| 1 | Supply , Installation , testing and commissioning of standard 4.0 Mtr. High (above ground) hot dip galvanized (grading of galvenisation average 70 micron or better as per IS 2629 or equivalent) pole, with stiffener, chain, allen bolt, foundation, single arm bracket, template, nut and bolts galvanized, factory finish base plate of size 200x200x12mm etc complete as required. The pole shall be made of 3mm thickness sheet with tolerance of +/- 5%. The column shall also be provided with flush door at the bottom with proper strengthening to the cutout of the door opening, a junction/loop box with heavy duty 3 phase , 32 Amp. connector with 16A DP MCB including all accessories complete as required derected by E/I.(Make - Bajaj/Valmont/Transrail) |
| 2 | S/Fixing of LED Street Light fitting having die cast Aluminium body and difuser with driver set suitable for 52 to 72 watt. Confirming to IP-66 and above protection. Complete in all respects. (PS No. 1422) Cat-AA (Make -LT/Bajaj/Havells /Crompton/Philips/Wipro |
| 3 | Supplying and laying of aluminium conductor PVC insulated armoured, served, sheathed cable 1100 Volts grade at a depth of 750 mm. below ground level over a cushion of 75 mm. thick sand alround and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. Clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respects. the armouring of the cable shall be properly connected with the earth conductor by clamps etc. P.S. No. 501 (Polycab, KEI Havell's make) |
| 4 | (1) 16 Sq.mm. 4.0 Core (PS No. 501) |
| 5 | (2) 50 Sq.mm. 3.5 Core (PS No. 501) |
| 6 | S/F of palm or pin type copper tin plated cable socket (lugs) to the cable leads, insulating with tape and making connection etc. complete in all respects as per direction of E/I. P.S No. 504. |
| 7 | a) 16 Sq.mm. |
| 8 | b) 50 Sq.mm. |
| 9 | S/Laying of 90 mm dia (OD 90 mm & ID 76 mm nominal) size of (DWC) HDPE Pipes ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part-II complete with filling and cutting, jointing etc. direct in ground ( 75 cm below ground level) including excavation and refilling the trench pat excluding sand cushioning and protective covering etc. Complete in all respects.( with Trenchless method) Rex/Duraline/Time/CPE make. (AOR) |
| 10 | S/Laying of 63 mm dia (OD 63 mm & ID 51 mm nominal) size of (DWC) HDPE Pipes ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part-II complete with filling and cutting, jointing etc. direct in ground ( 75 cm below ground level) including excavation and refilling the trench or Trenchless method if required but excluding sand cushioning and protective covering etc. Complete in all respects. Rex/Duraline/Time/CPE make. as per DSR 2018 item no. 14.16.1 page no. 49 |
| 11 | Supply and fixing of 40 Amp TPN capacity of automatic street light cubical control panel painted with anti corrosive alkali and acid proof paint crossing of time switch TSO 100 series with contractors, HRC fuse, isolating swtich metering instrument & instrument box with CTs etc. in case of TPN, Complete in all respects. as per PS No. 807F |
| 12 | Supply and burring of Safe Earthing Electrode T-19 (Hot Dip Galvanized), Length up to 2000mm, outer pipe 50mm, inner pipe 25, terminal Dia 12 mm, outer GI pipe of 16 swg and inner GI pipe of 12 swg with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame with hinged cover & masonry husing (from electrode terminal to switch board, cost of 25 x 3 G.I . strip will be extra) Make: As approved in U.P. P.W.D., & C.P.R.I. Certified.(P.S. No 725A) |
| 13 | Supply and burring of Safe Earthing Electrode T-19 (Hot Dip Galvanized), Length up to 3000mm, outer pipe 50mm, inner dia 25mm, terminal Dia 12 mm, outer GI pipe of 16 swg and inner GI pipe of 12 swg with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame with hinged cover & masonry husing (from electrode terminal to switch board, cost of 25 x 3 G.I . strip will be extra) Make: As approved in U.P. P.W.D., & C.P.R.I. Certified.(P.S. No 725B) |
| 14 | Supply & erection of overhead line with G.I. wire no. 8 to 4 SWG on poles/serivce bracket including binding etc. complete in all respect. as per PS No. 628 |
| 15 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. (DSR Elect 2018/1.17.3/P-4) |
| 16 | 3 x 1.5 sq. mm |
| 17 | Taking out existing CC interlocking paver blocks from footpath/ central verge, including removal of rubbish etc., disposal of unserviceable material to the dumping ground, for which payment shall be made separately and stacking of serviceable material within 50 metre lead as per direction of Engineer-in-Charge.(AOR) |
| 18 | Laying old cement cocrete interlocking paver blocks of any design/ shape laid in required line, level, curvature, colour and pattern over and including 50 mm thick compacted bed of coarse sand, filling the joints with fine sand etc. all complete as per the direction of Engineerin-charge. (Old CC paver blocks shall be supplied by the department free of cost). |
| 19 | Providing and laying 60mm thick factory made cement concrete interlocking paver block kof M-30 grade made by block making machine with strong vibratory compaction of approved size, design & shape, laid in required colour and pattern over and including 50mm thick compacted bed of coarse sand, filling the joints with line sand etc. all complete as per the direction of E/I (AOR) |
| 20 | Dismantling of pole/street Lightr standard / strut embedded in cement concrete foundation etc. as per required (DSR -2018/Item No. 12.42 P-46) |
| 21 | Demolishing cement concrete manually/ by mechanical means including disposal of material with in 50 Mtr. Lead as per direction of E/I. Nominal concrete 1:3:6 or richer mix(i/c equivalent design mix) (DSR civil I No. 15.2.1/P-258) |
| 22 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) Please Enable Macros to View BoQ information |