Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | (33kV HT PANELS)Supply, Installaton, Testing & Commissioning of 33 KV ,Indoor type 6 panel board Vacuum circuit breaker (With 1 No. Incomer 1250 Amps, 2 No. Outgoing 1250 Amp, 2 No. Tie Feeder 1250 Amp & 1 No. Bus Coupler 1250 Amp), 3 phase, 31.5 KA for 1 sec. , HT switch gear with all necessary protection, metering and other accessories as required. Analysis of Rate YEIDASOR- 73 |
| 2 | Supply , Installaton, Testing & Commissioning of 33KV , Indoor type 2 panel board Bus PT, 3 phase, 31.5 KA for 1 sec with all necessary protection, metering and other accessories as required. Analysis of Rate YEIDASOR- 71 |
| 3 | Supply, Installation, testing & commissioning of out door type 10 MVA Power Transformer with on load tap changer as per ISI specification including loading, unloading, local carriage & erection of the same on plinth & making all necessary connection etc. Complete in all respects as per specification (Make ABB/ Crompton/ Schinider). Cable termination box with disconnecting facility for 33 KV XLPE cable at 33 KV side. Cable termination box with disconnecting facility for 11 KV XLPE cable at 11 KV side.On load tap changer+/- [email protected]%, Bi directional roller, Conservator with drain valve, Earthing ferminals, Double diaphragm explosion vent, Radiator with top & bottom shut off valve, First filling of oil including make up fill, Silica gel breather with oil seal, Rating and diagram plate, Air Release plug,Buchholz relay with shut off valve,Winding temperature indicator (WTI), Oil temperature indicator (OTI), Megenatic oil level guage, Pressure relief device, Marshalling box. No load losses-7Kw, load losses 50KW, Toleronce as per I.S. code Analysis of Rate YEIDASOR- 75 |
| 4 | Supply Installaton Testing & Commissioning of 11 kV, Indoor type 12 panel board Vacuum circuit breaker (2 No. Incomer 1250 Amps, 1 No. bus coupler 1250 Amps and 9 Nos.630Amp Outgoing) 11 KV, 3 phase, 25 KA for 1 sec. HT switch gear VCB breaker with all necessary protection, metering and other accessories as required. Analysis of Rate YEIDASOR-72 |
| 5 | Supply, Installaton, Testing & Commissioning of 11KV Indoor type 2panel board Bus PT, 3 phase, 25 KA for 1 sec with all necessary protection, metering and other accessories as required. Analysis of Rate YEIDASOR- 70 |
| 6 | Supplying, assembling, installation, commissioning of Sealed maintenance free (SMF) 110V D.C., 200 AH batteries. The batteries shall rest on treated wooden planks fabricated from MS angle and free standing floor mounted rack with acid resistant finish and complete with series connecting electrical leads and charging of batteries. The batteries shall be accompanied with tester. This shall have incoming leads as well as outgoing leads and of suitable battery charger for 8 hrs charge of 200AH battery charger enclosed in sheet metal with fan on top and it should automatically charge the batteries With booster and trickle charge. Charger shall be complete with incoming & outgoing leads and D.C. Distribution board will have one set of 63 amps MCB as incomer and 10 Nos. of suitable rated MCB (as per coil rating of VCB) on outgoing side enclosed in metal sheet enclosure of 2mm thick CRCA sheet steel dully painted anti-corresion paint. The unit will be complete with bus bars, accessories, links, terminal strip, clamps etc along with cables up to incoming & outgoing to VCB panels.Analysis of Rate YEIDASOR- 69 |
| 7 | Supply, delivery, laying, testing & commissioning of 33KV (E), XLPE cable having compacted circular staranded aluminium conductor, conductor screening of extruded semi conducting compound, cross linked polythylane (XLPE), insulation screening of the extruded semin conducting compound followed by copper tape, cores laid up, taped PVC inner sheath, single layer of steel strip armouring, overall PVC outer sheath conforming to IS: 7098 (Part-amendments) for following mentioned sizes. It should be operational at 33 KV, 50 Hz. AC system in ground at a depth of 1200 mm below ground level over a cushion of 75 mm thick sand alround and protected with bricks on sides and top on surface the cable run shall be fixed on M.S. clamps etc of suitable size or as directed by the E/I. Complete in all respect. The price are inclusive of all earth work such as digging, back filling, supply & spreading of good earth all around the cable, supply & providing cable identification markers. The installation should be complete in all respects and as per requirement of the job. (CCI , Fort Gloster, Asian , Universal, Nicco , ICL , Diamond, Havells, KEI make. Analysis of Rate 33kV, 3C X 400 sq. mm. (from 33kV HT Panel to 33/11kV Power transformer). Analysis of Rate YEIDASOR- 03 |
| 8 | Supply, delivery, laying, testing & commissioning of 11KV (E), XLPE cable having compacted circular staranded aluminium conductor, conductor screening of extruded semi conducting compound, cross linked polythylane (XLPE), insulation screening of the extruded semin conducting compound followed by copper tape, cores laid up, taped PVC inner sheath, single layer of steel strip armouring, overall PVC outer sheath conforming to IS: 7098 (Part-amendments) for following mentioned sizes. It should be operational at 33 KV, 50 Hz. AC system in ground at a depth of 1200 mm below ground level over a cushion of 75 mm thick sand alround and protected with bricks on sides and top on surface the cable run shall be fixed on M.S. clamps etc of suitable size or as directed by the E/I. Complete in all respect. The price are inclusive of all earth work such as digging, back filling, supply & spreading of good earth all around the cable, supply & providing cable identification markers. The installation should be complete in all respects and as per requirement of the job. (CCI , Fort Gloster, Asian , Universal, Nicco , ICL , Diamond, Havells, KEI make. Analysis of Rate 11kV, 3C X 300 sq. mm. (From 33/11 Power Transformer to 11 KV HT Panles). Analysis of Rate YEIDASOR- 02 |
