off valve and diverter, including cutting and making good the walls, wherever required. (Make:- Jaquar - Four way diverterKUB-35421, Thermostatic mixer 35671 or Equilent) |
| 469 | Providing and fixing 25 Ltr Vertical/ Horizontal type Gyser for use in toilet for hot water generation, suitable for 6 kg/sqcm working pressure complete in all respects. The water holding vessel shall be in stainless steel construction with proper insulation. |
| 470 | Providing,Fixing satin finish stainless steel AISI 316 grade wall mounted coat hook on door complete. The rate include cost of all material & labour involved in the item complete and all as per direction of engineer incharge. MAKE JAQUAR MODEL NO.- ACN-1161N or EQUIVALENT. |
| 471 | Providing and fixing SUBMERSIBLE single/multistage centrifugal pumping set with CI body, bronze impeller, stainless steel shaft and induction motor mounted on PUMP CASE, vibration eleminating pads accessories complete as per specifications. Motor to be suitable for 415 Volts. CAPACITY 200 LPM @ 12 MWC HEAD with Electrical panel and automatic on/ off operation by level controller. |
| 472 | Providing, fixing, testing and commissioning of UPVC SWR pipe type 'B' conforms to IS : 13592-1992 with all fittings such as bends, tees, elbow, 'Y', offset, cleaning pipe door, clamps etc. conforming to IS:14735-1999 and steel structural supports etc. including cutting the floors, walls and making good the same in cement concrete 1:2:4 & cement mortar 1:4. The wall thickness of pipe and technical characteristic conforms to IS : 13592-1992 type 'B'. The fitting dimension conforming to IS : 14735-1999. The jointing to be completed with rubber ring joint/solvent weld joint as required/applicable. 110 mm (OD) |
| 473 | Providing, fixing, testing and commissioning of UPVC 'P' trap/floor trap/urinal trap of self cleansing design having 50 mm water seal with or without horn conforming to IS : 14735-1999 including setting with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 hard stone ballast 20 mm nominal size) including cost of cutting and making good the walls & floors wherever required. 110 mm inlet x110 mm outlet. |
| 474 | Providing, fixing, testing and commissioning of UPVC inlet fittings (hopper) receive waste from fixture waste with maximum 3 inlets 40, 50 & 63 mm OD size, fabricated from 110 OD UPVC SWR pipe, UPVC sockets, fixed to UPVC traps including solvent weld joint/rubber ring joint, complete with all civil work set in cement concreate 1:2:4 as required including cost of cutting and making good the walls & floors wherever required. |
| 475 | Providing, fixing, testing and commissioning of UPVC waste Pipe conforming to IS : 4985-2000 class III including all moulding fittings conforming to IS : 7834 (Part-1 - Part -7) 1987 such as tees, bends, reducers, coupling, adopters etc. solvent welded joint as per manufacturer recommendation including cutting and making good the walls, floors, R.C.C. work etc. (For fixtures waste). |
| 476 | 40 mm (OD) |
| 477 | 50 mm (OD) |
| 478 | Providing and fixing UPVC floor drain including all fitting and accessories fixed in cement mortar complete in all respect. 110 mm OD x 63 mm OD |
| 479 | Providing, fixing, testing and commissioning of UPVC rain water pipes (IS : 4985-1983 class-III ) including injection moulded fittings (heavy duty) (plain or door) e.g. bends, junction, cowls, tees, offsets, access pieces etc. Clamps/Supports jointing with rubber ring/solvent cement joints including cutting chase or holes in walls and floors and making good as required at Site [For Balcony Drain + Terrace Rain Water Downtake Pipe]. 160 OD |
| 480 | Providing & fixing CI `Y' Strainer (screwed/ flanged) with stainless steel fine wire mesh perforated sheet basket with necessary flange/ unions nuts, bolts and washers complete as required. 65mm nominal bore |
| 481 | Providing and fixing M.S fabricated hot dipped galvanized coating puddle flange comprising of 600 mm dia long M.S class 'B' pipe (screwed end up to 50 mm & flange for more than 50 mm dia) with 6 mm thick M.S plates of required size including cutting holes in centre of plate, inserting pipe & making welded (Arc) joint complete. Same shall be installed with TEC welded joint in position with reinforcement bars of RCC tank wall/slab including making cutout in shuttering during concrete casting of tank of following diameter. (Location: Underground / Overhead Tanks.) |
| 482 | 25mm dia pipe, 600mm long with size of 250x250x6 mm MS plate |
| 483 | 32mm dia pipe, 600mm long with size of 250x250x6 mm MS plate |
| 484 | 40mm dia pipe, 600mm long with size of 300x300x6 mm MS plate |
| 485 | 50mm dia pipe, 600mm long with size of 350x350x6 mm MS plate |
| 486 | 65mm dia pipe, 600mm long with size of 350x350x6 mm MS plate |
| 487 | 100mm dia pipe, 600mm long with size of 400x400x6 mm MS plate |
| 488 | 150mm dia pipe, 600mm long with size of 450x450x6 mm MS plate |
| 489 | 200mm dia pipe, 600mm long with 6 mm MS plate of size 600mm dia |
| 490 | Providing, laying, Jointing, Testing and commissioning of uPVC pressure pipes of 10Kg/Sqcm pressure rating class 5 (IS : 4985-2000) including fittings, tees, bends, clamps, coupling and adaptors supports, and jointing with solvent joint, testing and necessary earth work in excavation, backfilling, disposal of surplus earth with a lead upto 50m complete, compaction and consolidation Including laying cement concrete 1:2:4 alround UPVC pipe including bed concrete and thrust blocks at bends as per standard design. |
| 491 | 40 OD mm |
| 492 | 50 OD mm |
| 493 | 63 OD mm |
| 494 | RO SYSTEM |
| 495 | Supply, installation, testing and commissioning built with Drinking Water R.O. unit with micron filtration pre-treatment unit, skid mounted R.O. module with pressure pump and pressure tank, drinking water cooler (High quality SS Tank for Storage 80 lts) , complete in all respects. ( Make & Model No. Eureka Forbes Pure Chill RO Storage Cooler cum Purifier or Equivalent) |
| 496 | PUMPS & ALLIED WORKS |
| 497 | Providing, installing, testing and commissining of variable speed (VSPS) hydropneumatic system mounted on a common base plate comprising of vertical centrifugal pumping set with S.S body, stainless steel impeller and mechanical seal, shaft directly coupled to a TEFC induction motor suitable for 400/440 volts, 3 phase, 50 cycles AC supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads under foundation, one No. microprocessor based controller, dedicated variable frequency drive for each pump, one No.remote sensors, pressure transducers, sequence running cotroller, dry running Protection,motor control centre, necessary power and control cabling from MCC to pumps including required rating of MCB, one No. 90 litre capacity M.S diaphragam tank with interchangeable butyl rubber membrane,complete in all respects including MS Zinc coated suction and delivery headers and isolation/ control valves( ball valves/butterfly valves/ Nan return valves/ vibration eliminators etc as required) , power box, equipped with fuses/ isolators/circuit breakers as required. |
| 498 | The entire Hydropneumatic system shall be factory fitted. |
| 499 | Hyd. System for Domestic Water Supply Pump |
| 500 | Flow rate : 2 lps each |
| 501 | Pumping Head - 55 m |
| 502 | 1 Set = 2 Nos. pump (1 working+1 standby) |
| 503 | Approx H.P.- 3 HP or as per manufacturer recommendation. |
| 504 | Location - Abow UGT. |
| 505 | Flow rate : 1.5 lps each |
| 506 | Head : 55 Mts |
| 507 | Required for : Flushing water transfer pump |
| 508 | (1 working + 1 standby) |
| 509 | Location - Abow STP |
| 510 | Supplying, installing, testing and commissioning of SS vertical centrifugal pump. Each pump shall have TEFC 2900 RPM three phase electric motor. The pump shall have cast iron head, base plate SS Shaft / Impeller / Intermediate chamber along with motor, pressure gauge with isolation cock, Isolation valve, NRV on delivery line. Isolation valve, stainer (with by-pass) at suction. Pump shall be provided with mechanical seal, suitable vibration elimination pads of approved design, drain pipe with valve (25 dia). The pump shall be suitable for auto/ manual operation. The installation shall be complete with all necessary ancillaries, starter panel / control panel & accessories including base plate complete as required. |
| 511 | Flow rate : 2 lps each |
| 512 | Head : 30 Mts |
| 513 | Required for : Filter feed pump |
| 514 | (1 working + 1 standby) |
