Name of Work:- A/R & M/O WSS Parour Kharoth & Jharet Rajhoon in Tehsil Pal ur Distt. Kangra (HP) (SH: - Grouting of cracks with water proofing main in the bed & walls of settling tank at WTP Jia)
Sl. No.
Item Description
1
Surface preparation, Treating the cracks, cleaning of survace with the help of various equipment wire brush etc. and surface to be made dirt, oil and foreign particles free. Once the cleaning is done the site area will be washed with watre to do away with micro fine particles from the water proofing area. All the area where water proofing job will be taken should be closed for normal foot trafic till .complete curing of water proofing job. Repair o surface with polymer modified mirtar (cement/ watr/ Fosroc nitobond SBRlatex) All the cracks to be repaired and filled with polymer midified mortar Any loose area present on the surface will also be repaired with PMM. Repair area will be required to cure for one day before application of water proofing coating on the surface will also be repaired with PMM. Repair are will be required to cure for one day before application of water proofing coating on the surface. Any pipe penetrations in the surface will be repaired and sealed with PMM. complete in all respect as per direction of Engineer in charge with in all leads and lifts.
2
Drilling and fixing injection packers in RCC members for cementitious grouting, drililng holes in structural members at the intervals as per recommendations/ requirements cleaning the holes by air blower prior to fixing nozzles.Insert 12 mm dia 50-75 In m long PVC or equivalent injection packers in cleaned holes with fast setting mortar like renderoc plug or equivalent cut the packers by cut of whoel aller completion of grouting without damaging structural elements.Injection grouting : Supplying & applying plasticised expanding grout admixture cementitious grouts cebex 100 of Fosroc or equivalent having chloride content Nil as per BS 5075, Typical unrestrained expansion of upto 1% in general.The admixture should be mixed a 225 gms 50 kg of ement as per manufacturers specificationed as directed, Grouting of structural
3
Cracks (it any): Injection Nozzle Packing cracks: Drilling and foxing injection packers in RCC members for grouting, drilling holes in structureal members at theintervals 200 mm o to o or as per site requirements, cleaning the holes by air blower prior to fixing nozzles prssure grouting using moisture insensilive, low viscous epoxy grout conbextra EP 10(M) of Fosroc having mix density 1060 kg/ m3, compressivel 2) strength (ASTM D695)-60 N/mm2. Finally cut the projected nozzle and seal with RENDEROC HS EXTRA with in all leads and lifts as per the direction of Engineer in charge.
4
Providing and applying waterproofing treatment to sound, moisture free concrete surface unsing Bursh bond RFX Grey manufactured by Fosroc chemicals india PVT. Ltd and applied by Fosroc authoried applicator.Well cleaned, dry and leveled concrete surface shall be primed with Nitobond SBR LATEX (diluted with water in alratio of 1 part SBR LATEX:4 part :5 part cement) applied at coverage of 10 sqm / Litre (after dilution) following by application of Brushbond RFX Grey @ recommended consumption of 12-14 sqm / Pack for 1 mm thickness in two coats. Burshbond RFX is high performance Elastomeric cementitious water proof coating.It shall be applied in two coats at coverage rate of 12-14 sqm/ Pack to acheve a minimum WFT of 1 mm. The memebrane formed hall confirm the following minimum properties:
5
1) Pot life :30 Min 270 as per 270 C as per ASTMD 4060, 454T,638, ASTMC 8362)
6
2) Mixed density : 1.68gloc (Brushable consistency)
7
3) Adhesion to concret
8
4) Static cracks accommodation :1 mm to concrete>1N/mm2
9
5) Turbity Non : Non Toxic
10
6) System includes supply, application, termination complete in all respect as per the manufacturer,s specification and hodology Nitroseal PU-40 & Fiber mesh etc.
11
7) Protection screed EP- EPOXY concrete bonding agent for use scred bonding over the coating providing and laying of average 100 mm thick ( min 50 mm at the drains) M20 grade concrete in slope admixed with approved integrul waterproofing compound like conplast WLXtra @ 200 ml/ sO kg cement bag, including making of concave coving of size 100 mm x 100 mm at the wall floor comers using same concrete. (Item will be contractor's scope)
12
8) Providing and fixing injection packers in RCC members for cementitous grouting, drilling holes in structural members at the qty. Terms and condition :- intervals as per recommendations/ requirements cleaning the holes by air blower prior to fixing nozzles. Insert 12 mm dia 50-75 mm2 0.32 metre holes with fast setting mortar like Renderoc Plug 75 mm long PVC or equivalent injection packers in cleaned holes Nothing shall be paid for the rejected work/ material 185.00. The work should be carried out as per specifications. Please Enable Macros to View BoQ information