| 9 | Supply, Delivery, Installation, Testing & Commissioning of 33KV, Indoor type cable termination kit complete in all respects as required for proper completion of work. (make Raychem, CCI, Frontec) 33kV, 3C X 400 sq. mm., XLPE insulated, Aluminum conductor E grade, strip armoured cable. Analysis of Rate YEIDASOR- 09 |
| 10 | Supply, Delivery, Installation, Testing & Commissioning of 33KV, Indoor type cable termination kit complete in all respects as required for proper completion of work. (make Raychem, CCI, Frontec) 11kV, 3C X 300 sq. mm. ,XLPE insulated, Aluminum conductor E grade, strip armoured cable. Analysis of Rate YEIDASOR- 04 |
| 11 | Supply, Delivery, Installation, Testing & Commissioning of 33KV, Outdoor type cable termination kit complete in all respects as required for proper completion of work. (make Raychem, CCI, Frontec) 33kV, 3C X 400 sq. mm. XLPE insulated, Aluminum conductor E grade, strip armoured cable from 33kV HT Panel to 33/11kV Power transformer. Analysis of Rate YEIDASOR- 09 |
| 12 | Supply, Delivery, Installation, Testing & Commissioning of 11KV, Outdoor type cable termination kit complete in all respects as required for proper completion of work. (make Raychem, CCI, Frontec) 11kV, 3C X 300 sq. mm. XLPE insulated, Aluminum conductor E grade, strip armoured cable. Analysis of Rate YEIDASOR- 05 |
| 13 | Control cable Supply, Installation, testing and commissioning of Control cables of following sizes to be laid buried in ground or laid on cable trays for transformers and VCB. 1.1kV Grade Stranded Copper Conductor, PVC Insulated Wrapped PVC Inner & Outer Sheathed Cable. Analysis of Rate CABLE 4CX2.5SQMM YEIDASOR- 01 |
| 14 | Control cableSupply, Installation, testing and commissioning of Control cables of following sizes to be laid buried in ground or laid on cable trays for transformers and VCB. 1.1kV Grade Stranded Copper Conductor, PVC Insulated Wrapped PVC Inner & Outer Sheathed Cable. Analysis of Rate CABLE 19CX1.5SQMM YEIDASOR- 01 |
| 15 | Supply, Installation, testing and commissioning of Cable end terminations/Glands/lugs for 1.1kV grade stranded copper conductor, pvc insulated wrapped pvc inner & outer sheathed cable for transformers and VCB. Analysis of Rate CABLE 4CX2.5SQMM |
| 16 | Supply, Installation, testing and commissioning of Cable end terminations/Glands/lugs for 1.1kV grade stranded copper conductor, pvc insulated wrapped pvc inner & outer sheathed cable for transformers and VCB. Analysis of Rate CABLE 19CX1.5SQMM |
| 17 | Supplying and fixing of S&F of 36 Nos, 6 Amp to 32 Amp. MCB (10 KA) C Curve,TPN MCB distribution board of steel sheet for 415 volts on surface/ recess complete with loose wire box, terminal connectors for all incoming and outgoing circuits, duly prewired with suitable size FR PVC insulated copper conductor up to terminal blocks, tinned copper bus bar, neutral link, earth bar, din bar, detachable gland plate, interconnections, powder painted including earthing etc of DB's (For Lighting & Small Power ). Note- Each incoming and outgoing MCB's shall have Ics = 10 kA minimum. S & F surface/ Flush mounting 12ways TPN distribution board with additional metal door without MCB complete in all respect,as directed at site by Engineer in charge. PWD PS No-1002 |
| 18 | Supply and fixing of power plug with 15A/250 volt flush type switch and 5 pin 15A/250V flush type universal socket in suitable M.S. box of 175mm x 100mm x 50mm size with phenolic laminated bakelite sheet cover 3mm thick fixed with brass machine screw and cup washer. & Add for plug point with modular switch & socket in place of piano type switch & socket. (UPS socket for computer). PWD PS No-1139 & 187C |
| 19 | S&F of 63 Amp. 415 V metal clad T.P. rewireable type switch fuse unit on angle iron bracket complete in all respect. PWD PS No-313 |
| 20 | S&F of LED Tube Light with batten suitable for upto 1X22 Watt LED Tube Light fitting including tube on surface complete in all respect. PWD PS No-1413 |
| 21 | S/F of 40mm. dia 1.5mtr. long G.I. pipe ‘B’ Class bracket with 2 Nos. ‘D’ clamps 50X6mm. flat iron on steel tubular pole/ steel rail pole / PCC pole with bolts, nuts etc. complete in all respect Analysis of RatesYEIDASOR- 35 |
| 22 | S&F of LED Street Light Fitting Having die cast aluminium body and diffuser with driver set suitable for 140 to 150 Watt. Confirming to IP 66 Protection complete in all respect. PWD PS No-1425 |
| 23 | Supply, Installation, testing and commissioning of 1200mm dia sweep ceiling fan with standard down rod. Analysis of Rate YEIDASOR- 62 |
| 24 | Supply, Installation, testing and commissioning of Oscillating type wall fan 400mm dia. Analysis of Rate |
| 25 | Supply, Installation, testing and commissioning of 300mm dia heavy duty 900 RPM exhaust fan complete with louvered shutters. Analysis of Rate YEIDASOR- 63 |
| 26 | Wiring point for light with 1.5 sq. mm. FRLSH PVC insulated multistrand single core copper conductor cable in in PVC conduit with 1.5 sq. mm.FRLSH PVC insulated multistrand copper conductor cable as earthwire drawn inside. each partly concealed in the wall and partly laid in slab alongwith the reinforcement before concreting, complete with GP Box, Modular type switch & ceiling rose/angle/batten holder on 3mm thick phenolic paminated backalite sheet etc complete in all respect as directed including matching colour wash. PWD PS No-138( C) +187(A) 2018 |
| 27 | Wiring point for fan / fresh air fan (light duty exhaust fan) with 1.5 sq.mm.FRLSH PVC insulated multistrand single core copper conductor cable in PVC conduit with 1.5 sq. mm.FRLSH PVC insulated multistrand copper conductor cable as earthwire drawn inside the conduit. partly concealed in wall and partly laid in slab alongwith the reinforcement before concreting, complete GP Box ,Modular type switch & ceiling rose on 3 mm. thick backelite sheet etc., complete in all respect including matching colour wash. PWD-140(C) +187(A) 2018 |