| 515 | Location - Abow UGT. |
| 516 | Providing, fixing, testing & commissioning of vertical FRP filter with adequate dirt holding capacity. Fabricated from FRP sheet as per IS-2825 and manufacturer's specifications complete with intitial charge filter media . The filter shall also be provided with set of internals for raw water inlet and bottom collecting system. Complete with frontal piping (PVC 10 Kg) and multiport valve . it is designed on 1.50 m / sec velocity. |
| 517 | WATER TREATMENT PLANT (WTP) |
| 518 | Dual Media Filter For Domestic Water Supply |
| 519 | Capacity- 7200 LPH |
| 520 | Filtration rate- 16000 LPH/Sqm. |
| 521 | Filter dia approx. - 750 MM |
| 522 | Working pressure: 3.0 Kg/sq cm. |
| 523 | Test pressure : 4. 5 Kg/sq cm |
| 524 | Activated Carbon Filter For Domestic Water Supply |
| 525 | Capacity- 2500 LPH |
| 526 | Filtration rate- 16000 LPH/Sqm. |
| 527 | Filter dia approx. - 750 MM |
| 528 | Working pressure: 3.0 Kg/sq cm. |
| 529 | Test pressure : 4. 5 Kg/sq cm |
| 530 | Treated water Pumps- Domestic water OHT Filling |
| 531 | Capacity : 150 LPM |
| 532 | Head : 55 m |
| 533 | App. HP : 3 HP |
| 534 | Motor RPM : 2900 |
| 535 | Each set consists of 2 pumps (1Working +1Standby). At any given time, only one pump need operate. Both the pumps must operate alternatively in service. |
| 536 | Providing & fixing butterfly valve (with motorized actuator) of rating PN 1.6, wafer type, in cast iron body with Ductile Iron disc, EPDM seal, SS single piece shaft, conforming to IS-13095 of the following sizes complete with cast iron hand level companion flanges, bolts, nuts, washers & inserted rubber gaskets, as required and as per enclosed specification, with single phase Electrical Actuator, of 15Nm- 400Nm Torque, made of aluminium alloy (resistant to heat, acid , alkali, corrosion), and weather proof heavy duty motor, with stabilized start speed to effectively avoid water hammering, with waterproofing seal (IP 67) for all housing seals, low noise level, built –in thermal protection complete as per specifications |
| 537 | 40 mm nominal bore |
| 538 | 50 mm nominal bore |
| 539 | Providing and fixing lever operated gun metal ball valve with SS-316 ball. |
| 540 | 40 mm nominal bore |
| 541 | 50 mm nominal bore |
| 542 | Providing, Installation ,testing and commission of Cast Iron Dual plate (SS-316 Plates) Non Return valve as per technical specification complete with rubber gaskets, SS bolts & nuts, washers etc. as required and two matching flanges as per table 'E' etc. 40 mm nominal bore |
| 543 | Providing and fixing of Cast Iron flanged Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 316, sheet with 3 mm dia. holes with stainless steel flange with rubber gaskets, SS bolts & nuts, washers etc. complete as required. |
| 544 | 50 mm nominal bore |
| 545 | 65 mm nominal bore |
| 546 | Providing and fixing of Pressure gauge (dial size minimum 6”) weather proof (IP-55) with a scale range from 0 to 10 Kg / cm² including stop cock. |
| 547 | Providing and fixing double flanged flexicion rubber expansion joint with unit control of standard length of a as per manufacturer specs tested to a pressure of 15 kg/sqcm including rubber gasket, flanges, nuts ,bolts and washers complete as required. 40 mm nominal bore |
| 548 | Design, manufacture, supplying, fixing in position, testing and commissioning of the following front operated cubicle type, front access 2mm thick mild steel sheet, free standing, dust proof, switchboard with IP42 protection with hinged and lockable doors complete with interconnections, tinned copper crimping lugs, bonding to earth and painting, suitable for use at 415 volts, 3 phase 4 wire 50 Hz system and suitable for a fault level of 25 MVA symmetrical at 415 volts. |
| 549 | All switchboards shall have provision for entry of cables from the top or bottom as required. |
| 550 | All live accessible parts shall be shrouded and all equipment shall be finger touch proof. The busbars insulation shall be with heat shrinkable sleeves. SMC/DMC shrouds and busbar supports shall be used. Padlocking facility shall be provided on all outgoing feeders doors and switch handles shall be lockable in OFF position. |
| 551 | Electric Panel For Water Supply Pumps at Water Supply Pump Room |
| 552 | INCOMING |
| 553 | 1 No. 63 amps TPN MCCB with the following accessories: |
| 554 | 1 No. square flush mounting 0-500 volts scaled voltmeter with three way and OFF switch. |
| 555 | Three phase indicating lights. |
| 556 | Electrolytic high conductivity three phase and neutral tinned copper bus bar rated at 100 amps having a current density of 1 amp per Sqmm suitable to with stand symmetrical fault level of 25 MVA at 415 volts. The neutral bus bar is to be of 100% capacity. |
| 557 | OUTGOING UNITS |
| 558 | 6 25/40 Amp. TP + NL M.C.C.B. with rotary handle of breaking capacity 25KA |
| 559 | Two 63 Amp. TP + NL M.C.C.B. with rotary handle of breaking capacity 25KA |
| 560 | 2 Nos. fully automatic DOL starters with push buttons and ON/OFF indicating lights and overload relays for 1.5 to 7.5 HP pump . |
| 561 | 2 Nos. rotary selector switch for selecting mode of operation i.e. auto/manual/off. |
| 562 | 2 Nos.cyclic relay for automatic duty changeover of pumps. |
| 563 | 2 No. single phase preventors. |
| 564 | 2 Nos. square flush mounting 0-30 amps scaled ammeters with three way and OFF selector switch. |
| 565 | Space for 3 Nos. Level Controllers. |
| 566 | Switchgear shall be suitable for the HPS of various motors. |
| 567 | 1 Nos. 63 Amp. TPN MCB Spare. |
| 568 | 2 Nos. 32/40 Amp. TPN MCB Spare. |
| 569 | The motor control panel shall be prewired with colour coded wires with identification labels complete in all respects as required. |
| 570 | Supplying, installing, testing and commissioning controllers with low voltage relays, stainless steel probes and PVC shroud wiring from tank top to probes of required. Level Controller For Water Supply Pump: To start pump when water level is low in Domestic Water U.G. tank and shut off pump when Domestic Water U.G. tank is full. Also to stop when water level is low in raw water underground tank. |
| 571 | FIRE FIGHTING WORK |
| 572 | Fabricating, Supplying, Installation, Testing and Commissioning Air Vessel of continuous welded construction with flanged discharge header on the top of each riser fabricated out of 8 mm thick MS sheet, Air Release Valve complete with suitable drain arrangement with 25 mm dia gun metal ball valve complete with all accessories etc. pressure gauge, synthetic enamel paint of approved shade as required of the following sizes 2 Meter high and 450 mm dia suitable to operate Jockey Pump, Main Fire Pump , Sprinkler pump & Diesel Engine Driven Fire Pump |
| 573 | (HYDRANTS SYSTEM) |
| 574 | Supplying, installation, testing and commissioning of weather proof M.S cabinet size 1200 mm x 2100 mm x 600mm deep fabricated from 1.6mm thick M.S. sheets and M.S angle 40mmx40mmx6mm complete with glass, locking arrangements to accommodate the following. |
| 575 | Gunmetal single headed Hydrant valve - 1 No. |
| 576 | Fire Hoses 63mm, 15 M long with accessories - 2 Nos. |
| 577 | Short branch - 1 No. |
| 578 | First Aid hose Reel - 1 No. |
| 579 | Fire Extinguisher - 2 Nos. |
| 580 | Fireman's Axe - 1 No. |
| 581 | Pressure Gauge - 1 No. |
| 582 | The cabinet shall be painted with one coat of primer and 2 coats of synthetic enamel paint of approved shade. |
| 583 | (PIPING, VALVES AND ACCESSORIES) |
| 584 | Supplying, Installation, Testing and Commissioning of CI body flanged (both ends) type serviceable suction / Y strainer with (stainless steel / brass mesh) conforming to relevant IS specifications amended upto date complete including providing and fixing nuts, bolts, washers, gaskets etc. complete as required. 65 mm dia |
| 585 | Providing & fixing double flanged Metallic expansion with M.S. fixed flanges (PN-1.6) joint (suitable for system test pressure) of standard length as per manufacturers specs including rubber gaskets, flanges, nuts, bolts and washers complete as required as per specifications. |
| 586 | 150 mm dia |
| 587 | 65 mm dia |
| 588 | Supplying and fixing of Fire Man's axe with heavy insulated rubber as per standard conforming to IS 926. |
| 589 | (FIRE EXTINGUISHERS) |
| 590 | Powder Fire Extinguisher (Stored Pressure type) Capacity 09 Kg duly ISI marked conforming to IS: 15683:2006, with IS 14609, ISI marked ABC powder complete with squeeze grip release valve, discharge pipe locking arrangement, pressure gauge, operation manual and bracket. Operating Temperature: - 10ºC to + 55ºC. Brand LIFEGUARD |
