| 1 | Cat (A) -Items to be supply and fixing |
| 2 | Taking down / dismantling of existing aluminium point wiring, main switches, cut-out carefully inside the DB and making good to disturbed surface of walls with proper filling & suitable colour wash as and where required etc. All as per the direction of In-charge. |
| 3 | S & Fixing or drawing of sub-main cables of size 4.0 sq. mm. two single core of multi-coloured (2X4.0 sq. mm) PVC insulated ISI marked stranded copper conductor cables with continuous run of 1X2.5sq.mm. green colour pvc insulated copper Conductor cable as a Earth wire (Make: finolex/Havells/RR) cables as per IS-694-1990 drawing in existing PVC conduit pipe on the wall with all accessories as per the site requirement, of any length with proper lug at termination end of cable. All as per the direction of In-charge. (old/damaged sub-main cable to be removed and deposit in store section for credit). |
| 4 | S & Fixing and drawing of circuit with cables of size 2.5 sq. mm. two single core of multi-coloured (2X2.5 sq. mm) PVC insulated ISI marked stranded copper conductor cables with continuous run of 1X1.5sq.mm. green colour pvc insulated copper Conductor cable as a Earth wire (Make: finolex/Havells/RR) cables as per IS-694-1990 drawing in PVC casing & capping (ISI mark)on the wall including cutting of walls for passing of circuit wire with all civil works for proper finishing of wall with all accessories as per the site requirement, of any length with proper lug at termination end of cable. All as per the direction of In-charge.(old/damaged sub-main cable to be removed and deposit in store section for credit). |
| 5 | S & F, One light point, to be controlled with wiring of-(a) 1.5 sq. mm. colour coding Single core PVC insulated ISI marked Stranded copper Conductor cables as per IS-694-1990 (make: - Havells/Finolex/RR).(b)PVC piping /PVC casing & capping with ISI mark, 1.8 mm. to 2.2 mm. thick 19/25mm. size PVC pipe or casing & capping of 25/32mm. width of size (make: cello/press fit/modi/finolex/super plast) & all accessories with joints, covers etc.,(c)Continuous 1 sq.mm. Green colour pvc insulated suitable copper earth wire through inside the PVC pipe/pvc cassing & capping.(d)wiring to be terminated on a pvc rectangular board for fixing switches on wall with back side closed type with all civil related works like plastering, colour washing etc. All work as per the direction of In-charge . |
| 6 | Supply and fixing piano Switch flush type 5 Amp. Single pole one way (white) as per IS- 3854/1997 to be fixed on switch board as per site requirement. Make: Anchor/cona. All as per the direction of In-charge. |
| 7 | Supply and fixing Switch socket combination 2 in 1, 3 pin, 5 and 15 Amp flush type universal on a separate hyleem sheet wooden board or as per site-requirement. Make: anchor/cona. All as per of In charge. |
| 8 | S & F, lamp holder, insulated body, suitable for 230 volt, 6 amp. Capacity with ISI mark threaded dome pattern, suitable for bracket fitting on a wooden board as per site requirement. Make: Anchor/cona. All as per the direction of In-charge. |
| 9 | Supply and fixing LED tube light 1x 20 W, 120-300v ,50 hz with holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size with ceiling rose. LED tube light should be T8, 4 feet with minimum 1800 lumens, 6500K colour temperature, to be fit on a good standard aluminium tube light patti, side holder of tube light patti should be metal type with holder for fixing tube light. Fitting to be fixed on wall with clamp or suitable fixing accessories as per site requirement. Tube light to be covered two year standard warranty against defect from date of installation. Make of tube light: Philips/wipro/osram/Bajaj. All as per direction of In-charge. |
| 10 | Supply and fixing of sheet metal MCB DB of triple pole and neutral of 4 way, 415 volt,50hz double door type with following a. SPN MCB of 32Amp. 415V 10KA 'B' curve miniature circuit breaker (MCB)-5 no. b. SP MCB Supply and fixing 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of single poles and current carrying capacity 5 to 32 AMP, in the MCB DB-04 NO. as per site requirement Make: legrand/havells/L&T on wall. All as per direction of In-charge. |
| 11 | Supply and fixing 415V 10KA ‘B' curve miniature circuit breaker (MCB) of 63Amp. capacity of TPN/FP-1 no. as per site requirement to be fixed in the sheet metal enclosure DB of 4 way -1 no. with double door type with connection testing and commissioning. Make: legrand/havells/L&T. Item to be fixed inside the metering DB with all fixing accessories. All as per direction of In-charge. |
| 12 | S & F of GI steel tubes of medium grade of 40 mm bore on wall for cable passing from roof entrance of building to meter DB. During fixing of pipe on wall proper fixing arrangement to be done as per site requirement with all accessories. All as per the direction of In-charge. |
| 13 | Supply and fixing of clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint as per site requirement .All as per direction In-charge. |
| 14 | Cutting of holes into cement concrete slabs of reinforcement throughout exceeding 100sq.cm. area with not exceeding 250sq.cm ,10cm. depth for crossing of sub-main conduit pipe and refilling of gap with bonding of cement mortar 1:4 with suitable colour wash as and where required or as per site requirement. All as per direction of In-charge. |
| 15 | Cutting of hole inside the brick wall of size 09\\" length into or through brick walls of built in mud mortar with area not exceeding 150sq.cm. and making good in cement mortar 1:3 or cement concrete 1:2:4 type B-l as required. All as per direction of In charge. |
| 16 | S & F Shackle Type, Porcelain, vitreous, white, brown or green insulator including galvanised mild steel straps, washers, insulator bolts, washers and nuts, as under: shackle insulator with following size and parameters. A. Working on 550 volt B. height of 50mm. C. Dia. of 65mm. D. Section of straps 25x1.59mm. E. Dia. of bolts 9mm. Insulator to be fixed on L.T. pole and roof of building for supporting of cable at both ends with suitable arrangement with all civil works as per site requirement. All as per direction of In-charge. |
| 17 | Supplying and fixing 1100 volts grade heavy duty cable PVC insulated stranded aluminium conductor of 10 sq.mm. size, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hanger’s notmore than 1 metre apart including 4mm suspension wire, with two twin core flat cables to be fixed from pole to dB partially passing through GI pipe or as per site requirement with all fixing Accessories. Cable make: RR/ORBIT/Equivalent. All as per direction of In-charge. (Firm to submit relevant documents of cable as per requirement of OFCH). |
| 18 | S & Fixing of Single pole MCB of 6 to 32 amp. rating of 240 volt, 50Hz with ISI mark as per IS/IEC 60898-1 in existing MCB DB as per site requirement with all fixing accessories. Make: legrand/siemens/L&T. All as per the direction of In-Charge. |
| 19 | S & Fixing of Double pole MCB of 32 amp. rating of 240 volt, 50Hz with ISI mark as per IS/IEC 60898-1 in existing MCB DB as per site requirement with all fixing accessories. Make: legrand /siemens/L&T. All as per the direction of In-Charge. |
| 20 | Cat (B) - Buy Back Items |
| 21 | Credit to contractor for old/ damaged pvc insulated aluminium conductor cable. All as per direction of In-charge. |
| 22 | Credit to contractor for defective main switches. All as per direction of In-charge. |
| 23 | Credit to contractor for defective switches & cut-outs. All as per direction of In-charge. Please Enable Macros to View BoQ information |