| 1 | M&L for sub-main wiring in repairs complete with PVC insulated & unsheathed two run of 2.5 Sqmm single core multi stranded copper copnductor cable (FRLSH) 1100 Volt grade along with one run of 2.5 Sqmm PVC insulated & Unsheathed copper conductor cable (FR-LSH) 1100 Volt grade connected to common earth dolly as earth continuty conductor, drawn through 20 mm dia PVC Casing Caping complete all as specified and as directed NOTE:- Two runs of 2.5.0 Sq mm +one run of 2.5 Sq mm and one run of PVC casing caping and its accessories of suitable size shall be measured as one unit length. |
| 2 | M&L for sub-main wiring in repairs complete with two run of 4.0 Sq mm and one run of 4.0 Sq mm for earth wire with multi standard copper conductors, 1100 volts grade, drawn through and including casing caping complete all as specified and as directed. NOTE:- Two runs of 4.0 Sq mm +one run of 4.0 Sq mm and one run of PVC casing caping and its accessories of suitable size shall be measured as one unit length. |
| 3 | M&L for sub-main wiring in repairs complete with two run 6.0 Sq mm and one run of 6.0 Sq mm for earth wire with multi standard copper conductors, 1100 volts grade, drawn through and including casing caping complete all as specified and as directed. NOTE:- Two runs of 6.0 Sq mm +one run of 6.0 Sq mm and one run of PVC casing caping and its accessories of suitable size shall be measured as one unit length. |
| 4 | M&L for sub-main wiring in repairs complete with four run 6.0 Sq mm and one run of 6.0 Sq mm for earth wire with multi standard copper conductors, 1100 volts grade, drawn through and including casing caping complete all as specified and as directed. NOTE:- four runs of 6.0 Sq mm +one run of 6.0 Sq mm and one run of PVC casing caping and its accessories of suitable size shall be measured as one unit length. |
| 5 | M&L for sub-main wiring in repairs complete with four run 10.0 Sq mm and one run of 10.0 Sq mm for earth wire with multi standard copper conductors, 1100 volts grade, drawn through and including casing caping complete all as specified and as directed. NOTE:- four runs of 10.0 Sq mm +one run of 10.0 Sq mm and one run of PVC casing caping and its accessories of suitable size shall be measured as one unit length. |
| 6 | S&F in repairs MCB Distribution board double door type SPN 12 way, sheet steel, powder painted, with bus bar neutral link & earth bar etc. and fixing MCBs of various rating capacity complete all as specified and as directed. |
| 7 | S&F in repairs MCB Distribution board double door type SPN 8 way, sheet steel, powder painted, with bus bar neutral link & earth bar etc. and fixing MCBs of various rating capacity complete all as specified and as directed. |
| 8 | S&F in repairs MCB Distribution board double door type SPN 4 way, sheet steel, powder painted, with bus bar neutral link & earth bar etc. and fixing MCBs of various rating capacity complete all as specified and as directed. |
| 9 | S&F in repairs Motion Sensing 20 Watt Tubelight 4Ft complete all as speified and as directed. |
| 10 | S&F in repairs Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 32 Amps complete all as specified and as directed. |
| 11 | S&F in repairs MCB TPN 40 Amps, 415V, 10KA 'C' curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the DB complete with connection testing and commissioning complete all specified and as directed. |
| 12 | S&F in repairs MCB TPN 63 Amps, 415V, 10KA 'C' curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the DB complete with connection testing and commissioning complete all specified and as directed. |
| 13 | S&F in repairs MCB TPN 100 Amps, 415V, 10KA 'C' curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the DB complete with connection testing and commissioning complete all specified and as directed. |
| 14 | S&F in repairs MCB SPN 32 Amp rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the MCB DB complete with connection testing and commissioning MCB DB complete all as specified and as directed |
| 15 | S&F in repairs MCB SPN 63 Amp rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the MCB DB complete with connection testing and commissioning MCB DB complete all as specified and as directed |