| 591 | Providing and fixing fire extinguisher of carbon dioxide type consisting of brand new high pressure steel cylinder bearing IS: 7285 mark and having the approval of controller of explosives Nagpur, wheel type valve bearing IS:3224 mark internal discharge tube, 1 meter long high pressure discharge hose, non conducting horn, suspension bracket, fully charged bearing IS: making fixed to wall as directed conforming IS : 15683:2006 4.5kg capacity cylinder |
| 592 | Providing and fixing in position approved make fire bucket of 24 gauge, galvanized steel, standard 9 liters capacity and of round bottom shape, panted white inside and red outside and black on bottom dome with letters ‘FIRE’ in black and gold with all mounting bracket and screws. |
| 593 | Providing and fixing of fire Bucket Stand including sheet metal (16 gauge) shade for 2 buckets. Platform and associated civil works complete. |
| 594 | (MOTOR CONTROL PANELS) |
| 595 | Supplying, assembling, erecting, connecting, testing and commissioning of Outdoor type fire fighting double door lockable type with epoxy paint. This panel shall be mounting on MS/brick pedestal support upto 400 mm high from ground level,cubical, dust, vermin proof and outdoor type (IP65) fabricated as per specification laid in document with following incomming and outgoing feeders including making connections/inter-connections testing and earthing etc. required with necessary interlocking with existing panel as shown in drawing as per specification and mounted with the followings. |
| 596 | Incoming |
| 597 | 1 No. - 630A 4P ATS |
| 598 | 1 No. - 630A TPN MCCB of fault breaking capacity 50 kA (Ics = Icu upto 500V), fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact, conforming to IS-13947-2 1993 as amended up-to-date complete with following accessories for each MCCB. |
| 599 | Independent electrical/manual spring closing mechanism - 1 No. |
| 600 | Microprocessor releases based relay(EMI & EMC certified) for over current, earth fault & short circuit protections with trip indications for each - 1 set. |
| 601 | Dual core calibrated digital Multifunctional meter of class 1.0 to record demand (KVA), energy (KWH & KVAH), power factor, current (in each phase and the neutral), voltage (between phases and between each phase and neutral) and 3 Nos. dual core CT of A Class 1.0 accuracy and 15 VA burden. |
| 602 | Following indicating lamps and push buttons for each MCCB with back up 2A SP MCB . |
| 603 | 3 No. Phase indicating Lamps . |
| 604 | Indicating Lamps for the following; |
| 605 | Bus Bar |
| 606 | 800 Amp. 50 kA, TPN Al. Bus Bar |
| 607 | Outgoings: |
| 608 | Following rated 420V,50KA MCCB's with overcurrent and short circuit releases Microprocessor based with ON,Trip indications, front operating handle & door interlock along with 2A SP MCB backup protection and control terminals & wiring as required. etc. complete in all respects as mentioned in specifications and as required For each outgoing: |
| 609 | 125 Amp. TP MCCB -4 Nos.(4 spare) |
| 610 | 16 Amp. TP MCCB -2 Nos.(2 spare) |
| 611 | Fully automatic Star Delta starter suitable for operating 2280 lpm (50 HP) motors/fan capacity, complete with contactors,Timer, overload protection relay, current sensing type single phase preventer, ON indications, push buttons, auto / manual / off selector switch,other accessories. complete as required. - 4 set. |
| 612 | Fully automatic DOL starter suitable for operating 180 lpm (4.0 HP) HP motors/fan capacity, complete with contactors,Timer, overload protection relay, current sensing type single phase preventer, ON indications, push buttons, auto / manual / off selector switch,other accessories. complete as required. - 2 set. |
| 613 | The Panel shall have necessary arrangement to start the pumps at automatic mode in following sequence. a) The Jockey Pump is start to maintain the drop in pressure in pipe line and also in case of opening of any hydrant to maintain the required pressure.b) The main fire pump will start in case of jockey doesnot able to maintain the required pressure due to opening of any fire hydrant.c) To start the diesel engine operated fire pump in case of failure of power supply or in case of minimum fire pump is not able to required pressure. |
| 614 | (d) Diesel Engine Control |
| 615 | Control for Diesel Engine comprising:- |
| 616 | (i) Auto/Manual selector switch & 3 attempt starting device, timers and relays as required, push buttons, start/stop in manual mode. |
| 617 | (ii) Indication lamp for High Water Temp. and Engine on indication and suitable tripping devices, overload, earth fault protection relays etc as required. |
| 618 | (iii)Battery charger suitable for 12 V/24 V DC with boost and tickle selector switch 0-15V/0-30V DC meter 0-20A DC Ammeter. |
| 619 | (iv) All standard relays and accessories for automatic operation of diesel engine. |
| 620 | (e) System Controller |
| 621 | Designing, Supply, Installation, Testing and commissioning of system controller to control operation of Main Fire Pump, Pressurization Pump in sequence as per specification consisting of relays, timers, sensor, annunciation window for fault indication, complete as per specification. |
| 622 | Fire panel as above |
| 623 | HVAC WORKS |
| 624 | Supplying, Installation, Testing and Commissioning of following minimum capacity and external static pressure VRF/VRV ceiling mounted single skin high ductable type Indoor/ Air Handling Unit unit equipped with washable synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, DC multispeed motor, coil section with DX copper coil, electronic expansion valve, corded remote control, outer cabinet, vibration Isolators, drain pan, drain pump, other necessary supports etc., suitable for operation on single phase AC supply 230 V ± 10%, 50 Hz complete as required. The Indoor units must shut down upon receiving a singal from the BMS System/Fire Singnals. The cooling capacity of indoor unit will be at air inlet conditions of 27 0C DB and 19 0C WB temperature. (Make will be same as of Outdoor) High Static Ductable units/ Air Handling Unit (450 pascal external static pressure) 16.0 TR Static Ductable/ AHU with Corded Controller & accessories (4 RD Coil) |
| 625 | Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required : |
| 626 | 44.50 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm |
| 627 | 50.80 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm |
| 628 | 54.10 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm |
| 629 | Darin Piping: |
| 630 | Supply, installation & testing of cPVC / uPVC pipes for Condensate Drain Piping with closed cell nitrile tube insulations of 6~9mm thick for the all indoor units as required for following sizes- |
| 631 | Pipe Size: 25mm Dia |
| 632 | Pipe Size: 40mm Dia |
| 633 | Supply & Charging of R410a Refrigerants Gas |
| 634 | Fire proof double layered canvass cloth connection for Indoor outlet complete with flanges made out of 22G G.S.S sheet on both sides for connection to Indoor and duct complete with nuts, bolts etc. as per specification. |
| 635 | Supply, installation, testing and commissioning of toilet exhaust fan of reputed makes of following capacities along with heavy duty PVC circular pipes along with required fittings to make system good as per sepcification. It should also include supply air extruded aluminium grill of required sizes. |
| 636 | 1500 CFM |
| 637 | 150 CFM |
| 638 | WTP EQUIPMENT |
| 639 | WATER TREATMENT, SEWERAGE TREATMENT AND WATER SUPPLY NETWORK |
| 640 | Providing and fixing GI pipes complete (IS:1239 Heavy Class) with GI fittings and clamps including MS pipe supports, enamel paint as per specifications cutting and making good the walls etc. complete.(WTP Room Abow the UGT.) |
| 641 | 50 mm dia, nominal bore |
| 642 | 65 mm dia, nominal bore |
| 643 | 80 mm dia, nominal bore |
| 644 | Providing & fixing CI `Y' Strainer (screwed/ flanged) with stainless steel fine wire mesh perforated sheet basket with necessary flange/ unions nuts, bolts and washers complete as required. 65mm nominal bore |
