| 1 | CONSTRUCTION OF 50,000 LTR Capacity OGR |
| 2 | Designing , construction, testing and commissioning of 50,000 ltr capacity circular shape flat bottom with domb shape RCC on the ground reservoir including supplying , fitting, fixing of M.S and aluminuim ladder , Water level indicator, lightening arrester 1 nos. 80 mm CI puddle collar-4, CI MH cover-2 nos., Inlet & Outlet arrangement with 80 mm dia GI pipe - 18 mtr and soil testing & drawing design etc. testing of the joints all complete fitting and fixing of 80 mm double flanged CI sluice valves-2 No , Sluice valve chamber -2 nos of standard make providing CC M-25 for RCC work with 20mm & down grade size hg chips with 20mm thick cement plater over the cement concrete work, cement punning over plaster surface and painting 2 coats of water proofing weather coat etc. all complete as per approved drawing and design as per direction of Engineer-in-Charge. |
| 3 | LAYING OF RISINGMAIN |
| 4 | Earth work in excavation of trenches for laying of pipe line including dressing, leveling the bed upto required depth & within initial lead of 50mtrs & 1.5mtrs initial lift breaking clods to maximum size (5 to 7cm) laying in layers not exceeding 0.30mtrs in depth etc. complete including cost of all labour, T&P, pipes, fittings and specials etc.required for completion of the item as per specification & direction of Engineer in charge. |
| 5 | In all kind of Soil : (2500 mtr x 0.38mtr x 0.90mtr) |
| 6 | Supplying all materials including HDPE pipes, fittings and specials, labour, T&P for laying in trenches unplasticised HDPE pipes of the following outside diameter for all classes and specials as required at site, including jointing with solvent cement by non heat application method excluding the cost of earth work in excavation but including the cost of pipes cost of fitting and specials & testing the pipe line etc. all complete as per direction of Engineer-in-charge. |
| 7 | 90 mm HDPE Pipe PE-80 PN-6 |
| 8 | Supplying all labour, T&P for filling excavated earth in the pipe line trenches by laying in layers not exceding 9\\" (225mm) including watering and ramming as per the direction Engineer-in-charge. |
| 9 | In all kind of Soil : |
| 10 | Supplying all labour T&P fitting and fixing of CI sluice valves with double flanged ends in the water line for controlling purposes conforming to IS:14846-2000 for the following rating and nominal diameters as per specifications complete of approved make with supply of all joining materials, T&P etc all complete including testing as per specicication complete |
| 11 | 80 mm dia CI Sluice Valve IS- 14846/2000 PN-1.00 |
| 12 | 15 mm dia CISingle Air Valve IS 14845/2000 |
| 13 | Supplying all labour, material, T&P and constructing brick masonry valve chambers of following mentioned inetrnal dimension, complete with C.C (1:4:8) with 40 mm size hbg metal at the bottom, C.B brick masonry in c.m(1:4) with internal plastering and R.C.C top cover with C.C(1:2:4) with 12mm size hbg metal & MS Rod 0.85qntl per 1 cum and with 12mm thick cement plaster (1:4) complete in all respect as per the direction of the Engineer-in-charge. |
| 14 | SluiceValve/NR Valve Chamber (Size 0.90mtr x 0.90 mtr x 1.15 mtr) |
| 15 | Air Valve Chamber(Size 0.75mtr x 0.75mtr x 1.15mtr) |
| 16 | Transporting and supplying all materials, labour T&P, fabricating, fitting and fixing with specials at the site using Electric resistance welded pipes of reputed make (TATA / Zindal ), confirming to IS 1239 (P-1) 2004, IS 1978 & IS 3598, medium quality & standard weight, including cutting the pipes & flanges, drilling the bolt holes in the flanges, matching the pipes and flanges and jointing with proper gradient & alignment, welding with arc welding using electrodes with power generated by using mobile diesel generator set, etc. complete as per direction of Engineer in charge, including painting two coats with black anti-corrosive paint over one coat of primer, all cost, conveyance, taxes of paints, cost of fittings as 'T', Bend, Offsets, Nuts and bolts, Leather packing etc. but excluding the cost of flanges and required earthwork, cutting holes in masonry works etc. |
| 17 | 80 mm dia G.I pipe |
| 18 | M.S /GI Framed Hoarding (2 Nos) |
| 19 | Supplying all labour, T&P and materials and providing & fixing of IEC hoarding board of size 1.22m(4')x 0.91m (3')in wall/post. The Hoarding frame made by 25mmx25mmx3mm thick hollow square GI bar supporting with 25mmx25mmx4mm size GI angle in middle 1 nos. covered with 1.6mm thick GI Sheet fixing of the IEC message over the board( Flex Banner of 6'x4' size) as per design & specification including 2 nos of 50x50x6 mm support pillar & cost, carriage, royality & taxes of all materials & labour etc, all complete as per specification and direction of the Engineer-in-charge. Please Enable Macros to View BoQ information |