| 28 | Supply and fixing of power plug with 15A/250 volt Modular type switch and 5 pin 15A/250V flush type universal socket in suitable M.S. box of 175mm x 100mm x 50mm size with phenolic laminated bakelite sheet cover 3mm thick fixed with brass machine screw and cup washer PWD PS No-1139+187(C) |
| 29 | Supply and wiring of submains with 2 nos. 2.5 sq mm & with 1 no earth wire of 1.5 sq mm FRLSH PVC insulated 1100 V grade single core multistrand copper conductor cable in existing PVC conduit complete, including supply of all material, labour and T & P etc. & Supply and laying of 20 mm dia heavey duty (2mm Thick) PVC conduit of 25mm dia.complete with bends and other acessories as required in slab alongwith reinforcement, before concreting and plastering etc, required for proper completion of the work as directed by Engineer in charge.For computer terminals from UPS DBs, PWD PS No-291&282(A ) |
| 30 | Supply and wiring of submain with two number 4 sq.mm. FRLSH PVC insulated 1100 V grade multistrand single core copper conductor cable in 20 mm dia heavy duty (2 mm thick) PVC conduit with one no. 2.5 sq. mm. FRLSH PVC insulated multistrand copper conductor cable as earth continuity wire drawn in conduit, including matching colour wash etc. ,complete in all respect.For 16A sockets, PWD PS No-221(C) |
| 31 | Supply and wiring of submain with two number 6 sq. mm. FRLSH PVC insulated 1100 V grade multistrand single core aluminium conductor cable but in 25 mm dia heavy duty (2 mm thick) PVC conduit with one number 4 sq. mm. FRLSH PVC insulated multistrand copper conductor cable as earth continuity wire drawn in conduit etc. complete in all respect.For 20A AC sockets, PWD PS No-222(C ) |
| 32 | Supply and wiring of 4 number 16 sq. mm. PVC insulated 1100 V grade single core Copper conductor cable in 40 mm dia PVC conduit partly concealed in wall and partly laid in slab alongwith reinforcement before concreting, with two number 10 sq mm single core Copper conductor cable as earth continuity wiredrawn in coudit including matching colour wash etc, complete in all respect For 63A sockets. PWD PS No-279(C ) |
| 33 | Supply & Burying of 600mm X 600mm X 6.00mm G.I. plate verticalley for Earthing with its top at least 3.00 mtr below ground level complete with 20mm Dia. G.I. pipe & Funnel for watering and one earthing lead of one no. 8 to 10 SWG G.I. wire in 15mm dia. GI pipe upto Switch Board (From approan to switch board the cost of GI pipe & GI wire will be extra) 30cm square C.I. frame with hinged cover masonory housing alternate layers of charcole/ coke and salt at least 150mm thick alround etc. as per direction of Engineer-in-charge complete in all respects. as per drawing (this will apply for earthing of poles also). PWD PS No-702 |
| 34 | Supply & Burying of 600mm X 600mm X 3.00mm Cu. plate verticalley for Earthing with its top at least 3.00 mtr below ground level complete with 20mm Dia. G.I. pipe & Funnel for watering and one earthing lead of one no. 8 to 10 SWG Cu. wire in 15mm dia. GI pipe upto Switch Board (From approan to switch board the cost of GI pipe & Copper. wire will be extra) 30cm square C.I. frame with hinged cover masonory housing alternate layers of charcole/ coke and salt at least 150mm thick alround etc. as per direction of Engineer-in-charge complete in all respects. PWD-704 (2018) |
| 35 | Supply & Burying of 40mm dia. X 4.5 mtr long G.I. pipe verticalley for Earthing haveing 12mm dia. Holes spaced 75mm apart drilled upto 2mtr from the bottom complete with earthing lead of No.6 to 8 SWG G.I. wire in G.I. pipe upto appron (and from appron to switch board the cost of G.I. wire & pipe will be Extra) upto Switch Board, 30cm squre C.I. Box hinged cover masonory inclosure , funnel at top, alternet layers of charcole/ coke and salt at least 150mm thick alround etc. as per direction of Engineer-in-charge complete in all respects. as per drawing. PWD PS No-701 |
| 36 | (ELCTRONIC EARTHING FOR INSTRUMENTATION SYSTEM)Supply & Burying of 600mm X 600mm X 6.00mm G.I. plate verticalley for Earthing with its top at least 3.00 mtr below ground level complete with 20mm Dia. G.I. pipe & Funnel for watering and one earthing lead of one no. 8 to 10 SWG G.I. wire in 15mm dia. GI pipe upto Switch Board (From approan to switch board the cost of GI pipe & GI wire will be extra) 30cm square C.I. frame with hinged cover masonory housing alternate layers of charcole/ coke and salt at least 150mm thick alround etc. as per direction of Engineer-in-charge complete in all respects. as per drawing (this will apply for earthing of poles also). PWD PS No-702 |
| 37 | S&L of 32 x 6 mm GI strip, complete in all respects as per approved by Engineer-in-charge, PWD PS No-717 |
| 38 | S&L of 32 x 6 mm Copper strip,complete in all respects as per approved by Engineer-in-charge, PWD PS No-718 |
| 39 | S&F of 25 x 3 mm GI strip with G.I clamps on surface complete in all respects as per approved by Engineer-in-charge.,PWD PS No-710 |
| 40 | S&F of 25 x 3 mm Copper Strip with G.I. Clamps on surface complete in all respects as per approved by Engineer-in-charge., PWD PS No-711 |
| 41 | Supply and Installation of Perforated type trays– Prefabricated 2.5mm G.I.(Hot Dip Galvanised), 75mm flange height with all accessories such as coupling plates, bends, tees, reducers, coupling nut-bolts etc. of following width. The cost of installation shall include connection, bolting, cutting, etc.The supporting steel for cable trays shall be painted type and Cable trays, accessories and covers shall be painted with one shop coat of red oxide zinc chromate primer and two site coats of aluminium alkyd paint. Analysis of Rate YEIDASOR- 66 ,300 mm width |
