|
| 1 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying cables, foundation for pole, etc and getting out in hard/dense soil complete all as specified and as directed. |
| 2 | Excavation in trenches exceeding 1.5 m wide and not exceeding 3.0 m in depth for laying cables, foundation for pole, etc and getting out in hard/dense soil complete all as specified and as directed. |
| 3 | Returning, filling in, including spreading, levelling, watering and well ramming of soil in layers n. exc 25cm thick complete all as specified and as directed. |
| 4 | Removing excavated soil to distance n. exc 50m and depositing where directed at a level n. exc 1.5m above the starting point complete all as specified and as directed. |
| 5 | Materials and labour for sand filling around the cable with approved quality coarse sand for sand cushioning of Under ground cable including spreading and punning down to requirred thickness complete all as specified and as directed. Note: Thickness of sand cushioning after punning down shall be measured for payment purpose. |
| 6 | Materials and labour for brick protection cover to underground cables with sub class ‘B’ over burnt brick of size 23 X 11.5 X 7.5 cm, (locally available best quality), laid dry and flat abutting each other with gaps not exceeding 10mm complete all as specified and as directed. |
| 7 | M&L for erection and fixing of steel tubular swaged pole type 410 SP - 31 (9.00 metres long) confirming to IS- 2713 Part I to III 1980 with and including cast iron base plate, finial taper plug, nuts, bolts and washers etc. fixed in PCC foundation duly painted painted with two coats of Aluminium paint over a coat of red oxide primer with 30 cm of black,yellow and white paint upto 1.2m including preparation of surface and including dismsntling of old pole of any size and description with foundation, PCC coping etc. complete all as specified and as directed. |
| 8 | M&L for PCC 1:4:8, type D2 (using 40 mm graded stone aggregate) as in foundations, filling and mass concrete complete all as specified and as directed. |
| 9 | M&L for PCC 1:3:6, type C2 (using 40 mm graded stone aggregate) as in foundations, filling and mass concrete complete all as specified and as directed. |
| 10 | M&L for PCC 1:2:4 type B-1 (using 20 mm graded stone aggregate) as in coping for the new/existing Steel Poles, cills, including necessary formwork (straight or curved) complete all as specified and as directed. |
| 11 | M& L for Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100mm height, 65mm dia for 1100 volts grade, including taking down of old ones complete all as specified and as directed. |
| 12 | M& L for Loop type insulator, vitreous porcelain, white, brown or green Large size, with overall dimensions 90mmx140mm, clearance of hole 25.5mm for 1100 volts grade with suitable size of insulator bolts,washers and nuts etc, including taking down of old ones complete all as specified and as directed. |
| 13 | M&L for preparation of old painted surface of 9/11 metre long steel pole with cross arms and brackets and two applying two coats of aluminium paint and writing pole nos with synthetic enamel black japan paint at a height of 1.5 mtr above ground level and black and yellow strips of 30cm each 3 nos complete all as specified and as directed. |
| 14 | M&L for Cross arms, bracings, supports, clamps, eye hook and back plates fabricated from structural steel sections including pole clamps, stay clamps, D clamps nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed including painting with one coat of aluminium paint over a coat of red oxide primer including taking down the old unserviceable cross arms, clamps etc complete all as specified and as directed. |
| 15 | M&L for ACSR conductors (weasel type) for LT OH lines on poles including stringing, binding with aluminium wire 14 SWG or aluminium tape including jumpers complete connecting of disconnected cable, service cable and street light connection including taking down the old unserviceable ACSR conductor of any type complete all as specified and as directed. |
| 16 | Material and labour for restringing, tightening of loose/broken ACSR conductor of any size and type, maintaining standard sag including binding the conductor with pin/shackle insulator and jumpers with aluminum binding wire not less than 2.00mm dia, PG clamp etc on HT/LT over head lines complete all as specified and as directed. |
| 17 | M & L for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 50 sqmm 3½ core laid in trenches /floor or fixed on wall /pole in including brass compression cable glands, terminal lugs etc, including taking down old unserviceable UG cable any type complete all as specified and as directed. |
| 18 | M&L for GI pipe light grade 50mm bore with all fittings laid in trenches or in floors, including taking up/ down old pipe complete all as speciffied and as directed. |
| 19 | S&F in repair for cable jointing kit for LT (Earthed) grade cable for end termination outdoor heat/cold shrink type joint complete with jointing material and accessories suitable for for aluminium Conductor cable size 70-120 Sqmm 3.5/4 core complete all as specified and as directed. |
| 20 | M & L for cutting the existing hard standing/PCC/WBM road at a depth not less than 30 cm and 15 cm wide for passing of cable through GI pipe returning filling in complete including finishing the surfaces by providing cement concrete (1:2:4) type B2 using 40mm grade stone aggregate) upto 20cm depth,finishing to a uniform smooth surface to match the existing surface complete all as specified and directed.Note - GI pipes shall be measured and paid seprately under relevant item of this schedule. |
| 21 | S & F wall mounted Busbar chamber made of ETP grade copper of capacity 100 A , 4 Way with suitable enclosure and connected accessories, clamps, MS stand with PCC if required, nuts and bolts ,earth work etc, Complete all as specified and as directed.Make -Havells, Cat No. IHBC025004 /L&T / ABB / Legrand / Schnieder as approved by AGE(I) Please Enable Macros to View BoQ information |
| 22 | S & F wall mounted Busbar chamber made of ETP grade copper of capacity 100 A , 4 Way with suitable enclosure and connected accessories, clamps, MS stand with PCC if required, nuts and bolts ,earth work etc, Complete all as specified and as directed.Make -Havells, Cat No. IHBC025004 /L&T / ABB / Legrand / Schnieder as approved by AGE(I) Please Enable Macros to View BoQ information |