| 645 | Providing and fixing M.S fabricated hot dipped galvanized coating puddle flange comprising of 600 mm dia long M.S class 'B' pipe (screwed end up to 50 mm & flange for more than 50 mm dia) with 6 mm thick M.S plates of required size including cutting holes in centre of plate, inserting pipe & making welded (Arc) joint complete. Same shall be installed with TEC welded joint in position with reinforcement bars of RCC tank wall/slab including making cutout in shuttering during concrete casting of tank of following diameter. (Location: Underground / Overhead Tanks.) |
| 646 | 25mm dia pipe, 600mm long with size of 250x250x6 mm MS plate |
| 647 | 32mm dia pipe, 600mm long with size of 250x250x6 mm MS plate |
| 648 | 40mm dia pipe, 600mm long with size of 300x300x6 mm MS plate |
| 649 | 50mm dia pipe, 600mm long with size of 350x350x6 mm MS plate |
| 650 | 65mm dia pipe, 600mm long with size of 350x350x6 mm MS plate |
| 651 | 80mm dia pipe, 600mm long with size of 400x400x6 mm MS plate |
| 652 | 100mm dia pipe, 600mm long with size of 400x400x6 mm MS plate |
| 653 | 150mm dia pipe, 600mm long with size of 450x450x6 mm MS plate |
| 654 | 200mm dia pipe, 600mm long with 6 mm MS plate of size 600mm dia |
| 655 | Providing, laying, Jointing, Testing and commissioning of uPVC pressure pipes of 10Kg/Sqcm pressure rating class 5 (IS : 4985-2000) including fittings, tees, bends, clamps, coupling and adaptors supports, and jointing with solvent joint, testing and necessary earth work in excavation, backfilling, disposal of surplus earth with a lead upto 50m complete, compaction and consolidation Including laying cement concrete 1:2:4 alround UPVC pipe including bed concrete and thrust blocks at bends as per standard design. |
| 656 | 25 OD mm. |
| 657 | 32 OD mm. |
| 658 | 40 OD mm |
| 659 | 50 OD mm |
| 660 | 63 OD mm |
| 661 | Supply, installation, testing and commissioning built with Drinking Water R.O. unit with micron filtration pre-treatment unit, skid mounted R.O. module with pressure pump and pressure tank, drinking water cooler (High quality SS Tank for Storage 80 lts) , complete in all respects. ( Make & Model No. Eureka Forbes Pure Chill RO Storage Cooler cum Purifier or Equivalent) |
| 662 | Providing, installing, testing and commissining of variable speed (VSPS) hydropneumatic system mounted on a common base plate comprising of vertical centrifugal pumping set with S.S body, stainless steel impeller and mechanical seal, shaft directly coupled to a TEFC induction motor suitable for 400/440 volts, 3 phase, 50 cycles AC supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads under foundation, one No. microprocessor based controller, dedicated variable frequency drive for each pump, one No.remote sensors, pressure transducers, sequence running cotroller, dry running Protection,motor control centre, necessary power and control cabling from MCC to pumps including required rating of MCB, one No. 90 litre capacity M.S diaphragam tank with interchangeable butyl rubber membrane,complete in all respects including MS Zinc coated suction and delivery headers and isolation/ control valves( ball valves/butterfly valves/ Nan return valves/ vibration eliminators etc as required) , power box, equipped with fuses/ isolators/circuit breakers as required. |
| 663 | The entire Hydropneumatic system shall be factory fitted. |
| 664 | Hyd. System for Domestic Water Supply Pump |
| 665 | Flow rate : 2 lps each |
| 666 | Pumping Head - 70 m |
| 667 | 1 Set = 2 Nos. pump (1 working+1 standby) |
| 668 | Approx H.P.- 3 HP or as per manufacturer recommendation. |
| 669 | Location - Abow UGT. |
| 670 | Flow rate : 1.5 lps each |
| 671 | Head : 70 Mts |
| 672 | Required for : Flushing water transfer pump |
| 673 | (1 working + 1 standby) |
| 674 | Location - Abow STP |
| 675 | Supplying, installing, testing and commissioning of SS vertical centrifugal pump. Each pump shall have TEFC 2900 RPM three phase electric motor. The pump shall have cast iron head, base plate SS Shaft / Impeller / Intermediate chamber along with motor, pressure gauge with isolation cock, Isolation valve, NRV on delivery line. Isolation valve, stainer (with by-pass) at suction. Pump shall be provided with mechanical seal, suitable vibration elimination pads of approved design, drain pipe with valve (25 dia). The pump shall be suitable for auto/ manual operation. The installation shall be complete with all necessary ancillaries, starter panel / control panel & accessories including base plate complete as required. |
| 676 | Flow rate : 2 lps each |
| 677 | Head : 70 Mts |
| 678 | Required for : Filter feed pump |
| 679 | (1 working + 1 standby) |
| 680 | Location - Abow UGT. |
| 681 | Providing, fixing, testing & commissioning of vertical FRP filter with adequate dirt holding capacity. Fabricated from FRP sheet as per IS-2825 and manufacturer's specifications complete with intitial charge filter media . The filter shall also be provided with set of internals for raw water inlet and bottom collecting system. Complete with frontal piping (PVC 10 Kg) and multiport valve . it is designed on 1.50 m / sec velocity. |
| 682 | WATER TREATMENT PLANT (WTP) |
| 683 | Dual Media Filter For Domestic Water Supply |
| 684 | Capacity- 7200 LPH |
| 685 | Filtration rate- 16000 LPH/Sqm. |
| 686 | Filter dia approx. - 750 MM |
| 687 | Working pressure: 3.0 Kg/sq cm. |
| 688 | Test pressure : 4. 5 Kg/sq cm |
| 689 | Activated Carbon Filter For Domestic Water Supply |
| 690 | Capacity- 2500 LPH |
| 691 | Filtration rate- 16000 LPH/Sqm. |
| 692 | Filter dia approx. - 750 MM |
| 693 | Working pressure: 3.0 Kg/sq cm. |
| 694 | Test pressure : 4. 5 Kg/sq cm |
| 695 | Treated water Pumps- Domestic water OHT Filling |
| 696 | Capacity : 150 LPM |
| 697 | Head : 70 m |
| 698 | App. HP : 3 HP |
| 699 | Motor RPM : 2900 |
| 700 | Each set consists of 2 pumps (1Working +1Standby). At any given time, only one pump need operate. Both the pumps must operate alternatively in service. |
| 701 | Providing & fixing butterfly valve (with motorized actuator) of rating PN 1.6, wafer type, in cast iron body with Ductile Iron disc, EPDM seal, SS single piece shaft, conforming to IS-13095 of the following sizes complete with cast iron hand level companion flanges, bolts, nuts, washers & inserted rubber gaskets, as required and as per enclosed specification, with single phase Electrical Actuator, of 15Nm- 400Nm Torque, made of aluminium alloy (resistant to heat, acid , alkali, corrosion), and weather proof heavy duty motor, with stabilized start speed to effectively avoid water hammering, with waterproofing seal (IP 67) for all housing seals, low noise level, built –in thermal protection complete as per specifications |
| 702 | 40 mm nominal bore |
| 703 | 50 mm nominal bore |
| 704 | Providing and fixing lever operated gun metal ball valve with SS-316 ball. |
| 705 | 40 mm nominal bore |
| 706 | 50 mm nominal bore |
| 707 | Supplying, fixing, testing and commissioning of Cast Iron butterfly valve of PN 1.0 rating with SS-316 seat, Shaft SS-316 duly ISI marked complete with SS bolts & nuts, washers, gaskets conforming to IS 13095 of following sizes as required and two matching flanges as per table 'E' etc. |
| 708 | 65 mm nominal bore |
| 709 | 80 mm nominal bore |
| 710 | 100 mm nominal bore |
| 711 | Providing, Installation ,testing and commission of Cast Iron Dual plate (SS-316 Plates) Non Return valve as per technical specification complete with rubber gaskets, SS bolts & nuts, washers etc. as required and two matching flanges as per table 'E' etc. |
| 712 | 40 mm nominal bore |
| 713 | 50 mm nominal bore |
| 714 | 65 mm nominal bore |
| 715 | 80 mm nominal bore |
| 716 | Providing and fixing of Cast Iron flanged Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 316, sheet with 3 mm dia. holes with stainless steel flange with rubber gaskets, SS bolts & nuts, washers etc. complete as required. |
| 717 | 50 mm nominal bore |
| 718 | 65 mm nominal bore |
| 719 | Providing and fixing of Pressure gauge (dial size minimum 6”) weather proof (IP-55) with a scale range from 0 to 10 Kg / cm² including stop cock. |
| 720 | Providing and fixing G.I. suction & delivery headers / pipes for water supply pumps (IS:1239 heavy class) with G.I. Fittings (bends, tees, reducers, plugs, union, flange & blank flanges etc.) and clamps and jointing with Teflon tape or hold tite including chase cutting and making good the walls, floors etc. wherever required. Painting with two or more coats of synthetic enamel paint of approved quality and shade over a coat of approved primer coat as directed including surface preparation (Shade as per pipe colour code) |
| 721 | 40 mm nominal bore |
| 722 | 50 mm nominal bore |
