| 1 | Wiring for light point / fan point / exhaust fan point / call bell point with 1.50 Sq. mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable G I box and earthing the point with 1.50 sq. mm FRLS PVC insulated copper conductor single core etc. as required. --- Group B |
| 2 | Wiring for light / power plug with 2 x 4.00 sq. mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, along with 1 No. 4.00 sq. mm FRLS PVC insulated copper conductor single core for loop earthing as required. |
| 3 | Supply and drawing following size of FRLS PVC insulated copper conductor, single core cable in the existing surface / ressesed surface/ PVC cuduict as required---5x2.5 Sq.mm (For DB3 ) 25mtr |
| 4 | 2x4 Sq.mm (DB1& DB4) 120+102+8 Mtr |
| 5 | 3x4 Sq.mm ( DB1, DB2, DB4) 142+226+37 Mtr |
| 6 | 4x4 Sq.mm (DB4) 16mtr |
| 7 | 5x4 Sq.mm (DB3) 36 mtr |
| 8 | 3x6 Sq.mm ( DB4) 10mtr |
| 9 | Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit as required. -- 4 x 10.00 sq. mm + 2 X 6.00 sq. mm earth wire (DB1,DB3, DB4) 57+15+78 mtr |
| 10 | 4 x 16.00 sq. mm + 2 X 6.00 sq. mm earth wire (DB3) 26mtr |
| 11 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but modular plate etc. as required. |
| 12 | Supplying and fixing suitable size G I box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 13 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. :1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 |
| 14 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc.. as required. -- Upto 450 mm sweep. |
| 15 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) ---- 8 Way (4+24) Double Door VTPN |
| 16 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.10 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required.---Above 35.00 sq. mm and upto 95.00 sq. mm |
| 17 | Above 185.00 sq. mm and upto 400.00 sq. mm |
| 18 | Supply and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.10 KV grade as required.---3.50 x 50.00 sq. mm (32 mm) |
| 19 | 3.5 x 300.00 Sq.mm ( 70mm) |
| 20 | Earthing with G I earth plate 600 mm x 600 mm x 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.70 metre long ete with charcoal / coke and salt as required. |
| 21 | Providing and fixing 25 mm x 5 mm G I strip on surface or in recess for connections etc. as required. |
| 22 | S & F sheet steel enclosure for T.P./Four Pole MCB.PWD E&M SOR 2018 |
| 23 | Supply and fixing of 40/63 Amp MCB(10KA)C Curve ---40 Amp.Four pole |
| 24 | 63 Amp. Four pole |
| 25 | S&F of 40 Amp. TP MCB (10 KA) C Curve |
| 26 | S&F of 63 Amp. TP MCB (10 KA) C Curve |
| 27 | Supply and fixing of LED Street Light fitting with mandatory driver set having die cast aluminium body and lences suitable for 45 Watt to 50 Watt, confirming to IP 65/66 protection having Company LOGO Engraved complete in all respects including labour. Mid power LED with lences, 100 lm / Watt, PF > 0.95, THD < 10 % at full load, CRI > 70, Potted driver set (not circulatory) , with 3 year warranty. |
| 28 | Supply of Exhaust fan (Not fresh air fan) 450 mm sweep, double ball bearing complete in all respects. Usha / Crompton / Khaitan / Bajaj / Havells make. |
| 29 | S&F of 125 Amp 4 pole MCCB (25 KA) ThermalMagnetic release Cat AAA |
| 30 | S&F of 400 Amp. four pole change over switch on 50mm x50mm x 6mm angle iron frame, including the cost of labour,T&P, painting and other material required for propercompletion of the work as per direction and satisfaction ofEngineer in charge. |
| 31 | Supply, installation, testing and commissioning of electrical panel, modular type, front accessible only, free floor standing confirming to Minimum IP:43 degree of protection. The panel sheet structure shall undergo seven tank pre-treatment process before painting. The sheet steel shall be all of 2.0mm thick CRCA sheet. All the openable compartments of the panel shall be completely shrouded and provided with padlocking arrangement on all compartments including bus bar and cable alley chambers. The panel height shall not exceed 2200mm and the maximum operating height for any switchgear shall not be more than 1700mm. The panel shall be provided with minimum 75mm base channel frame fabricated from ISMC sections. All bus bar links in the panel shall be solid bus bars with coloured PVC shrinkable sleeves, no wires will be acceptable. Continuous earth bus shall run alround the panel with earthing studs provided at minimum 2 places. The control wiring shall be carried out with minimum 1.5/2.5 sqmm copper wires and adequate number of NO/NC, potential free contacts incorporated for remote operation of the starters. Proper sized cable termination gland plates shall be provided on cable alleys and knockouts for same shall be provided during fabrication stage itself. The panel shall be provided with a thermostatically controlled heating arrangement (200 W) to take care of high humidity conditions. A 5A socket service outlet (single phase) shall be provided in one of the compartments as ervice outlet in the panel. Panel shall be so designed at to have minimum 20% spare feeders/space. Panel shall undergo epoxy powder coated paint, colour as per IS:5 requirement. All cable terminations shall be from top. The complete panel shall be fuse less type, for control circuits 2A/6A MCB's to be used.ll bus bars shall be of aluminium, electrolytic grade only. Maximum design density shall not exceed 1 Amps/Sqmm. All bus bars shall be insulated with coloured heat shrinkable PVC sleeved. All bus bar supports shall be non hygroscopic DMC/SMC supports. The panel shall be manufactured in conformance to requirements of local electrical inspector and it shall be contractors responsibility to get initial approval of drawings and also final approval of complete electrical works related to this section. , ---- Panel described as above |
| 32 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections /appropriate Z sections and other sections of approved makeconforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required includingcleat angle, Aluminium snap beading for glazing / paneling, C.P.brass / stainless steel screws, all complete as per architecturaldrawings and the directions of Engineer-in-charge. (Glazing, panelingand dash fasteners to be paid for separately) : For fixed portion: Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 33 | Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS: 12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of engineerin-charge.: Pre-laminated particle board with decorative lamination on both sides |
| 34 | Providing and fixing aluminium tubular handle bar 32 mm outer dia, 3.0 mm thick & 2100 mm long with SS screws etc .complete as per direction of Engineer-in-Charge. : Powder coated minimum thickness 50 micron aluminium tubular handle bar |
| 35 | Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete : 300x10 mm |
| 36 | Providing and fixing aluminium sliding door bolts, ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868), transparent or dyed to required colour or shade, with nuts and screws etc. complete :300x16 mm |
| 37 | Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc.complete:125mm |
| 38 | Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS:1868 transparent or dyed to required colour and shade, with necessary screws etc. complete.Single rubber stopper |
| 39 | Providing and fixing Brass 100mm mortice latch and lock with 6 levers without pair of handles (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete. |
| 40 | Providing & fixing fly proof wire gauze to windows, clerestory windows & doors with M.S. Flat 15x3 mm and nuts & bolts complete.Stainless steel (grade 304) wire gauze of 0.5 mm dia wire and 1.4 mm aperture on both sides |
| 41 | Providing and fixixng mirror of superior glass( of approved quality) and of required shape and size with plastic moulded frame of approved make and shade with 6mm thick hard board backing: Rectangular shape 453x357 mm |
| 42 | Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete. Fixed to steel windows by welding. (by weight)---forn drain cover |
| 43 | Providing and fixing 1mm thick M.S. sheet door with frame of 40x40x6 mm angle iron and 3 mm M.S. gusset plates at the junctions and corners, all necessary fittings complete, including applying a priming coat of approved steel primer.Using M.S. angels 40x40x6 mm for diagonal braces. |
| 44 | Drilling suitable holes in reinforced or plain cement concrete with power driven drill machine to a minimum depth of 100mm upto 200mm in RCC beams, lintels, columns and slabs to introduce steel bars for sunshades/balconies including fixing the steel bars in position using epoxy resin anchor grout of approved make but excluding the cost of reinforcement, all complete as per direction of Engineer-In-Charge. ----Upto and including 12mm dia. |
| 45 | P/F of Flush Door shutter confroming to IS:2202(Part 1) Non decorative Type Single leaf. |
| 46 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade :Two or more coats on new wood work over an under coat of suitable shade . Please Enable Macros to View BoQ information |