| 1 | Erection of 33 kv overhead line Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement 3 course sand; 6 graded aggregate 40mm nominal size) foundation including excavation and refilling etc. required above 11.0 meter and up to 12 meter |
| 2 | Erection of ACSR conductor of 7/3.35 mm to 7/4.00 diameter and above including binding etc. as required |
| 3 | Supplying and erection of galvanised stay stay set for 33 Kv overhead lines complete with 19/20mm dia X 1.8 meters long stay rodn anchor plate of size 45cm x 45cm x 7.5mm thick, thimble, stay clamps, turn buckle(20mm x 600mm x 7/4.00 mm dia GI stay wire and 33kv starin insulator etc in cement concrete 1:3:6 (1 cement 3 course sand; 6 graded aggregate 40mm nominal size) foundation including excavation and refilling etc as required |
| 4 | Supplying and erection of 33 KV pin insulator complete with large steel head G.I.pin,nuts, washers etc. as required. |
| 5 | Supplying and erection of a set of three 11KV disc insulator for 33 KV overhead lines with galvanised insulator fittings ball and socket type and complete with galvanized strain clamps, bolts, nuts, washers etc. as required |
| 6 | Supplying of two lengths of channel iron 100 mmX50mmX6mm(9.56Kg per meter) double pole cross arm for three wire 33 KV overhead line conductors complete with through bolts and nuts for clamping to the poles, 50mmX6mm M.S.fiats welded on one side to the channel iron and with bolts and nuts on the other side for tying the cross arm together, including drilling holes for insulator pins/fittings, bolts, nuts, washers etc. and painting with primer and finish paint as required |
| 7 | Erection of double pole 3 wire cross arm for 11KV/22KV/ 33KV overhead lines as required. |
| 8 | Supplying and erection of a set of cross bracing FRLS frame work for 33KV overhead line double pole structure having four members fabricated out of 65mmX65mmX6mm angle iron to form a rectangle of minimum size 2400 mm width X 2800 mm height complete with 50mmX6mm M.S. flat iron clamps, bolts, nuts including drilling holes for insulator pins, bolts, nuts, washer set and painting with primer and finish paint as required. |
| 9 | Dismantel/Erection of 3.3 kv overheadline Dismantling of pole/street light standard/strut embedded in cement concrete foundation etc.as required |
| 10 | Dismantling of over lines comprising of copper/aluminium overhead conductor, G.I.wire, cross arms, insulators etc. as required. |
| 11 | Erection of metallic pole of following length in cement concrete 1:3:6 (1) cement: 3 coarse sand: 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. required. Above 11.0 meter and up to 12.0 meter |
| 12 | Erection of ACSR conductor of 7/3.35 mm to 7/4.00 diameter and above including binding etc. as required |
| 13 | Supplying and erection of galvanized stay set for 3.3 KV overhead lines of complete with 19/20 mm dia X 1.8 meters long stay rod, anchor plate of size 45cm X 45cm X 7.5cm thick, thimble,stay clamps, turn buckle (20mm X 600mm),7/4.00mm dia G.I.stay wire and 3.3 KV strain insulator etc. in cement concrete 1:3:6(1 cement: 3 coarse sand 6 graded stone aggregate 40mm nominal size) foundation including excavation and refilling etc. as required. |
| 14 | Supplying and erection of 3 3KV overhead lines with galvanized insulator fittings, ball and socket type and complete with galvanized strain clamps, bolts, nuts, washers, etc.as required |
| 15 | Supplying and erection of 3.3 KV pin insulator complete with large steel head G.I.pin, nuts, washers etc. as required. |
| 16 | Supplying of channel iron 75mmX40mmX6mm(7.14kg per meter) pole top bracket/cross arm for single 11KV overhead line conductor complete with 50mmX6mm M.S. flat iron clamps, bolts, and nuts including drilling holes for insulator pins, bolts, nuts, and washers etc. (as per drawing) and painting with primer and finish paint as required. |
| 17 | Supplying of t channel iron 75mmX40mmX6mm(7.14kg per meter) cross arm for two 11KV overhead line conductors complete with 50mmX50mmX6mm (angle iron bracket welded to the channel iron and complete with 50mmX6mm M.S. flat iron clamps, bolts and nuts including drilling holes for insulator pins, bolts, nuts, washers etc. (as per drawing) and painting with primer and finish paint as required. |
| 18 | Supplying of two lengths of channel iron 75mm X 40mm X 6mm(7.14 kg per meter) double pole cross arm for three wire 3.3 KV overhead line conductors complete with through bolts and nuts for clamping to the poles, 50mm X 6mm M.S. flats welded on one side to the channel iron with bolts and nuts on the other side for tying the cross arms together, including drilling holes for insulator pins/fittings, bolts, nuts and washers etc. (as per drawing) and painting with primer and finish paint as required. |
| 19 | Erection of pole top/straight two wire/ V shape two wire, angle iron/channel iron, cross arm on steel tubular/ rail/ PCC p;e for 11/22/33 KV as required. |
| 20 | Supplying and erection of a set of cross bracing FRLS frame work for 3.3 KV overhead line double pole structure having four members fabricated out of 50mm X 50 mm X 6mm angle iron to form a rectangle ogf monimum size 1400mm width X 2500 mm height, complete with 50mm X 6mm M.S. flat iron clamps, bolts and nuts including drilling holes for insulator pins, bolts and nuts etc. (as per drawing) and painting with primer and finish paint as required. |
| 21 | Providing and fixing of GOAB switch 11KV, 630 Amp, 25kA. Triple pole, Double Break, horizontal upright mounting with 11KV grade porcelain post insulator, vertical operating pipe, phase coupling pipe. |
| 22 | Supply of 7/16 SWG G.I wire for continuity |
| 23 | Supply of 8 SWG G.I. wire |
| 24 | Erection of G.I. wire No. 8 SWG including binding etc. as required. |
| 25 | Erection of cradle guard as required |
| 26 | Earthing with G.I. earth plate 600 mm X 600 mm X 6mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/coke and salt as required. |
| 27 | Total impact of GST for the purpose of CTC Please Enable Macros to View BoQ information |