| 42 | Supply and Installation of Perforated type trays– Prefabricated 2.5mm G.I.(Hot Dip Galvanised), 75mm flange height with all accessories such as coupling plates, bends, tees, reducers, coupling nut-bolts etc. of following width. The cost of installation shall include connection, bolting, cutting, etc.The supporting steel for cable trays shall be painted type and Cable trays, accessories and covers shall be painted with one shop coat of red oxide zinc chromate primer and two site coats of aluminium alkyd paint. Analysis of Rate YEIDASOR- 66 ,150 mm width |
| 43 | Supply and Installation of Perforated type trays– Prefabricated 2.5mm G.I.(Hot Dip Galvanised), 75mm flange height with all accessories such as coupling plates, bends, tees, reducers, coupling nut-bolts etc. of following width. The cost of installation shall include connection, bolting, cutting, etc.The supporting steel for cable trays shall be painted type and Cable trays, accessories and covers shall be painted with one shop coat of red oxide zinc chromate primer and two site coats of aluminium alkyd paint. Analysis of Rate YEIDASOR- 66 , 100 mm width |
| 44 | Supplying, fixing, testing & commissioning heavy duty PVC pipe with all necessary conduit accessories etc., 110mm dia conduit,PWD-2020, Civil-33(iii),Page No. 6 |
| 45 | S/L of 120mm dia. DWC pipe for drawing of power cable across the road by drilling of 150mm dia. at 1mtr. below the road level thereby doing the work of providing DWC pipe by Manual Trenchless method (Manual). Analysis of RateYEIDASOR- 13. |
| 46 | S/L of 200mm dia. H.D.P.E. pipe for drawing of power cable across the road by drilling of 220mm dia. at 1mtr. below the road level thereby doing the work of providing H.D.P.E. pipe PE-63/PN-8 by Manual Trenchless method (Manual). Analysis of Rate.YEIDASOR- 23 |
| 47 | ( LIGHTING PROTECTION )Supply and fixing of vertical Air termination final rod comprising of 300mm long x 25mm dia. G.I. Material with one pointed prong and 100mm dia x 3 mm thick base plate etc. complete in all respect. PWD PS No-712(B) |
| 48 | Supply and fixing of horizontal air termination (roof conductor) of 25mm x 3mm G.I. strip, G.I. clamps on surface complete in all respects as approved by Engineerin-charge. PWD PS No-710 |
| 49 | Supply and fixing of testing joint of G.I. strip 32mm x 6mm and 150mm long with G.I. bolts and nut etc. complete in all respect PWD PS No-719 |
| 50 | Supply and burying of 40mm dia x 4.5 metres long G.I. Pipe vertically for earthing having 12mm dia. Holes spaced 75mm apart drilled up to 2 metre from the bottom complete with earthing lead of No. 6 to 8SWG GI wire in G.I. Pipe up to appron (and from appron to switch board the cost of G.I. wire and pipe will be extra) upto switch board, 30cm square C.I. box with hinged cover masonary enclosure, funnel at top, alternate layers of charcoal/coke and salt at least 150mm thick alround etc. as per directions of Engineer-in-charge complete in all respects as per drawing.PWD PS No-701 |
| 51 | S/F of Identification plate of earthing pit with associated work.Complete in all respects as per direction of the Engineer-in-charge. YEIDA SOR-60 |
| 52 | SAFETY EQUIPMENTS Supply & Fixing of Danger Board Fabricated from 10 gauge M.S. Sheet. (33 kV Danger Caution Boards as per IS 2551 & IS 8923 ,PWD PS No-1109 |
| 53 | Supply and fixing of shock treatment chart (prescribed under I.E. rules) duly framed with glass and supported from back with hard board or soft board with supply of all material labour T&P for proper completion of work. PWD PS No-1134 |
| 54 | Supply and fixing of Carbon Di-oxide Fire Extinguishers of 4.5 Kg. each mounted on wall hooks as per IS 2878- PWD PS No-1132 |
| 55 | Supply and fixing of fire bucket,(6 Nos) round bottom made of G.I. sheet 9-11 litres capacity duly painted as per fire brigade design, supported on hanging bracket chained and locked, initially filled with fine river sand, water as per directions of Engineer-in-Charge. PWD PS No-1133 |
| 56 | 33 KV HV insulating mats confirming to IS 15652-2006. The mats should have been type tested by CPRI or another third party lab of equivalent stature. The mats shall be moisture proof, fire retardant and resistant to acids, alkalies & transformer oil. Analysis of RateYEIDASOR- 58 |
| 57 | S/E of Section Double pole structure on ST pole 410 SP-62 with 1/6 over length of poles grouted with cement concrete in 1:3:6 (one cement: 3coarse sand :6 Stone ballast) including plingthing of pole 30 cm above grade level, plastering of plinth including excavation & back filling etc.The double pole structure consist of 100X50X6mm 2.50 mtr.&75X40X6mm 2.50 mtr. M.S. channel and braings with M.S.clamppacking piece Nuts Bolts etc. The rates includes all materials labour T&Petc. required for proper completion f work as per direction of E/1. YEIDA SOR - 25 |
| 58 | S/F of 33 KV POLYMER pin insulator with pin on poles or any where specified including bolts to fasten on pole cap/cross arm with the poles. (Jaishree, BHEL,RR, Hindustan make) Analysis of rate |
| 59 | S/F of cross arm made of 100X50 X6 mm M.S. channel 2.5 mtr. long on poles with packing, piece, M.S. clamp, Nut bolts etc. complete in all respect. Analysis of rate YEIDA SOR -30 |
| 60 | Painting of the electric pole with two coat of Al-paint over red oxide primer complete in all respect. PWD PS No-634 |
| 61 | Supply & fixing of MS rod for earthing with 2.5 m long, solid, 20 mm dia hot dipped galvanised MS rod buried till the top reaches 1.7 mts. Below the GL complete with bolts & nuts & GI earth wire 7/14. Analysis of rate- YEIDA SOR -52 |
| 62 | S/F of G I pipe 150mm dia \\"B\\" Class Jindal/Tata make including required material T&P etc. Complete in all respects. Analysis of Rate YEIDA SOR - 65 |