| 723 | 65 mm nominal bore |
| 724 | 80 mm nominal bore |
| 725 | Providing and fixing double flanged flexicion rubber expansion joint with unit control of standard length of a as per manufacturer specs tested to a pressure of 15 kg/sqcm including rubber gasket, flanges, nuts ,bolts and washers complete as required. 40 mm nominal bore |
| 726 | Design, manufacture, supplying, fixing in position, testing and commissioning of the following front operated cubicle type, front access 2mm thick mild steel sheet, free standing, dust proof, switchboard with IP42 protection with hinged and lockable doors complete with interconnections, tinned copper crimping lugs, bonding to earth and painting, suitable for use at 415 volts, 3 phase 4 wire 50 Hz system and suitable for a fault level of 25 MVA symmetrical at 415 volts. |
| 727 | All switchboards shall have provision for entry of cables from the top or bottom as required. |
| 728 | All live accessible parts shall be shrouded and all equipment shall be finger touch proof. The busbars insulation shall be with heat shrinkable sleeves. SMC/DMC shrouds and busbar supports shall be used. Padlocking facility shall be provided on all outgoing feeders doors and switch handles shall be lockable in OFF position. |
| 729 | Electric Panel For Water Supply Pumps at Water Supply Pump Room |
| 730 | INCOMING |
| 731 | 1 No. 63 amps TPN MCCB with the following accessories: |
| 732 | 1 No. square flush mounting 0-500 volts scaled voltmeter with three way and OFF switch. |
| 733 | Three phase indicating lights. |
| 734 | Electrolytic high conductivity three phase and neutral tinned copper bus bar rated at 100 amps having a current density of 1 amp per Sqmm suitable to with stand symmetrical fault level of 25 MVA at 415 volts. The neutral bus bar is to be of 100% capacity. |
| 735 | OUTGOING UNITS |
| 736 | 6 25/40 Amp. TP + NL M.C.C.B. with rotary handle of breaking capacity 25KA |
| 737 | Two 63 Amp. TP + NL M.C.C.B. with rotary handle of breaking capacity 25KA |
| 738 | 2 Nos. fully automatic DOL starters with push buttons and ON/OFF indicating lights and overload relays for 1.5 to 7.5 HP pump . |
| 739 | 2 Nos. rotary selector switch for selecting mode of operation i.e. auto/manual/off. |
| 740 | 2 Nos.cyclic relay for automatic duty changeover of pumps. |
| 741 | 2 No. single phase preventors. |
| 742 | 2 Nos. square flush mounting 0-30 amps scaled ammeters with three way and OFF selector switch. |
| 743 | Space for 3 Nos. Level Controllers. |
| 744 | Switchgear shall be suitable for the HPS of various motors. |
| 745 | 1 Nos. 63 Amp. TPN MCB Spare. |
| 746 | 2 Nos. 32/40 Amp. TPN MCB Spare. |
| 747 | The motor control panel shall be prewired with colour coded wires with identification labels complete in all respects as required. |
| 748 | Supplying, installing, testing and commissioning controllers with low voltage relays, stainless steel probes and PVC shroud wiring from tank top to probes of required. Level Controller For Water Supply Pump: To start pump when water level is low in Domestic Water U.G. tank and shut off pump when Domestic Water U.G. tank is full. Also to stop when water level is low in raw water underground tank. HYDROSTATIC PRESSURE SENSOR TYPE WITH CONTROLLER CUM INDICATOR |
| 749 | Design, Supplying, installing, testing & commissioning of Sewage Treatment Plant (MBBR) of 50 KLD (excluding excavation, back filling & disposal of surplus earth MS / Civil construction work) for the following duty: |
| 750 | Sewage treatment plant shall include the following items: |
| 751 | a. Screen chambers with SS Screenb. Equalization Tankc. Aerobic & Anoxic tankd. MBBR TANK e. Air Blowersf. MBBR Media g. Recirculation pumps, backpulse pump, permeate pump etc.h. Dewatering systemj. Electrical Panel, Cabling (Power & Control), Earthingk. Tertiary Treatmentl. Clear Water tank and Flushing Water tank. |
| 752 | INLET SEWAGE CHARACTERSTICS (ASSUMED) |
| 753 | pH - 6.0 – 8.5 |
| 754 | BOD5 : 250 - 350 mg/lit |
| 755 | Total Suspended Solids (TSS) : 250 - 450 mg/lit |
| 756 | COD : 500 - 700 mg/lit |
| 757 | Oil / Grease : upto 50 mg/lit |
| 758 | Inflow time : 24 HRS |
| 759 | Peak factor : 3 |
| 760 | Temperature : Ambient |
| 761 | Desired Sewage Quality After Treatment |
| 762 | pH : 7 - 8 |
| 763 | BOD5 : < 10 mg/lit |
| 764 | Total Suspended Solids (TSS) : < 10 mg/lit |
| 765 | COD : < 50 mg/lit |
| 766 | Oil / Grease : < 5 mg/lit |
| 767 | Colour : Colourless |
| 768 | Odor : unobjectionable |
| 769 | E.coli : Nil |
| 770 | NH4-N :< 5 mg/lit |
| 771 | N Total :< 10 mg/lit |
| 772 | PO4-P : 2 mg/lit |
| 773 | Note: |
| 774 | Vendor shall ensure submission of detailed GA drawings (Plan & Section), P&I diagram, schematic diagram for the above said component and additional component if so required for the complete working of the STP for the full capacity. |
| 775 | SIGNAGES |
| 776 | Providing and fixing the sign shall comprise of channel letters in required fonts of Hindi or English in specified Font Height depicting the name fixed on rigid supporting system in steel. Channel letters will be made out of 2mm thick Aluminum sheet to make it 3D Channel letter, side & back painted with Polyutherene paint of desired color and front face of channel letter will be fully covered with 5mm translucent 040 acrylic sheet as approved by engineer-in-charge and internal lighting arrangement in channel letter will be using LEDs LUCOLED Module complete. with 5 year warranty. The signage shall be free from hot spots and will have even illumination to achieve a desired effect. Providing necessary supporting system comprising of mild steel members of required size and lengths as per drawings. Polyurethane painting of the MS angles, MS tubes, and to required colour, mounting at the required locations on the building. Channel letters sign are installed at site in plumb and level at specified location as per drawing to the satisfaction of the engineer-in-charge. |
| 777 | Providing and fixing at location a signs M.S internal hollow tube structure using Cosign Make- Modular Aluminium extrusions (Alloy 6060 as per European standards EN755-2-2008 tensile strength 190 MPamade from virgin homogeneous aluminium billet) with Premium grade Anodizing (Thickness 15-20 microns) International standards, with 10 years warranty under normal working conditions. Sign is including all extruded aluminium profiles profiles including i) 4 base profiles mill finished glossy appearance or texture, base profile with slots to accomodate 50 x 50 mm , 100x50 mm (to create max depth of 200 mm from either of the combination aftet mounting base & cover profiles, M.S structure & 'V' notch groove to guide self tapering screws,directly to be screwed with ,Internal M.S structure with help of stainless steel high tensile strength zinc coated self tapering CSK screws (length as per requirement) ii) 4 cover profiles of eliiptical shape premium anodised with intel- locating faciltiy with base profile for posiotioning. to be screwed with base profile (screws not visible from outside) after cover profile is mounted to base iii) Top & bottom ACP egde profile premium grade anodised to cover edges of ACP free mounting without drilling or screwing. iv) ACP connect profile with minimum display free mounting without lockuing & drilling. etc ,Ultra violet print on ACP or ACRYLIC sheet can be done. Also, arrangement is done to (ACP or Acrylic 3 mm thick can be Inserted in Cosign totem profile slots). Top hat asper profile shape (aluminium 2-3 mm thick) is used to cover top part, 2mm thick opaque white acrylic(or clear)can be pasted on text panels as numbers with help of 3M make adhesive.also LED (Back lite) modules or edge lite modules. CosignTotem profiles screwed fixed with internal M.S structure are installed at site in plumb and level at specified location as per drawing to the satisfaction of the engineer-in-charge. |
| 778 | Providing a signs made as using Cosign India make Modular Aluminium extrusions (Alloy 6060 as per European standards EN755-2-2008 tensile strength 190 MPa made from virgin homogeneous aluminium billet) with Premium grade Anodizing (Thickness 15-20 microns) as per International standards, with 10 years warranty under normal working conditions.Sign is double sided 50 mm depth profile with media accomodation depth of 6 mm media of ACP acrylic upto 5 mm thickness can be pasted directly on frames or attched on frame with help of dual lock tape.Sign can be edge lite with help of edge lite led modules ,led of LUCOLED make EL31 , fitted and installed at site in plumb and level at specified location as per drawing to the satisfaction of the engineer-in-charge. |
