| 1 | Supplying and installation of Bus bar chamber of the following ratings and sizes made of steel sheet enclosure with all accessories including necessary connection etc. as required:- |
| 2 | 200 amps 415 volts four strip Copper busbar chamber 4 ways of size (455mmx330mmx120mm):- |
| 3 | 100 amps 415 volts four strip Copper busbar chamber 6 ways of size (610mmx410mmx120mm):- |
| 4 | 63 amps 415 volts four strip Copper busbar chamber 6 ways of size (455mmx330mmx120mm):- |
| 5 | Supplying and installation of Switch disconnector fuse unit (main switch) of the following ratings with all accessories including necessary connection etc. as required:- |
| 6 | 100 amps TPN 415 volts front handle cubical main switch (HRC):- |
| 7 | 63 amps TPN 415 volts front handle cubical main switch (HRC):- |
| 8 | 32 amps 240 volts DP main switch (rewireable):- |
| 9 | 63 amps 240 volts DP main switch (rewireable):- |
| 10 | Supplying and installation of change over switch of following ratings with enclosure including necessary connection etc. as required:- |
| 11 | 200 amps FP on load change over switch (Front handle with enclosure):- |
| 12 | 63 amps FP on load change over switch (Front handle with enclosure):- |
| 13 | Supplying and installation of fuse unit kitkat/HRC/HBC of the following ratings in existing main switch/panel board including necessary connection etc as required:- |
| 14 | 200/250 amps kitkat porcelain fuse unit with base(rewireable):- |
| 15 | Supplying and installation of powder coated steel sheet enclosure (MCB DB) suitable for 240/415 volts MCB/Isolator/RCCB (SP/SPN/DP/TP/TPN/FP) complete with necessary bus bar, neutral link, din rail, earth bar etc i/c connection as required. |
| 16 | (2+6) / 8 way SPN MCB DB (single door):- |
| 17 | Supplying & installation of 10 KA breaking capacity, B/C curve MCB of following ratings in the existing MCB DB including connection as required:- |
| 18 | 6 to 32 amps SP MCB:- |
| 19 | Wiring for Circuit/Sub-main with the following sizes of PVC insulated Copper conductor cable (FR) in existing PVC casing capping/ conduit in recess/surface including connection etc. as required:- |
| 20 | 4 X 50 sq mm |
| 21 | 1 X 16 sq mm |
| 22 | 4 X 35 sq mm |
| 23 | 1 X 10 sq mm |
| 24 | 4 X 25 sq mm |
| 25 | 1 X 6 sq mm |
| 26 | Providing earthing system with maintenance free earthing electrode of 50 mm dia & 3 mtr long of dual electrode technology filled with highly conductive compound and back fill compound of 2 nos. 25 kg bag, terminal size 32mmx 6mm including accessories with masonry enclosure of CI cover plate size 12\\"x 12\\" having locking arrangement including CC works etc as required:- |
| 27 | Supply and fixing of 25mm x 5mm GI strip on wall/ floor of the building for horizontal/ vertical run including necessary spacers and porcelain insulators at regular intervals. |
| 28 | Proving and fixing / drawing of 4.06 mm dia (8 SWG) G.I. wire on surface or in existing G.I/ PVC/ Polythene pipe for loop earthing as required. |
| 29 | Supplying and fixing of the following PVC casing capping with all accessories etc. as required. |
| 30 | 32mm x 12mm |
| 31 | Supplying and fixing of Copper terminal ends (LUGS) - long barrel of following sizes: - |
| 32 | 2.5 sq mm |
| 33 | 4 sq mm |
| 34 | 6 sq mm |
| 35 | 10 sq mm |
| 36 | 16 sq mm |
| 37 | 25 sq mm |
| 38 | 35 sq mm |
| 39 | 50 sq mm |
| 40 | Supplying and fixing of MS frame made of (25mm x 25mm x 5mm) MS angle with necessary support by (40mm x 6mm) MS flat and 12 mm thick marine plywood on top, grouted on wall with 4 nos legs (25mmx25mmx5mm MS angle 20 cm long) finished with red oxide and 2 coat synthetic enamel paint including necessary cc work, mending the damages & painting etc as required:- Please Enable Macros to View BoQ information |