| 16 | S&F in repairs MCB SP 6 to 32 Amp rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the MCB DB complete with connection testing and commissioning MCB DB incl taking down old unsv MCB complete all as specified and as directed |
| 17 | S&F in repairs VTPN DPX 4 way,double door 415 Volts, 50 Hz, IP 43 IK 09 sheet steel, powder painted, with 02 neutral link & 02 earth bar and cable ties for cable management suitable for fixing of MCCB as incomer and MCB SP/TP as outgoing MCB DBs complete all as specified and as directed. |
| 18 | S&F in repairs MCCB 4 Pole, 415 V, Adjustable type, 160 Amps with breaking capacity 25 KA complete all as specified and as directed. |
| 19 | S&F in repairs MCCB 4 Pole, 415 V, Adjustable type, 125 Amps with breaking capacity 16 KA complete all as specified and as directed. |
| 20 | S&F in repairs MCCB 4 Pole, 415 V, Adjustable type, 100 Amps with breaking capacity 16 KA complete all as specified and as directed. |
| 21 | S&F in repairs MCCB 4 Pole, 415 V, Adjustable type, 63 Amps with breaking capacity 16 KA complete all as specified and as directed. |
| 22 | S&F in repairs MCB Distribution board double door type TPN 4 way, sheet steel, powder painted, with bus bar neutral link & earth bar etc. and fixing MCBs of various rating capacity complete all as specified and as directed. |
| 23 | S&F in repairs 1100 Volts grade heavy duty cable PVC insulated aluminium conductor served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hanger not more than 1 meter apart including 4 mm suspension wire one twine core cable flat or circular stranded conductor of size 4 Sqmm complete all as specified and directed. |
| 24 | S&F in repairs 1100 volts grade heavy duty cable PVC insulated aluminium conductor, 10 Sqmm served with inner sheathing of PVC tape and overall PVC sheathed in service connections complete all as specified and directed by Engr-in-Charge |
| 25 | S&F in repairs 1100 volts grade heavy duty cable PVC insulated aluminium conductor, 6 Sqmm served with inner sheathing of PVC tape and overall PVC sheathed in service connections complete all as specified and directed by Engr-in-Charge |
| 26 | S&F in repairs 1100 volts grade heavy duty cable PVC insulated aluminium conductor, 16 Sqmm served with inner sheathing of PVC tape and overall PVC sheathed in service connections complete all as specified and directed by Engr-in-Charge |
| 27 | Supply , fixing and testing in repairs/replacement of LED Bldg Security light fitting of capacity 25 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete with and including 1.2 mtr GI bracket of 25mm bore light grade bent to shape and fixed on wall with metal fastners 2 Nos 10mm dia incl drilling of holes as reqd and connecting up with flexible copper cable of size 0.75 sqmm 3 core from ceiling rose to the light fitting and complete all as specified and as directed by Engr-in-Charge. |
| 28 | M & L for Earthing complete with galvanized steel earth plate 60cm x 60cm x 6mm thick electrode, burried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to GI strip 32 x 6mm size up to test point by means of nuts, bolts, check nuts and washers of GI including excavation and earth work, PCC (1:3:6) type C-1 pit, 20mm bore dia GI pipe, medium grade pipe for watering arrangement and 40 mm bore dia GI pipe, light grade for protection of earth strip, 50mm thick RCC nominal mix (1:2:4) type B-1 cover reinforced with 8mm dia TMT bars @ 15cm C/C both ways and with handle made out of 10mm dia bars, funnel, wire mesh etc. as shown in electrical Plate No. 03 of SSR Part-I connected to earthing test point including taking down old unserviceable material and testing on completion etc complete all as specified and as directed. |
| 29 | M&L for test point terminal block made of gun metal or phosphorus bronze size 75 x 75 x 25 mm, drilled and screwed including 3 nos. 8 mm dia 25 mm long hex. Head screw complete all as specified and as directed. |
| 30 | M&L for Air termination, single pointed aluminium rod 12 mm dia and 300 mm long any height complete all as specified and as directed. Please Enable Macros to View BoQ information |
| 31 | M&L for Air termination, single pointed aluminium rod 12 mm dia and 300 mm long any height complete all as specified and as directed. Please Enable Macros to View BoQ information |