| 779 | Providing a signs made as using Modular Aluminium extrusions (Alloy 6060 as per European standards EN755-2-2008 tensile strength 190 MPa made from virgin homogeneous aluminium billet) with Premium grade Anodizing (Thickness 15-20 microns) as per International standards, with 10 years warranty under normal working conditions.Sign is single sided with 1 aluminium profile click fitted on 2 plastic moulded endcaps.Sign is including all plastic injection moulded end caps black in shade which are directly press fitted ,media can be flat bed UV printed on panels/ profiles.Cosign make MPI panels fitted and installed at site in plumb and level at specified location as per drawing to the satisfaction of the engineer-in-charge. |
| 780 | Providing a signs made as using Cosign India make Modular Aluminium extrusions (Alloy 6060 as per European standards EN755-2-2008 tensile strength 190 MPa made from virgin homogeneous aluminium billet) with Premium grade Anodizing (Thickness 15-20 microns) as per International standards, with 10 years warranty under normal working conditions.Sign is double sided 50 mm depth profile with media accomodation depth of 6 mm media of ACP acrylic upto 5 mm thickness can be pasted directly on frames or attched on frame with help of dual lock tape.Sign can be edge lite with help of edge lite led modules ,led of LUCOLED make EL31 , fitted and installed at site in plumb and level at specified location as per drawing to the satisfaction of the engineer-in-charge. |
| 781 | Providing a signs made as using Modular Aluminium extrusions (Alloy 6060 as per European standards EN755-2-2008 tensile strength 190 MPa made from virgin aluminium homogeneous billet) with Premium grade Anodizing (Thickness 15-20 microns) as per International standards, with 10 years warranty under normal working conditions.Sign is single sided with aluminium side tracks and common click clips for panel fitting. a.Sign is including all plastic injection moulded clips black in shade which are slided in side tracks ,media can be flat bed UV printed on panels/ profiles.Cosign make MPI panels fitted and installed at site in plumb and level at specified location as per drawing to the satisfaction of the engineer-in-charge. |
| 782 | Providing a signs made as using Modular Aluminium extrusions (Alloy 6060 as per European standards EN755-2-2008 tensile strength 190 MPa made from virgin homogeneous aluminium billet) with Premium grade Anodizing (Thickness 15-20 microns) as per International standards, with 10 years warranty under normal working conditions.Sign is single sided with 1 aluminium profile click fitted on 2 plastic moulded endcaps.Sign is including all plastic injection moulded end caps black in shade which are directly press fitted ,media can be flat bed UV printed on panels/ profiles.Cosign make MPI panels fitted and installed at site in plumb and level at specified location as per drawing to the satisfaction of the engineer-in-charge. |
| 783 | Providing sign of Cosign make Modular Aluminium extrusions (Alloy 6060 as per European standards EN755-2-2008 tensile strength 190 MPa Made from virgin homogeneous aluminium billet) with premium grade anodizing (Thickness 15-20 microns) as peinternational standards, with 10 years warranty under normal working conditions. Profile to form frame with overall depth of 10 mm with media of thickness upto 3mm. 2 mm thick acrylic/ACP . I-sign Fix profile of Cosign make with M.S zinc coated corners with grub screws. Installed at site in plumb and level at specified location as per drawing to the satisfaction of the engineer-in-charge. |
| 784 | Providing a signs made as using Modular Aluminium extrusions (Alloy 6060 as per European standards EN755-2-2008 tensile strength 190 MPa made from virgin homogeneous aluminium billet) with Premium grade Anodizing (Thickness 15-20 microns) as per International standards, with 10 years warranty under normal working conditions.Sign is single sided with 1 aluminium profile click fitted on 2 plastic moulded endcaps.Sign is including all plastic injection moulded end caps black in shade which are directly press fitted ,media can be flat bed UV printed on panels/ profiles.Cosign make MPI panels fitted and installed at site in plumb and level at specified location as per drawing to the satisfaction of the engineer-in-charge. |
| 785 | Providing sign of Cosign make Modular Aluminium extrusions (Alloy 6060 as per European standards EN755-2-2008 tensile strength 190 MPa Made from virgin homogeneous aluminium billet) with premium grade anodizing (Thickness 15-20 microns) as peinternational standards, with 10 years warranty under normal working conditions. Profile to form frame with overall depth of 10 mm with media of thickness upto 3mm. 2 mm thick acrylic/ACP . I-sign Fix profile of Cosign make with M.S zinc coated corners with grub screws. Installed at site in plumb and level at specified location as per drawing to the satisfaction of the engineer-in-charge. |
| 786 | Providing ready sign & fixing at location a Cosign make emergency exit sign- illuminated, surface mount (wall or ceiling) Dual sided made up of plastic material , battery backup of 3 hours (180 mins) .Battery life of 300 cycles of charge & discharge Li- ion battery 3.7 Volt, 100 mA, Charge time of 24 hours. Input voltage 220-240 Volt A.C, 50/60 Hz. Viewing distance 30 meter, degree of protection IP20 (rating for protection against solid object upto 12 mm) white light colour full back (white colour) LED illumination with green white coloured graphic inserted on both sides on 0.4 mm PC (sizes, texts, symbols or graphics as per standard safety norms & regulations) graphic options of -left ,right, up staircase down staircase. Test facilty button self test plus auto self test, opreration in maintained and non maintained mode (power saver mode).Sign with 12 months warranty for electric circuit & 6 months warranty for battery. Sign provided with dual mounting arrangement of mounting on wall & celing both ( with flat rigid support/base).Sign is including all connection wires (upto 1 mtr) & high tensile strength zinc coated self tapering screws (4 nos with screw wall plastic packing), installed at site in plumb and level at specified location as per drawing to the satisfaction of the engineer-in-charge. |
| 787 | Fabrication of The Mushroom Head Stem which is a set of 3 such stems rising at varying heights with a maximum height of 10mtr using MS Structuring and MS Outer Framing |
| 788 | Fabrication of The Leaf Designed Entrance pergola which is a set of 4 such Leaves of dimension 11mtr x 5.5mtr each with suitable vertical poles and bracing made MS Structure & MS Sections |
| 789 | Audio & Visual System |
| 790 | Supply, Installation, Testing & Commissioning of 1-chip DLP LASER Phosphor Multimedia Projection system having, 9600 Lumens 20000 hours lamp life, 1920 x 1200 WUXGA Native Resolution, Inbuilt blending and warping with automatic caliberation software, 3D ready, 3000000:1 Contrast Ratio, inputs: HDBaseT,HDMI2.0, DVI-D, Active 3D, Motorised zoom and focus, alongwith 0.65-0.75 lens & projector mountin bracket etc. min offset 110%V and 50%H power consumption shuld not be more than 660W,complete with installation as per the site requirement.DWU960ST-iSApproved Make:- Christe/ Barco/Sony. |
| 791 | Supply, Installation, Testing & Commissioning of Customized Hanging Arrangments above Projector complete with satandard accessories as required. Approved Make:- Custom. |
| 792 | Supply, Installation, Testing & Commissioning of 300\\" diagonal motorized projection screen with an aspect ratio of 16:10, High quality aluminium frame with a black velvet cover, prevents reflection & serves to absorb projected light.Approved Make:- Draper/Netmas/da-lite |
