| 1 | Dismantling of steel tubular swaged pole 11 mtr long by breaking PCC and removing from site complete all as specified and directed. |
| 2 | Dsimantling and taking down OH ACSR conductor of any size from poles complete all as specified. |
| 3 | Dsimantling and taking down insulator conductor of any size from poles complete all as specified. |
| 4 | Dismantling of cross arms, brancings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers complete all as specified and directed. |
| 5 | Excavatingin trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for laying of cable, foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and getting out in soft/loose soil including forming bottom surface to required level or slope, complete all as specified and directed. |
| 6 | Excavatingin trenches, n exc 1.5 m wide and exc 1.5 m in depth and n exc 3.0 m depth; for laying of cable, foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and and getting out in soft/ loose soil including forming bottom surface to required level or slope, complete all as specified and directed. |
| 7 | Returnig, filling in, including spreading, leveling , watering and well ramming in layers not exc 25 cm in soft / loose soil complete all as specified and directed by Engr-in-charge. |
| 8 | Removing excavated material n. exc 50m and depositing where directed at a level n. exc. 1.5 m above the starting point complete all as specified and directed by Engr-in-charge. |
| 9 | Material and labour for sand cushioning / sand covering for underground cable protection and consolidated and compected with clean dry sand complete all as specified and directed by Engr-in-charge. |
| 10 | Supplying and laying unreinforced precast cement concrete cable covers,ISI Marked Class HV, Flat, Type - 1, of size 300 mm X 180 mm X 40mm in trenches for cable protection, embossed with \\"ELECTRIC\\" on the top surface complete all as specified and as directed by the Engineer - in - Charge. |
| 11 | M&L for cement concrete in foundation, filling mass concrete type-C2, 1:3:6, (40mm graded aggregate) for pole foundation & finishing the surface even & smooth without using extra cement incl necessary formwork complete all as specified & as directed. |
| 12 | M&L for RCC (nomial mix) type B1 1:2:4 with using 20mm graded stone agg as in foundations, including rafts, footings, foundation beam, plinth beams and bases of columns basement slabs, and mass concrete. |
| 13 | M&L for PCC (1:4:8) type B-1 (using 20 mm graded aggregate) as in foundation of pole etc complete all as specified and as directed. |
| 14 | M&L for RCC (nomial mix) type B1 1 :2:4 ( using 20mm graded stone agg) in Columns, pillars, piers, posts and struts complete all as specified and as directed. |
| 15 | M&L for RCC B1 1:2:4 with using 20mm graded stone aggregate as in Beams, cantilevers, bressummers, lintels over 1.5m span complete all as specified and as directed. |
| 16 | M&L for reinforced cement concrete (nominal mix) (1:2:4), type B1 (using 20 mm graded stone aggregate) as in slabs supported on walls, beams and columns in floors, roofs, landings, balconies, canopies, deck slabs and in shelves and the like, complete all as specified and directed.. |
| 17 | M&L for Formwork to sides of rough finished flat surfaces of concrete foundations, footings, bases of columns, raft and raft beams, sides and soffits (if any) of foundation and plinth beams; and similar work, vertical or to batter complete all as specified and as directed. |
| 18 | M&L for Formwork to sides of rough finished square, rectangular or polygonal surfaces of concrete of pillars, posts, struts, piers, columns, fair finished surface. |
| 19 | Formwork to sides and soffits of floor or roof beams, beam haunchings, girders, bressummers, lintels, slab cantilevers, shelves including supports, overhangs, etc. also splays between floors and beams, etc and finished rough surfaces of concrete flat complete all as specified and as directed. |
| 20 | Formwork to soffits of suspended slabs such as roof slabs , floorslabs ,landing and similar work not exc 200 mm thick (horizontal or slope) complete all as specified and as directed. |
| 21 | M&L for mild steel TMT bars 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with the including mild steel wire (annealed) not less than 0.9mm dia or securing complete all as specified and as directed. |
| 22 | Ditto all as per item ser No 8 as above but 5mm dia and over upto and including 10mm dia in stirrups, spacers and binders |