| 63 | Supply, Installation, testing and commissioning of Out door type distribution transformer. Specification and also confirming to IS : 1180. Level-2 as per the directions of the Engineer-in-charge Analysis of Rates (a) 63 KVA Aluminium wound YEIDASOR- 34 |
| 64 | Supply, delivery, laying testing & commissioning of 11KV (E), XLPE cable having compacted circular staranded aluminium conductor, conductor screening of extruded semi conducting compound, cross linked polythylane (XLPE), insulation screening of the extruded semi conducting compound followed by copper tape, cores laid up, taped PVC inner sheath, single layer of steel strip armouring, overall PVC outer sheath conforming to IS: 7098 (Part-amendments) for following mentioned sizes. It should be operational at 11 KV, 50 Hz. AC system in ground at a depth of 1200 mm below ground level over a cushion of 75 mm thick sand alround and protected with bricks on sides and top on surface the cable run shall be fixed on M.S. clamps etc of suitable size or as directed by the E/I. Complete in all respect. The price are inclusive of all earth work such as digging, back filling, supply & spreading of good earth all around the cable, supply & providing cable identification markers. The installation should be complete in all respects and as per requirement of the job. (CCI, Gloster, Asian, Universal, Nicco , ICL,Havels,Dimond make) PWD PS No-506 (a) 3CX70 Sqmm. |
| 65 | Supply, Delivery, Installation, Testing & Commissioning of 11 KV Out door type cable termination kit of 3 core cable for cable termination at the panel & transformer complete in all respects as required for proper completion of work. (650mm length) (make Raychem/C.C.I./Frontec) Analysis of rate. (a).3CX50 Sq.mm.YEIDASOR- 05 |
| 66 | Supply & laying of aluminium conductor, XLPE insulated, armoured served, sheathed cable 1100 V grade at a depth of 750mm below ground level over a cushion of 75mm thick sand alround and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the E/I, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. [CCI (Mumbai/Nasik), Fort Gloster (Kolkata), Asian (Thane/Silvasa), Universal (Satna), Nicco (Kolkata/Baripara), ICL (Rajpura), Diamond, Havells make] & for small works upto value of cable for Rs. 25.0 Lacs Kalinga (Gold), Suraj, Delton, Grandly & Polycab make can be used) as per direction of Engineer-in-charge PWD PS No -501 (a) 3.5C x 50 Sqmm. |
| 67 | S/F of palm or pin type copper tin plated cable socket (Lug) to the cable leads, insulating with tape & making connections etc. complete in all respects as per the directions of the Engineer-in-charge. PS-504 (a) 50 Sqmm. |
| 68 | S/F of MS Cubical box of size 600x300x180mm made of MS Sheet including base plate with 6 Nos 6 to 32 Amp MCB, 8 Nos HRC Fuse 32A, 1 No. 4 pole MCB including connection, painting. Complete in all respects as per direction of E/I. (E80) |
| 69 | BOQ-B : (Civil Work:) Earth work in rough excavation , banking excavated earth in layers not exceeding 20 cm in depth, breaking clods, watering rolling each layer with % tonne roller or wooden or steel rammers, and rolling every 3rd and top-most layer with power roller of minimum & tonnes and dressing up in embankments for roads, flood banks, marginal banks and guide banks or filling up ground depressions, lead up to 50 m and lift up to 1.5 m: All kinds of soil UP PWD SOR 2020 SCHEDULE ITEM NO251 PAGE NO. 14 |
| 70 | Disposal of surplus excavated earth/mateiral within the plant area including spreading, levelling as directed at places indicated by Enginner incharge (Maximum lead 1.0 Km.) UP PWD SOR SCHEDULE ITEM NO 261 PAGE -16 |
| 71 | CONCRETE WORK:Providing and laying plain cement concrete mixed by volume in mechanical mixers with 40 mm and down aggregate as levelling course raft, foundation, floors , footings, and bed block etc. laid rough finished with wooden flats, including compacting, levelling , ramming , curing, shuttering etc. at all levels. complete as per drawing or as per direction of Engineer incharge 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size )UP SOR 2020/ 281 p-17 |
| 72 | Providng and laying in position maching batched and machine mixed design mix M-25 grage cement concrete for reinforced cement concrete work. Using cement content as per approved desing mix, including pumping of concrete to site of layig but excluding the cost of centering, shuttering, finishing and reinforcement , including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting concrete, improve workability without imparing strength and durability as per direction of Engineer-in-charge.Note Cement content considered in this item is @ 330kg/cum Excess or less cement used as per design mix is payable or recoverable separately. A) All work upto plinth level SOR Based ON DSR 2018 (Item 5.33.1) P-592 |
| 73 | B) From ± 00 level to All heights SOR based on DSR 2018 (Item 5.33.2) P-592 |
| 74 | REINFORCEMENT STEEL WORK/ STEEL EBMEEMENTSSteel reinforcement for R.C.C. Work including straightening, cutting, bending, placing in position and binding all complete upto plinth level, Cold twisted bars SOR BASED ON DSR 2018 (Item 5.22.6) |
| 75 | Steel reinforcement for R.C.C. Work including straightening, cutting, bending, placing in position and binding all complete above plinth level, Cold twisted bars SOR BASED ON DSR 2018 (Item 5.22A.6) |
| 76 | Placing and fixing in RCC work/Masonry PCC work sleeves, frames, inserts, ancher plates, anchor bolts of any description and any size at all level including carriage from employer store, positioning, levelling and supporting as per drawing and specification excluding cost of materials and fabrication and taking proper care at the time of concrete and expose the surface of insert plates after removal of shuttering and painted with approved quality red-oxide primer bolts and sleeyes to be cleaned greased and covered with water tight material after concerting or removal of shutteirng etc as predirection of the Engineer-in-charge SOR BASED ON DSR 2018/10.25.2 P-592 |