| 793 | Supply, installation, testing and commissioning of a high-performance outdoor active LED video wall system with 2.5 mm pixel pitch, suitable for auditoriums and large-format display applications, delivering high-resolution visuals with excellent brightness and uniform color performance. The LED video wall shall be built using modular LED cabinets of 320 mm (W) × 480 mm (H), each with a native resolution of 128 × 192 pixels. The proposed configuration shall comprise 16 cabinets horizontally and 6 cabinets vertically, forming an overall display size of approximately 5.1 m (W) × 2.8 m (H), with an effective screen resolution of 2432 (H) × 1536 (V) pixels and an approximate diagonal size of 231 inches. The scope shall include supply and installation of all associated components such as LED video wall controller/video processor, signal interface units, power and data cabling, and a sturdy mounting frame structure, ensuring proper alignment and fully functional operation of the complete LED video wall system. Approved makes: Christie / Barco / Absen. |
| 794 | Supply, Installation, Testing & Commissioning of Wallplate Transmitter over Cat 6( HDBaseT) upto 70 meter with Inputs 1 HDMI, 1 USB-C & 1 Cat6 (HDBaseT) Output, 2K and 4K support, HDCP 1.4 & 2.3 both Compliant, Up to 60W USB–C charging on USB-C input, PoE acceptor, stereo audio output, 1 RS-232 for device control & 1 RS232 for serial link extension over HDBaseT output, Safety Regularity Compliance : CE, RoHs and WEEE, ISO 9001, ISO 14001, ISO 27001:2013.Approved Make:- Extron/ Kramer/ Lightware. |
| 795 | Supply, Installation, Testing & Commissioning of HDMI Receiver over Cat 6 ( HDBaseT) up to 70m with Input 1 Cat6 (HDBaseT), 1 HDMI Output, 1080p, 2K and 4K@60 4:4:4, HDCP 2.2 Compliant, with IR and RS-232, Compliance : CE, etc complete as required.Approved Make:- Extron/ Kramer/ Lightware. |
| 796 | Supply, Installation, Testing & Commissioning of 2 × 11.25\\" 3-way horn-loaded club speaker system with a frequency response of 90 Hz–23 kHz (-3 dB) and 72 Hz–20 kHz (-10 dB). Power handling: HF 80W/320W peak, MF 80W/320W peak, LF 2 × 500W/2000W peak. It offers 70° × 40° (standard) or 90° × 50° (wide) dispersion with rotatable horns and active crossover at 630 Hz and 6.3 kHz. Impedance: HF 8Ω, MF 8Ω, LF 2 × 8Ω. Max SPL is 137 dB continuous and 143 dB peak. Connectivity includes 2 × NL-8 SpeakON (input & thru). Compatible with or without PW-Six DSP. LF section features dual 11.25\\" Fortex™ weather-resistant cones, MF with 1.4\\" compression driver (3\\" VC), and HF with dual 1.25\\" compression drivers and conical waveguide. Approved Make: British acoustics/ Meyer sound/Martin audio/d&b audiotechnik. |
| 797 | Supply, Installation, Testing & Commissioning of Mounting arragement for Main FOH Speakers. Approved Make: British acoustics/ Meyer sound/Martin audio/d&b audiotechnik. |
| 798 | Supply, Installation, Testing & Commissioning of Dual 18\\" Horn-Loaded High Power Subwoofer System is an ultra-efficient, high-output bass solution engineered to deliver deep, thunderous low frequencies with outstanding clarity and impact. Designed for large-scale live sound applications, concert venues, and high-performance installations, this subwoofer boasts an impressive frequency response of 29 Hz - 190 Hz (-3 dB) and an extended frequency range of 25 Hz - 200 kHz (-10 dB), ensuring unmatched low-end depth and presence. With a continuous power rating of 3000W and peak handling of 12,000W, this subwoofer is built to handle extreme sound pressure levels without distortion. Delivering a maximum SPL of 146 dB and a sensitivity of 100 dB, it ensures superior efficiency, making it a powerhouse for bass-heavy applications that demand precision and power. The subwoofer is equipped with dual 18\\" long excursion ADR drivers, featuring 5.3\\" voice coils (VC) with neodymium magnets, ensuring powerful bass output with excellent heat dissipation and reduced weight for ease of handling. Approved Make: British acoustics/ Meyer sound/Martin audio/d&b audiotechnik. |
| 799 | Supply, installation, testing, and commissioning of 4\\" High-Performance Rimless Ceiling Speaker is an advanced audio solution designed for seamless integration into modern architectural spaces. With a frequency response of 81 Hz – 20 kHz (-3 dB) and an extended range down to 65 Hz (-10 dB), this speaker delivers clear and detailed sound across a wide spectrum. It features a rated power of 60W AES and 240W peak, ensuring reliable performance for both background music and more dynamic audio applications. Designed with a 130° conical dispersion, the speaker provides broad and even sound coverage, making it ideal for commercial and residential installations Approved Make: British acoustics/ Meyer sound/Martin audio/d&b audiotechnik. |
| 800 | Supply, installation, testing, and commissioning of a 5\\" IP67 garden speaker with a frequency response of 68 Hz–20 kHz (–3 dB) and 55 Hz–20 kHz (–10 dB). The speaker delivers 80 W AES (320 W peak) with 99 dB continuous and 105 dB peak SPL, 100° horizontal × 100° vertical dispersion, 8 Ω nominal impedance, and a 2.2 kHz passive crossover. It features a 5\\" low-frequency driver with 1\\" copper voice coil and ferrite magnet, environmental resistance coating, and enhanced porting for full-range performance, and a 1\\" high-frequency driver with ferrite magnet mounted on a contoured waveguide with built-in filtering for clear sound. The unit is weatherproof and suitable for outdoor installations. Approved Make: British acoustics/ Meyer sound/Martin audio/d&b audiotechnik. |
| 801 | Supply, installation, testing, and commissioning of a 7\\" outdoor coaxial speaker with IP64 rating, offering a frequency response of 8 Hz–18 kHz (–3 dB) and 61 Hz–20 kHz (–10 dB). The system delivers 225 W AES (900 W peak) with 115 dB continuous / 121 dB peak SPL, 100° horizontal × 100° vertical dispersion, 8 Ω nominal impedance (selectable 100 W / 70 W), and shielded screw terminal connections. It features a high-power 7\\" coaxial driver with 1.25\\" copper voice coil, ferrite magnet, and environmental resistance coating for reliable outdoor performance. Approved Make: British acoustics/ Meyer sound/Martin audio/d&b audiotechnik. |
| 802 | Supply, installation, testing, and commissioning of a 10\\" outdoor coaxial speaker with IP64 rating, providing a frequency response of 67 Hz–20 kHz (–3 dB) and 55 Hz–20 kHz (–10 dB). The system delivers 450 W AES (1800 W peak) with 122 dB continuous / 128 dB peak SPL, 100° horizontal × 100° vertical dispersion, 8 Ω nominal impedance, and shielded screw terminal connections. It includes passive 1.2 kHz crossover and selectable transformer taps of 15 W / 30 W / 40 W. The high-power 10\\" coaxial driver features a 2\\" copper voice coil, ferrite magnet, and environmental resistance coating for reliable outdoor performance. Approved Make: British acoustics/ Meyer sound/Martin audio/d&b audiotechnik. |
| 803 | Supply, installation, testing, and commissioning of 2 × 2600 W Class H amplifier. Each unit provides 2 output channels rated at 1500 W per channel at 8 Ω, 2600 W at 4 Ω, 2800 W at 2.7 Ω, and 3000 W at 2 Ω, with bridged output capacity of 4500 W at 8 Ω and 6000 W at 4 Ω. The amplifier features 2 analogue inputs, 2 link outputs, and 2 power outputs. Connections are made via XLR connectors for signal input and link output, and Speak-On plus binding post connectors for channel outputs, delivering high-efficiency, professional-grade amplification. Approved Make: British acoustics/ Meyer sound/Martin audio/d&b audiotechnik. |
| 804 | Supply, installation, testing, and commissioning of 2 × 1500 W Class H amplifier. Each amplifier has 2 output channels delivering 900 W per channel at 8 Ω, 1500 W at 4 Ω, 1800 W at 2.7 Ω and 2 Ω, with bridged outputs of 2700 W at 8 Ω and 3600 W at 4 Ω. The units feature 2 analogue inputs, 2 link outputs, and 2 power outputs. Connections are provided via XLR for signal input and link output, and Speak-On plus binding post connectors for channel outputs, ensuring reliable, high-power audio performance. Approved Make: British acoustics/ Meyer sound/Martin audio/d&b audiotechnik. |
| 805 | Supply, installation, testing, and commissioning of 2 × 350 W constant-voltage compatible installation amplifiers. Each unit provides 2 output channels delivering 250 W per channel at 8 Ω, 350 W at 4 Ω, 350 W at 2.7 Ω, with bridged outputs of 700 W at 8 Ω and 1000 W at 4 Ω. The amplifiers include 2 analogue inputs, 2 link outputs, and 2 power outputs. Connectivity is via XLR connectors for signal input and link output, and Speak-On plus binding post connectors for channel outputs, ensuring reliable and flexible audio distribution. Approved Make: British acoustics/ Meyer sound/Martin audio/d&b audiotechnik. |