| 23 | M & L Brickwork with subclass ‘B’ bricks, straight or curved on plan exc 6m mean radius, built in cement mortar 1:6 complete all as specified and directed. |
| 24 | Taking up old U/S HT cable any size & type from the trenches of pipe including taking out brick cable protection as directed(Excavation and earth work if any measured & paid separately). |
| 25 | Take down old U/S jionting kit 11 KV, any type & any size complete all as specified and as directed by Engr -In - Charge. |
| 26 | Supply and laying in replacement of unserviceable cable HT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (Heavy duty) with aluminum conductor, 11000 volts (Earthed), grade cross sectional area 95 Sqmm 3 core coMplete all as specified and directed by Engr-in-charge. |
| 27 | Supply and fixed in replacement of unserviceable Cable jointing kit for 11 KV (Earthed) grade cable for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm coplete all as specified. |
| 28 | Supply and fixed in replacement of unserviceable Cable jointing kit for 11 KV (Earthed) grade cable for indoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm coplete all as specified. |
| 29 | Supply and fixed in replacement of unserviceable Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm coplete all as specified. |
| 30 | Supply, transportation, fixing and erection of steel tubular sewaged pole 11 mtr long complete with MS base plate, final taper plug nut bolts, scres as specified type 410 SP-55 as per relevant IS specification including two coats of aluminium paint over a coat of red oxide primer and inclusing making alternate red and black strips 30 cm height (Total 5 Nos) compete all as specified and directed. (excavation and PCC will be measuered and paid seperately) |
| 31 | Supply and fixing of Switch air break, gang operated triple pole mechnically operated mounted on with 9 insulators and steel frame with operating mechanism working from ground level current rating upto 200A, |
| 32 | Supply and fixing of expulsion drop out fuse carrier assembly outdoor & channel type 100 Amps capacity and insulators suitable for HT 11 KV complete all as specified and as directed. |
| 33 | M&L for lightning arrestors expulsion type with all fittings, transmission class, discharge capacity 65 Kilo amp including taking down old one complete all as specified and as directed by Engr-in-charge. |
| 34 | S&F in reapir fabricated, fixing structural mild steel RS joint, channel angle iron and brackets etc for fabrication of cross arms, bracing supports clamps including D clamps, eye hook and back plate etc fabricated from structual steel section including nuts, bolts, washers, welding (cols and hot) drilling holes for bolts, bend to any shape of size as indicated and directed, inclusive of one primer coat and two coats of aluminium apint after preparation of surfaces complete all as specified and directed. (Note :- Taking down of old unsv item will be measured saparetely) |
| 35 | Taking up old U/S GI pipe any size complete all as specified and as directed by Engr -In - Charge. |
| 36 | Boring/Drilling (horizontally) manually under min 0.5 to 2 m deep in soil below existing road suitable for passing GI tubing of 80 to 100 mm bore complete all as specified. |
| 37 | Supply and laying in replacement GI pipe 100 mm dia light grade for UG cable protection and for supporting of cable to pole complete all as specified and as directed by Engr-in - charge. |
| 38 | S & F UG cable route indicator made out of 100 mm dia MS Plate with 20mm dia 60 cm long MS bar as legs for writing HT cable fixing with and including necessary PCC 1:2:4 in grounding route complete all as specified and directed. |
| 39 | Anti climbing devices; comprising 2.24mm dia galvanised steel 2-strand barbed wire with 2.00mm dia barbs wrapped spirally round poles, to a length of 0.5 to 1.0 metre clamped and properly secured or as ordered (clamps measured separately) complete all as specified and directed. |
| 40 | M&L earthing complete with galvanised steel earth plate electrode of size 600 x 600 x 6 mm thick buried directly in ground in vertical position (earth pit not less than 2.25 m deep below the normal ground level) with top edge of the earth plate not less than 1.5 m below normal ground level, connected to galvanised earth lead of GI strip 32x6 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel, all as shown in electrical plate No. 3 connected to earthing test point and including dismantling complete all as specified and directed.Note:- The unit rate shall also include for earth work in any type of soil, PCC 1:3:6 type C1 chamber, RCC 1:1.5:3, type A1 cover slab, 450 x 450x 50 mm thick reinforced with 8 mm dia TMT bar @ 140 mm C/C both ways, 10 mm dia plain bar lifting handle embedded in cover slab, 20 mm bore medium grade GI watering pipe, 40 mm bore GI medium grade earth lead protection pipe, funnel, wire mesh, copper lugs, charcoal and common salt in alternate layer etc. |
| 41 | M&L earthing complete with copper plate electrode of size 600 x 600 x 3.15 mm thick buried directly in ground in vertical position (earth pit not less than 2.25 m deep below the normal ground level) with top edge of the earth plate not less than 1.5 m below normal ground level, connected to copper earth lead of GI strip 20x3 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel, all as shown in electrical plate No. 3 connected to earthing test point and including dismantling complete all as specified and directed.Note:- The unit rate shall also include for earth work in any type of soil, PCC 1:3:6 type C1 chamber, RCC 1:1.5:3, type A1 cover slab, 450 x 450x 50 mm thick reinforced with 8 mm dia TMT bar @ 140 mm C/C both ways, 10 mm dia plain bar lifting handle embedded in cover slab, 20 mm bore medium grade GI watering pipe, 40 mm bore GI medium grade earth lead protection pipe, funnel, wire mesh, copper lugs, charcoal and common salt in alternate layer etc. |
| 42 | Earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 meter deep below ground level) with top edge of plate not less than 1.5 meter below normal ground level, connected to galvanized iron earth lead wire of 4 sqmm by means of bolts, nuts, check nuts and washers of galvanized iron or steel, all as shown in Electrical Plate No 3 of SSR Part - I, including necessary excavation and earth work, P.C.C (1:3:6) type C-I with 50 mm thick Pre-cast R.C.C. (1:2:4) type B-I cover slab (reinforced with 8 mm dia deformed bar @ 15 cm C/C both ways and suitable handle of 10 mm dia round bar), including providing charcoal or coke and common salt in alternate layers of 15 cm compacted thickness all around the earth electrode, with funnel and 20 mm bore galvanized iron watering pipe (light grade), wire mesh, aluminium lugs, complete in all respect, GI earth wire protected by 15 mm bore (medium grade) galvanized iron pipe and other end connected with main switch board or Earthing test point as directed, including necessary earth work and disposal of spoil to a distance not exceeding 50 metre and necessary testing on completion including dismentaling old unsv ones complete all as specified and as directed by the Engineer-in-Charge. |
| 43 | M&L preparation of 2 Pole structure 9/11 mtr pole with connected cross arms, cable protection pipes, clamps etc, and including applying one coat of aluminium paint on complete height of the pole and including applying one coat of synthetic enamel paint upto 0.80 m height from the top of coping with multi colour strips,weather proof painting of coping as per existing colour code complete all as specified and directed. |
| 44 | Supply and fixing in replacement of old vintage Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25x20cm size complete all as specified and directed. |
| 45 | M&L preparation of 4 Pole structure 9/11 mtr pole with connected cross arms, cable protection pipes, clamps etc, and including applying one coat of aluminium paint on complete height of the pole and including applying one coat of synthetic enamel paint upto 0.80 m height from the top of coping with multi colour strips,weather proof painting of coping as per existing colour code complete all as specified and directed. |
| 46 | Cutting / trimming of tree branches in close promixity to 2/4 pole structure and transformer to maintain a clearance of 1.5 meter from the 2/4 pole structure and transformer to nearby trees, complete all as specified and as directed. |
| 47 | Note 1:- (Applicable for all parts/items) : The bidders/contractors are advised to read tender document, all drawings & all corrigendum / amendments and general condition of contracts before entry / quoting the rates.Note 2:-The contract sum shall be arrived at after deducting amount of schedule of credit from the total quoted amount. Please Enable Macros to View BoQ information |