| 77 | FORM WORKCentering and shuttering including ,strutting, propping etc. and removal of form forfoundations, footing, bases of columns, etc SOR BASED ON DSR 2018 (Item 5.9.1) P-592 |
| 78 | Suspended floors, roofs, landings , balconies and acess platform SOR BASED ON DSR 2018 (Item 5.9.3.) P-592 |
| 79 | Lintels, beams, plinth beams, girders, bressumers and cantilevers. SOR BASED ON DSR-2018/5.9.5 |
| 80 | Columns, Pillars, Piers, Abutments, Posts and Struts. SOR BASED ON DSR-2018/5.9.6 |
| 81 | Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc. including cost of de-shuttering and decentering at all levels, over a height of 3.5 m, for every additional height of 1 metre or part thereof (Plan area to be measured) Suspended floors, roofs, landing, beams and balconies (Plan area to be measured).SOR BASED ON DSR-2018/5.11.1 |
| 82 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including , cutting , hosting , fixing in position and applying a priming coat of approved steel primer all complete SOR BASED ON DSR (Item 10.25.2) P-592 |
| 83 | BRICKWORK/ CONCRETE BLOCK MASONRYBrick work with common burnt clay modular bricks of class designation 7.5 in foundation and plinth in a) Cement mortar 1:6 (1 cement : 6 coarse sand ) SOR BASED ONDSR 2018 (Item 6.1.1) P-111 |
| 84 | b) In superstructure ± 00 level to any height SOR BASED ON DSR (Item 6.4.2) P-111 |
| 85 | c) Half brick masonry with common burnt clay F.P.S (non modular ) bricks of class designation 7.5 in superstructure above plinth level up to floor V level cement mortar 1:4 (1 cement : 4 coarse sand )SOR 2020/307/309/310 19 |
| 86 | FINISHING WORK (Plaster)12mm cement plaster of mix: a) 1:6 (1 cement : 3 fine sand )SOR BASED ON DSR 2018 (Item 13.1.2) P-222 |
| 87 | 6 mm cement plaster of mix: a) 1:3 (1 cement : 3 fine sand )SOR BASED ON DSR 2018 (Item 13.16.1) P-223 |
| 88 | 18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement : 5 coarse sand ) finished with a top layer 6 mm thick cement plaster 1:6 (1 cement : 6 fine sand ) DSR 2018 (Item 13.11) P-223 |
| 89 | WALL FINISHESWhite wasing with lime to give an even shade: New work (three or more coats ) UP PWD SOR SCHEDULE ITEM NO.672 2020 P-24 |
| 90 | Wall painting with acrylic emulsion paint of approved brand and manufacture to give and even shade : Two or more coats on new work DSR 2018 (Item 13.60.1) P-227 |
| 91 | Finishing walls with water proofing cement paint of required shade : New work (Two or more coats applied @ 3.84 kg/10sqm) DSR 2018 (Item 13.44.1) P-225 |
| 92 | Painting with acid proof paint of approved brand and manufacture of required colour to give an even shade : Two or more coats on new work DSR 2018 (Item 13.64.1) P-227 |
| 93 | WALL DADOProviding and fixing 1st quality ceramic glazed wall tiles conforming to IS 15622 (thickness to be specified by the manufacture), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-charge , in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 ( 1 cement : 3 coarse sand ) and jointing with grey cement slurry @ 3.3 kg per sqm, including pointing in white cement mixed with pigment of matcing shade complete SOR BASED ON DSR 2018 (Item 11.36) P-191 |
| 94 | WALL SKIRTINGCement plaster skirting upto 30 cm height, with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement . 18mm thick SOR BASED ONDSR 2018 (Item 11.6.1) P-186 |
| 95 | Providing and laying Virified tiles in different sizes (thickness to be specified by the manufacturer ), with water absorptin less than 0.08% and conforming to IS: 15622, of approved brand & manufacturer, in all colours and shade, in skirting , riser of steps, laid with cement based high polymer modified quick set tile adhesive (wate based ) conforming to IS: 15477 , in average 6 mm thickness, including grouting of joints (Payment for grouting of joints to be made separately) Size of Tile 600x600mm SOR BASED ON DSR 2018 (Item 11.41.1) P-192 |
| 96 | Providing edge moulding to 18 mm thick marble stone counters, vanities etc., including chinepolishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-charge Grainte work SOR BASED ON DSR 2018 (Item 8.3.2) P-128 |
| 97 | Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement : 3 coarse sand ) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbbing and polishing complete SOR BASED ON DSR 2018 (Item 11.27) P-190 |
| 98 | FLOOR FINISHProviding and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer ) with water absorption less than 0.08% and conforming to IS : 15622, of approved make , in all colours and shades, laid on 20 mm thick cement mortar 1:4 ( 1cement : 4 coarse sand ), including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 1000x1000 mmDSR 2018 (Item 11.41.2) P-191 |
| 99 | Supplying and laying approved quality and non-skid type vitrified tiles over 20mm thick bed of cement mortar 1:4 (1 cement : 4 coarse sand ) jointed with neat cement slurry mixed with pigment to match the sade of files including rubbing and polishing with all materials labour, tools, etc. complete as per schedule and specification and as directed by the PM SOR BASED ON. DSR 2018/11.37 P-191 |
| 100 | Providing and fixing 10 mm thick and acid and / or alkali resistant tiles of approved make and colour using acid and / or alkali resisting mortar bedding , and joints filled with acid and / or alkali resisting cement as per IS: 4457, complete as per the direction of Engineer-in-charge . Acid and alkali resistant tileSOR BASED ON DSR 2018 (Item 11.21.1.1.) P-189 |
| 101 | Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 ( 1 cement : 3 coarse sand ) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete DSR 2018 (Item 11.27) P-190 |
| 102 | CEILING FINISHWall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade: Two or more coats on new work DSR 2018 (Item 13.60.1) P-227 |
| 103 | Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade : New work (Two or more coats ) over and including priming coat with water thinnable cement primer DSR 2018 ( Item 13.41.1) P-225 |
| 104 | EXTERNAL FINISH Finishing walls with Acrylic Smooth exterior paint of required shade : Now work (Two or more coat applied @ 1.67 ltr/10sqm over and including priming coat of exterior primer applied @ 2.20kg /10 sqm) SOR BASED ON DSR 2018 (Item 13.45.1) |
| 105 | PLINTH PROTECTION Making plinth protection 50 mm thick of cement concrete 1:3:6 ( 1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size ) over 75 mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand , including finishing the top smooth . SOR on Based DSR 2018 (Item 4.17 ) P-88 |
| 106 | TERRACING Providing and fixing Heat Resistant Terrace Tiles ( 300 mm x 300 mm) with SRI (Solar refractive index)> 78, solar reflection > 0.70 and initial emittance > 0.75 on waterproof and sloped surface of terrace, laid on 20 mm thick cement sand mortar in the ration of 1:4 (1 cement : 4 coarse sand ) and grouting the joints with mix of white cement & marble powder in ration of 1:1 , including rubbing and polishing of the surface upto 3 cuts complete, including providing skirting upto 150 mm height along the parapet walls in the same manner. SOR 2020/new item no 3 pagr no 29 |
| 107 | Providing gola 75x75 mm in cement concrete 1:2:4 ( 1 cement : 2 coarse sand : 4 aggregate 10 mm and down gauge ) including finishing with cement mortar 1: 3 ( 1 cement : 3 fine sand ) as per standard design: In 75x75 mm deep chase DSR 2018 (Item 12.21.1) P-206 |
| 108 | DOOR SHUTTERSProviding and fixing ISI marked flush door shutters conforming to IS: 2202 (Part I) decorateive type, core of block board construction with frame 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters, 35 mm thick including ISI marked Stainless steel butt hinges with necessary screws DSR 2018 9.20.1 (Item 9.20.1) P-150 |
| 109 | DOOR FRAMESProviding and fixing pressed steel door frames conforming to IS: 4351, manufactured from commerical mild steel sheet of 1.60 mm thickness, including hinges, jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50x25 mm, or base ties of 1.60 mm pressed, mild steel welded or rigidly fied together by mechanical means , including M.S. pressed butt hinges 2.5 mm thick with mortar guards, lock strike-plate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by Engineer-in-charge: Fixing with adjustable lugs with split end tail to each jamb DSR 2018 (Item 10.14.2.1) P-179 |
| 110 | Supply and fixing rollinig shutters of approved make, made of required size M.S laths, interlocked together through their entiere length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locing with push and-pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part-1 and MS. Springs top over of required thickness for rolling shutters. 80x1.25 mm M.S laths with 1.25 mm thick top cover DSR 2018 (Item 10.6.1) P-177 |
| 111 | ALLUMINIUM WINDOWS DOORSProviding and fixing anodised and / or powder coated aluminium work for doors, windows Ventilatos and partitions with extruded built up standard tubular and other sections of approved make conforming to IS733 and IS 1285 anodised transparent or dyed to required shade according to IS: 1868 (Minimum anodic coating of grade AC 15 ), fixed with Rawl plugs or with fixing clips, or with expansion hold fasteners including necessary fillings upto glass junctions, at top, bottom and sides with required P V C /neoprine felt etc. Aluminium sections shall be smooth, rust free, strainght, mitred and jointed mechanically where ever required including cleat angle, stainless steel screws, Aluminum snap beading for glazing / panelling. C.P Brass/ stainless steel screws, hingers, Handles, Locks & tower bolt and all complete as per Architecural drawings and direction of Engineer-in-charge (Glazing and panelling to be paid for seprately ) SOR BASED ON DSR21.10 , P-373 |
| 112 | SANITARY FIXTURES Providing and fixing water close squatting pan (Indian type W.C. pan) with 100 mm Sand Cast Iron P or S trap, 10 litre low level white P.V.C flushing cistern, including flush pipe, manually controlled device (handle lever) conforming to IS: 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required :White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests SOR BASED ON DSR 2018 (Item 17.1.1) P-287 |
| 113 | Providing and fixing white vitreous china pedestal type water closet (European type) with seat arid lid 10 ltr. Low level white vitreous china flushing cistern & C.P. flush bend with fitting & C.I. brakets, 40m flush bend , overflow arrangement with specials of standard make and mosquito proof of approval municipal design complete including painding of fittings and brackets cutting and making good the walls and floors wherever required: W.C. pan with ISI marked white solid plastic seat and lid sor BASED On DSR 2018 (Item 17.3.1) P-287 |
| 114 | Providing and fixing wash basin with C.I brackets, 15 mm C.P. brass pillar taps, 32 mm C.P brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require: White Vitreous China Wash basin size 630x450 mm with a single 15 mm C.P brass pillar tap SOR BASED On DSR 2018 (Item 17.7.1) P-288 |
| 115 | Providing and fixing toilet paper holder: C.P. brass DSR 2018 (Item 17.34.1) P-291 |
| 116 | Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm and 340x410x265 mm sizes respectively with automatic flushing cistern with standard flush pipe and C.P brass spreaders with brass unions and G.I clamps complete, including painting of itting and bcakets, cutting and making good the walls and floors wherever required : DSR 2018 (Item 17.4.1) P-287 |