| 806 | Supply, installation, testing, and commissioning of 2 × 700 W constant-voltage compatible installation amplifiers. Each amplifier provides 2 output channels delivering 400 W per channel at 8 Ω, 700 W at 4 Ω, 700 W at 2.7 Ω, with bridged outputs of 1400 W at 8 Ω and 2000 W at 4 Ω. The units feature 2 analogue inputs, 2 link outputs, and 2 power outputs, with XLR connectors for signal input and link output, and Speak-On plus binding post connectors for channel outputs, ensuring flexible and reliable audio distribution. Approved Make: British acoustics/ Meyer sound/Martin audio/d&b audiotechnik. |
| 807 | Supply, installation, testing, and commissioning of a 400 W Class AB 6-zone mixer amplifier. The unit provides a single channel with six independent zones, delivering 250 W per channel at 8 Ω, 400 W at 4 Ω, 400 W at 2.7 Ω, and 400 W for 100 V or 70 V operation. Inputs include 1 priority mic, 2 additional mic inputs, 2 auxiliary inputs, 1 USB input, 1 wireless input, 1 fireman’s mic, 1 siren input, 1 siren control, and 1 paging network input. Outputs feature 1 direct output (100 V/70 V or low-impedance) and 6 individual zone outputs. Connections are via Euroblock for direct and signal outputs, TRS jack for mic inputs, USB-A for media, and Cat 6 for paging integration. Approved Make: British acoustics/ Meyer sound/Martin audio/d&b audiotechnik. |
| 808 | Supply, installation, testing, and commissioning of a 6-Zone Call Station for providing a reliable paging device with noise-cancelling microphone, easy zone selection, volume control, and talk functions. It supports balanced mic inputs and line-level outputs for PA integration. The unit is housed in a durable enclosure for wall or desktop mounting and features visual zone indicators. Installation involves secure mounting, wiring, and power setup as per specs. Testing ensures clear audio, accurate zone activation, and system reliability, complying with safety standards. Complete documentation and test reports will be provided. Approved Make: British acoustics/ Meyer sound/Martin audio/d&b audiotechnik. |
| 809 | Supply, Installation, Testing & Commissioning of 4-IN 8-OUT Loudspeaker Processor, Matrix & Controller with 4 analogue inputs, 8 analogue outputs, and 96 kHz DSP on all channels. Audio performance: impedance >10 kΩ, CMRR >60 dB, min. load 600 Ω, frequency response 10 Hz–40 kHz, dynamic range >116 dB, THD <0.004%. Crossovers: Linkwitz-Riley, Bessel, Butterworth (12/24/36/48 dB/oct). EQ: 6 filters per input/output (parametric, low/high-shelf, all-pass), plus 2 dynamic EQ filters per input with adjustable threshold, ratio, attack/release. Dynamics include visual compressor, automatic gate compensation, and output limiters. Control & monitoring via 4 input/8 output meters, LED display, DSP control panel. Connectors: 4 XLR inputs, 8 XLR outputs, RS-485 (ETH/Euroblock), USB Type-B. Power: 85–230 VAC, 50/60 Hz; nominal consumption 1 A @ 240 V, 2 A @ 120 V. Approved Make: British acoustics/ Meyer sound/Martin/d&b audiotechnik. |
| 810 | Supply, Installation, Testing & Commissioning of 20-Channel Analogue Mixing Desk with Dual FX featuring 16 mic/line XLR inputs, 2 stereo line TRS inputs, USB audio playback/recording, and wireless media input. Outputs include stereo L/R, 4 group, 3 aux, and phones output. The desk has an 8-bus mixer: stereo L/R, 4 groups, and 3 auxes. Input strips provide dedicated metering, +48V phantom power, 20 dB pad, 3-band EQ, aux/FX sends, L/R panning, peak/solo PFL, and group selection. FX & features include Class-A PSL preamps, Oliver FX engine with preset library, individual return channels for FX1 & FX2, iPhone/Android/PC/Mac sound card compatibility, and 7-band stereo graphic EQ. THD+N: 0.03% (mic input to L/R at 30 dB gain), 0.015% (mic input to L/R at 0 dB gain), 0.04% (line input to L/R at 30 dB gain); input CMRR >60 dB.Approved Make: British acoustics/ Digico/ Wave / Yamaha / Midas /allen-heath. |
| 811 | Supply, Installation, Testing & Commissioning of Wireless Handheld Microphone Transmitter with Receiver: The wireless handheld microphone shall feature a display on the transmitter, be of dynamic type, and have an RF power output of 30 mW. The microphone shall use a cardioid polar pattern, provide a frequency response of 55 Hz to 20 kHz, and include a mute button on the transmitter. It shall operate on rechargeable batteries with 8 hours of operation, offer a wireless range of 100 meters, and use PLL synthesized circuits for frequency stability.Approved Makes: Clearone/OSL/Shure / Sennheiser. |
| 812 | Supply, Installation, Testing & Commissioning of Wireless Lapel and Headworn Transmitter: The wireless lapel and headworn microphone shall have an RF power output of 30 mW, frequency response of 20 Hz to 20 kHz, and include volume and mute controls on the transmitter. It shall operate on rechargeable batteries with 8 hours of operation, provide a wireless range of 100 meters, and use PLL synthesized circuits for stable frequency transmission.Approved Makes: Clearone/OSL/Shure / Sennheiser. |
| 813 | Supply, Installation, Testing & Commissioning of Vocal Wired Microphone: The vocal wired microphone shall be of dynamic type with a cardioid polar pattern, frequency response of 80 Hz to 18 kHz, and maximum SPL of 150 dB. It shall feature an all-metal housing, mute switch, foam protector to reduce wind and pop noise, and include an anti-glide microphone holder..Approved Makes: OSL/Shure / Sennheiser. |
| 814 | Supply, Installation, Testing & Commissioning of Instrument Condenser Microphone: The instrument condenser microphone shall be of hybrid condenser type with a cardioid polar pattern, frequency response of 80 Hz to 18 kHz, and maximum SPL of 129 dB. It shall feature an all-metal housing and a mute switch.Approved Makes: OSL/Shure / Sennheiser. |
| 815 | Supply, Installation, Testing & Commissioning of Light weight tripod alluminium Microphone stand with Long Arm, boom type & black anodized finish. Approved Makes: - My stand/ Amp Luxe /Netmas. |
| 816 | Supply, Installation, Testing & Commissioning of Light weight tripod alluminium Microphone stand with Short Arm, boom type & black anodized finish. Approved Makes: - My stand/ Amp Luxe /Netmas. |
| 817 | Supply, Installation, Testing and Commissioning of Customized Floor Box with 4x Mic In, 1x Speaker Out. Approved Makes: - My stand/ Amp Luxe /Netmas. |
| 818 | Supply, installation, testing, and commissioning of Speaker Cable – 1.5 Sqmm (80/0.20mm) x 2 core cable ATC copper conductor PVC insulated, core twisted, outer jacketed with Vasiform Type PVC Sheath. Approved Make:- Kramer / Belden/Netmas |
| 819 | Supply, Installation, Testing and Commissioning of Speaker Cable – 2.5 Sqmm (80/0.20mm) x 2 core cable ATC copper conductor PVC insulated, core twisted, outer jacketed with Vasiform Type PVC Sheath.Approved Make:- Kramer/ Belden/Netmas. |
| 820 | Supply, Installation, Testing and Commissioning of 18 AWG microphone cable (24/0.20mm) x 2 core ATC copper conductor, PE insulated, core twisted in a circular form, Inner sheathed with moisture Proof Polymer, braid shielded (80%) with ATC copper, outer Jacketed with Matt finish Rugged Flexible PVC.Approved Make:- Kramer/ Belden/Netmas. |
| 821 | Supply, Installation, Testing and Commissioning of 8 Pair Snake Microphone Cable. Approved Make:- Kramer/ Belden/Netmas. |
| 822 | Supply, Installation, Testing and Commissioning of 1.8 Metres 4K HDMI patch cord in existing conduit. Approved Make:- RGB Spectrum/ Kramer/ Lightware. |
| 823 | Supply and Laying of HDBaseT recommanded 23 AWG shielded CAT6A Cable with appropriate connectors in existing conduit. Approved Make:- RGB Spectrum/ Kramer/ Lightware. |
| 824 | Supply, Installation, Testing and Commissioning of for Auditorium, bulk connectors such as XLR (Male & female), RJ-45, Speakon, Phono, Stereo Jack, velcro tape, cable ties etc as per site requirement.Approved Make:- Neutrik / Amphenol / Netmas. |
| 825 | Supply, Installation,Testing & Commissioning of 36U Equipment rack to house all rack mountable equipment, with internal wiring, front glass door,heat dissipation fans,power distribution units etc.complete with standard accessories as required.Approved Make: Valrack/Chief/Middle Atlantica/Netmas. |
| 826 | Supply, Installation,Testing & Commissioning of 42U Equipment rack to house all rack mountable equipment, with internal wiring, front glass door,heat dissipation fans,power distribution units etc.complete with standard accessories as required.Approved Make: Valrack/Chief/Middle Atlantica/Netmas. Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail