| 1 | Excavation in trenches in Soft / loose soil not exc. 1.5 mtr wide and n. exc. 1.50 m deep for laying of HT under ground cable and getting out including forming bottom surface to required level or slope, complete all as specified and directed. (The excavation should be carried out Manually and excavation considered for only DWC length / GI PIPE) |
| 2 | Returning filling in hard/dense soil including spreading, levelling, watering and well ramming in layers not exceeding 25cm complete all as specified and as directed |
| 3 | Removal of surplus excavated (soil) to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.50m above the starting point complete all as specified and as directed. |
| 4 | M&L laying of GI pipe 80 mm bore, medium grade for passing through cables under the floor / road etc complete all as specified and directed. |
| 5 | Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6.00 mm thick buried directly in ground [earth pit not less than 2.25 metre deep below normal ground level] with top edge of the plate electrode not less than 1.5 m below normal ground level, connected to including galvanised iron strip size 32 x 6 mm by means of bolts, nuts, and washers of galvanized iron or steel all as shown in electrical plate No. 3 of SSR Part I connected to earth test point including provision of earth strip protected by 40 mm dia light grade GI pipe & watering pipe shall be 20 mm bore medium grade GI pipe including all excavation and earth work in any type of strata, PCC pit with RCC cover, CI frame, char coal, salt & funnel etc complete all as specified or indicated including testing on completion. Rate to be considered for earth strip to be fixed 7.5 m long.all as specified and directed by Engr-in-charge. |
| 6 | Dismantling/Taking out of old Unsv HT cable of size 95 Sq mm from any location complete along with earth work manually with out damaging of the HT cable and making the surface good all as specified and directed by Engr in Charge.Note: Earth work will be common for both removal an laying new cable in same route |
| 7 | Re laying, jointing, testing and commissioning existing healthy Span of HT XLPE cable cross sectional area of any size removed from above item and re laying in DWC pipe / ducts / trenches, under floor and road or fixed to wall etc complete all as specified and directed. |
| 8 | Supply, laying, jointing, testing and commissioning HT XLPE cable cross sectional area 95 Sqmm 3 core, 11000 volt screened, PVC bedded \\"Earthed grade\\" insulated bedded, galvanized steel (Heavy duty) strip armoured with aluminium conductor 11 KV pressure earth system conforming to IS-7098 (Part-I) 1977 and Part-II of 1985 laid in pipe / ducts / trenches, under floor and road or fixed to wall etc complete all as specified and directed.Note: The length of one HT Cable Drum shall not less than 280 RM from the mentioned quantity |
| 9 | Supplyand laying DWC pipe SN-8 with coupler 75 mm OD,ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. laid in trenches/ fixed to pole /laying under road crossing/fixed on pavement walls with clamps complete all as specified and as directed. |
| 10 | M&L in replacement of end terminal joints kits cold shrinkable suitable for HT 11000 V (Earthed), XLPE insulated armoured heavy duty under ground cable including joint kits complete for making joints suitable for aluminium conductor cable of cross sectiona larea 95 Sqmm, 3 core, complete all as specified and directed. |
| 11 | M&L including supply of straight through heat shrinkable suitable for HT 11000 V (Earthed), XLPE insulated armoured heavy duty under ground cable including joint kits complete for making joints suitable for aluminium conductor cable of cross sectiona larea 95 Sqmm, 3 core, complete all as specified and directed. Please Enable Macros to View BoQ information |
| 12 | M&L including supply of straight through heat shrinkable suitable for HT 11000 V (Earthed), XLPE insulated armoured heavy duty under ground cable including joint kits complete for making joints suitable for aluminium conductor cable of cross sectiona larea 95 Sqmm, 3 core, complete all as specified and directed. Please Enable Macros to View BoQ information |