| 117 | Supplying & Installation / fixing (Complete). Of 15 mm CP health faucet of approved with necessary CP flexible hose 1000mm long nozzle, CP wall flange, C.P Holder CP angle cock etc., complete (CP Health Faucet ) (Mkt) |
| 118 | Providing and fixing C.P. brass long nose bid cock of approved quality conforming to IS standards and weighing not less than 810 gms 15 mm nominal bore DSR 2018 (Item 18.50.1) P-329 |
| 119 | Providing and fixing C.P brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 DSR 2018 (Item 18.53.1) P-328 |
| 120 | Providing and placing on terrace ( at all floor levels) polyethylene water storage tank ISI : 12701 marked , with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank DSR 2018 (Item 18.48 ) P-327 |
| 121 | Providing and fixing soil , waste and vent pipes :Centrifugally cast (Spun) iron socket & spigot (S&S) pipe as per IS: 3989 a) 100 mm dia DSR 2018 (Item 17.35.1.2) P-291 |
| 122 | b) 75 mm dia DSR 2018 (Item 17.35.2.2) P-291 |
| 123 | Providing lead caulked joints to sand cast iron/centrifugally cast (spun) iron pipes and fitting of diameter. a) 100 mm dia DSR 2018 (Item 17.58.1.) P-296 |
| 124 | b) 75 mm DSR 2018 (Item 17.58.2) P-296 |
| 125 | Providing and fixing single equal plain junction of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete: . a) 100 x100x 100mm Sand cast iron S&S as per IS-3989 DSR 2018 (Item 17.43.1.2) P-293 |
| 126 | b) 75 X75X75 mm Sand cast iron S&S as per IS- 3989 DSR 2018 (Item 17.43.2.2) P-293 |
| 127 | Providing and fixing terminal guard: sand cast iron S&S as per IS-3989 a) 100 mm DSR 2018 (Item 17.56.1.1) |
| 128 | b) 75 mm DSR 2018 (Item 17.56.2.2) |
| 129 | Providing and fixing trap of self cleansing design with screwed or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors: 100mm inlet and 75 mm outlet Sand cast Iron S&S as per IS-3989 DSR 2018 (Item 17.60.2.1) P-296 |
| 130 | Providing and fixing M.S holder -bat clamps of approved design to Sand Cast Iron/ Cast Iron (Spun) pipe embedded in and including cement concrete blocks 10x10x10 cm of 1:2:4 mix ( 1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ), including cost of cutting holes and making good the walls etc. a) for 100 mm dia pipe DSR 2018(Item 17.37.1) P-292 |
| 131 | b) For 100 mm dia pipe DSR DSR 20182016 (Item 17.37.2) P-292 |
| 132 | Slab with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand ) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 ( 1 cement : 2 coarse sand: 4 graded stone aggregate 20 mm nominal size ) finished with a floating coat of neat cement complete as per standard design: Inside size 90x80 cm and 45 cm deep including C.I cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg): With common burnt clay F.P.S( non modular ) bricks of class designation 7.5 DSR 2018 (Item 19.7.1) P-351 |
| 133 | Providing and fixing Chlorinated polyvinyl Chloride (CPVC) pipes , having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing . This includes jointing of pipes & fitting with one step CPVC solvent cement and testing of joints complete as per direction of Engineer-in-charge . Internal work-Exposed on wall of joints complete as per direction of Engineer -in-charge internal work- Exposed on wall. a) 15mm nominal outer dia pipes SOR BASED ON DSR 2018 (Item 18.8.1) P-319 |
| 134 | b) 20mm nominal outer dia pipes SOR BASED ON DSR 2018 (Item 18.8.2) P-319 |
| 135 | c) 25 mm nominal outer dia pipes SOR BASED ON DSR 2018 (Item 18.8.3) P-319 |
| 136 | Providing and laying non-pressure NP2 class (light duty) R.C.C pipes with collars jointed with shift mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand ) including testing of joints etc, complete 250 mm dia R.C.C pipe SOR BASED ON DSR 2018 (Item 19.6.3) P-362 |
| 137 | Providing and laying cement concrete 1:5:10 ( 1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all -round S.W. pipes including bed concrete as per standard design: 150 mm diameter S.W Pipe DSR 2018 (Item 19.2.2) P-349 |
| 138 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 15 mm nominal bore DSR SOR BASED ON2018 (Item 18.15.1) P-327 |
| 139 | Providing and fixing PTMT liquid soap container 102 mm wide, 138 mm high and 75 mm distance from wall of standard shape with bracket of the same materials with snap fittings of approved quality and colour weighing not less than 106gms SOR BASED ON.DSR 2018 (Item 17.71) P-297 |
| 140 | Providing and fixing stainless Stee A ISI 304 ( 18/8) kitchen sink as per IS 13983 with C.I brackets and stainless steel plug 40 mm. including painting of fittings and brackets, cutting and making good the walls wherever required: 510x1040 mm bowl depth 178 mm DSR 2018 (Item 17.10.1.1) P-289 |
| 141 | Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fitting arrangement of approved quality and colour. 600 mm long towel rail with total length of 645 mm , width 78 mm and effective hight of 88 mm weighing not less than 190 gms SOR BASED ON DSR 2018 (Item 17.73.2) P-297 |
| 142 | Providing and fixing 600x450 mm beveled edge mirror of superior glass ( of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P brass screws and washers complete SOR BASED ON DSR 2018 (Item 17.31) P-294 |
| 143 | MISCELLANEOUS BUILDING WORKSGranite of any colour and shade Area of slab over 0.50 sqm DSR 2018 (Item 8.2.2.2) P-128 |
| 144 | ANTI TERMITE TREATMENT Diluting and injecting chemical emulsion for POST-CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) : Along external wall where the apron is not provided using chemical emulsion @ 7.5 litres/sqm of the vertical surface of the substructure to a depth of 300 mm including excavation channel along the wall & rodding etc. complete : With Chlorpyriphos/ Lindane E.G. 20% with 1% concentration SOR Based on DSR 2018 (Item 2.35.1.1) |
| 145 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail