| 1 | Supply/ Procurement of ABT meter & metering infrastructure suitable for metering on 01nos of 33 KV feeder, 50 Hz and suitable for installation of CT/PT of specification mentioned in Sr. No.3&4 below (Cost of CT/PT is not included in this) System as per relevent specification of the state DICOM/TRANCO/SLDC, as mentioned below :- Secure/L&T Make ABT Meter for 33.KV CT Ratio -/1A Accuracy:0.25s, complete with Software, MRI instrument and all accessories required for installation of meter and to start of Open Access complete. The meter should be relevant IS marked and open access standards complete all as specified and directed. |
| 2 | Supply, installation, and testing of 33 KV Outdoor type CT of 0.2s of 0.2 accuracy class having burden of 5 VA respect , in confirmation to DISCOM/UPPTCL/SLDC Specification with Cubical (CT-PT ratio depends on the existing meter available at comsumer site) of relevant IS standard and as per Open access requirement complete all as specified and directed. |
| 3 | Supply, installation and testing of 33 KV Outdoor type PT of 0.2 accuracy class having burden of 10 VA respect, in confirmation to DISCOM/UPPTCL/SLDC Specification with Cubical (CT-PT ratio depends on the existing meter available at comsumer site) of relevant IS standard and as per Open access requirement complete all as specified and directed. |
| 4 | Supply, installation and testing of 33 KV Indoor type CT of 0.2s & PT of 0.2 accuracy class having burden of 5&10 VA respect, in confirmation to DISCOM/UPPTCL/SLDC Specification with Cubical (CT-PT ratio depends on the existing meter available at comsumer site) of relevant IS standard and as per Open access requirement complete all as specified and directed. |
| 5 | Supply, installation and testing of 33 KV outdoor type oil cooled combined CT-PT unit having CT ratio 200/1A, class 0.2S, burden 15 VA PT ratio 33KV/110V, class 0.2, Burden 30 VA in confirmation to IS 2705/1992 & 3156/1992. including pole mounted metering panel size not less than 450x900 x 400 mm.made out of 3.15 mm thick powder coated CRC sheet suitable to accommodate ABT meter and accessories complete all as specified and directed. |
| 6 | Open Access Approvals, Installation and commissioning of the metering infrastructures including but not limited to inspection, Testing and Installation of Meter infrastructure ( item 1 above ) liaisoning work as listed below : |
| 7 | Project management and coordination with vendor/DISCOM/UPPCL for timely execution and installation of metering infrastructure complete all as specified and directed. |
| 8 | Liason for getting approval from DISCOM and SLDC for acording Open Access for initiation of the subsequent activities and registration at UPSLDC including all standsrd process, documentation and obtain NOC complete all as specified. |
| 9 | Liason with metering and other allied wings of DISCOM and UPPCL for witnessing testing and installation, commissioning, sealing of the respective equipment and joint inspection report of all the meters to be installed at metering point complete all as specified and directed. Work in DISCOM's/UPPCL site, accessories and cable etc. |
| 10 | Final NOC for power commencement and scheduling from concerned TRANSCO/DISCOM/SLDC for making final delivery of power as per application duration & load requirement complete all as specified and directed. |
| 11 | NOC from concerned TRANSCO/SLDC for first installation complete all as specified and directed. |
| 12 | Construction of foundation for the finalisation of installation of CT/PT complete all as specified and directed. |
| 13 | Installation, commissioning, sealing of the respective equipment and joint inspection report of all the meters to be installed at metering point. Work in DISCOM's site including arrangement of crane, cable, welding, execution,transmission, hardware and cable accessories and cabling etc complete all as specified and directed. |
| 14 | (i) Electrical inspection of metering infrastructure by an authorised independent electrical inspector (ii) Electrical safety NOC at consumer premises. This includes in vendor scope and no extra payment will be made for it complete all as specified and directed. |
| 15 | Final NOC for power commencement and scheduling from concerned Trading Centre for making final delivery of power as per application duration & load requirement of Open Access transaction complete all as specified and directed. |
| 16 | Labour charges towards cabling electrical and general hardware , installation of CT-PT arrangement for mounting of meter cublicle, welding etc. at metering point. (i) unit adjustment services at UPSLDC complete all as specified and directed. (ii) unit adjustment services at DISCOM complete all as specified and directed. |
| 17 | Testing fee of NABL for performing meter testing in the presence of UPPCL Other Statutory fee for any requirement from SLDC and other authorities paid by consumers complete all as specified and directed. |
| 18 | NOC from concerned TRANSCO/SLDC for first installation complete all as specified and directed. |
| 19 | Regulatory support and assistance for the complete one year of services starting from the grant of Open Access complete all as specified and directed. Note:- The job includes arrangement of standing clearance/NOC/concurrence fron the Nodal agency (SLDC) for short term open access (STOA) for a period of one year to the MES facility 33 KV incoming power from UPPCL and implementin Open Access by accomplishing procurement of power for MES through Power Exchange Bilateral mechanism complete all as specified and directed. The scope of work also includes the following scope of work:- |
| 20 | (i) complete project management and coordination woith vendors for timely execution and installation of metering infrastructure. (ii) All required coordibnation with distribution licencee i.e. PVVNL, UPPTCL & nodal agency (SLDC) in arranging the requisute approvals for Short Term Open Acess (STOA) for the period of one year will be carried out by the vendor. (iii) Coordination in procuring ABT meters and coresponding CT/PT arrangement required for availing power in STOA complete with installation and providing requisite certificates and NOCs. (iv) Coordination for testing of meters by independent Authorised agency (NABL accredited) at consumer premises will be arranged by the vendor. (v) Requisite coordination with distribution/ third party electrical contractor & transmission lincesee for installation & sealing of meters at consumer premises. (vi) Submission of compliance reports & arranging final NOC/ concurrence for STOA for trading in Open Access for implementing purchase of power through Open Access. (vii) Monthly liasioning & consultancy for arranging NOC/ Open Acess approval from SLDC & Discom upto one year. (viii) Billing settlement on monthly basis with Distribution licensee upto one year. |
| 21 | SITE VISIT (i) The bidder is advised to visit and examine the site of work and its surroundings and obtain for itself on its own resposibility all info tha may be necessary for preparing the bid and entering into a contract for the required job. The cost of visiting the site shall be borne by the bidder. (ii) The bidder or any of its personal or agents shall be granted permission by the employer to enter upon its premises and land for the purpose of suich visits , but only upon the express conditions that the bidder, its personal and agents will release and indemnify the employer and aits personnel ,agents from and against all liabilities in respect thereof, and will be resposible for deathn or injury, loss or damage to property and any other loss, damage costs and expense incurred as a result of inpection complete all as specified and directed. |
| 22 | The bidder shall not be entitled to hold any claim against MES for non compliance due to lack of any kind of pre requisite info as it is the sole resposibility of the bidder to obtain all the necessary info with regard to site , surrounding working condition , weather etc. on its own before submission of the bid . All statutory charges in respect of the above is included in the rate quoted. No extra payment shall be paid to the bidder complete all as specified and directed. |
| 23 | S& F Metering Panel CPRI approve for Main Meter of size not less than 1.5mx 1.5m x 1.0m made out of 3.15 mm thick powder coated CRCA sheet suitable to accommodate ABT meter and accessories complete all as specified and directed. Note :- Size of panel will be approved by Engr-in-Charge as directed. |
| 24 | M&L for sand cushioning to U/G cable in layers of 23 cm thick ( 8 Cm before laying the cable and 15 Cm thick after laying the cable) in trenches complete all as specified and directed. Note :- Only Puned down volume shall be measured. |
| 25 | Supply and laying un-reinforced precast concrete cable cover, class HV, Type I, flat size 300 mm x 180 mm x 40 mm laid dry for protection of UG cable complete all as specified and directed |
| 26 | Supply, laying & testing cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 33000 volts (Earthed) grade HT cable, of size 3 core 300 sq mm complete all as specified and directed. |
| 27 | Supply and fix cable jointing kit for 33 KV grade cable for outdoor termination Heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 300 sq mm complete all as specified and as directed |
| 28 | M&L for earthing complete with galvanised steel earth plate electrode 600 x 600 x 6 mm thick, burried directly into the ground (earth pit not less than 2.25 mtr below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to GI earth strip 25x4 mm by means of bolts, nuts, check nuts, and washers of galvanised iron or steel all as shown iln electrical plate No. 3 connected to earthing test point all as specified or indicated including excavation and connected earth work, PCC chamber and cover, watering pipe, funnel wire mesh but without earth lead protection pipe and test on completion after dismantling unserviceable erthing complete all as directed. |
| 29 | M&L for point wiring with 1100 volt grade PVC insulated and unsheathed 1.5 Sq mm (FRLSH) multistranded copper conductor cable with continuous earth wire of 1.5 Sq mm (FRLS) multistranded copper conductor cable PVC insulated and unsheathed, drawn in & including concealed/surface PVC medium grade with fittings (ISI marked) not less than 20 mm dia & 1.6 mm thick sunken pressed steel galvanised terminal boxes with top cover ISI marked plastic laminated hylam sheet for housing/ fixing switches etc complete all as specified and directed for the following:- |
| 30 | (a) One light/ holder/fan/exhaust/bell point controlled by one switch. |
| 31 | (b) One 5 pin 5 Amp switch socket combination point on an independent board. |
| 32 | (c ) One 5 pin 5 Amp switch socket combination point on an same board. |
| 33 | All as per item 14 here in before but for one 15 Amp 6 Pin switch socket combination independent with 4.0 Sqmm FRLS unsheathed copper conductor single core multistranded complete all as specified. |
| 34 | S&F in replacement of Switch Piano flush type 5 Amp single pole one way. |
| 35 | S&F in replacement of switch socket combination 2 in 1 flush type 5 Amp 5 Pin |
| 36 | S&F in replacement of switch socket combination 5 in 1, 15 Amp flush type |
| 37 | S&F in replacement LED batten Tube light surface / wall mounted with specially designed powder coated aluminum hou sing, high optically efficient polycarbonate diffuser, in built electronic driver duly wired upto terminal block, power consumption <20W (4 FT 22 W), luminaire lumen >2000 Im, system efficiency of >120 lumens /W, with LED binning as per ANSI Bin C78.377A, photo biological safety report as per IEC624718 & electrical insulation class I, Ingress protection IP 20. colour rendering index CRI>80, temp range 0 to 450C, driver efficency>85%, power factor>0.9,| THD <20% as per IEC 61000-3-2, colour temp -650OK, surge protection 2.5 KV, 50000 burning hrs (mnin) as per L70 criteria, two stages isolated constant current operated driver with range 150- 270V AC and seafty extra low voltage safe level <60V DC as per IEC standard with LM70 & LM80 certification including marking CA No on LED fitting with permanent marker style and size completed all as specified and directed. |
| 38 | Supply and fix exhasut fan heav duty metal bod AC single phase, 450 Volt of size 300 mm sweep with blades and frame louvers and frame and louvers and shutter complete all as specified and directed. |
| 39 | Supply and Laying cable XLPE Insulated screened PVC bedded, galvanized steel strip armoured service cable pole to building electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 Sqmm 2.0 Core incl dismentaling complete all as specified and directed. |
| 40 | Supply and laying DWC high density polyethelene pipes having dia 63/50 mm, innder dia as per site equitpmet having corrugation on the wall and plain surfaces on the inner wall conforming to IS-14930 (Part-I & II) for protection of under ground cable laid along pole/along wall/ in PCC/GL Roof and including all fittings as required at site complete all as specified and directed. |
| 41 | M & L for Surface excavation n.exc (not exceeding) 30 cm deep and averaging 15cm deep and getting out complete all as specified and directed. |
| 42 | Excavating over areas, n exc 1.5 m deep ; for foundation and getting out in soft/loose soil complete all as specified and directed. |
| 43 | Excavation in trenches not exceeding 1.5 mtr in depth for laying of cables including getting out in any type of soil complete all as specified and directed. |
| 44 | M & L for PCC 1:4:8 type D-2 as in foundations, filling and mass-concrete etc complete all as specified and directed. |
| 45 | Returning, filling in including spreading, leveling, watering and well ramming in layers n exc 25 cm complete all as specified and directed. |
| 46 | Removal of surplus excavated soil to a distance n exc 50 m and deposited where directed at a level n exc 1.5 m above the starting point all as specified and directed. |
| 47 | M & L for Type B1 1:2:4 RCC nominal mix as in Foundations, including rafts, footings, foundation beams; plinth beams; bases for columns, etc; basement slabs, under-reamed piles and mass concrete etc complete all as specified and directed. |
| 48 | M & L for formwork to sides of concrete foundations, footings, bases of columns, raft and raft beams, sides and soffits (if any) of foundation and plinth beams; and similar work; vertical or to batter etc complete all as specified and directed. |
| 49 | M & L for Mild steel TMT fe 500D bars 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with the including mild steel wire (annealed) not less than 0.9mm dia or securing with clips etc complete all as specified and directed. |
| 50 | M & L for Mild steel TMT fe 500D bars 5mm dia and over upto and including 10mm dia in stirrups, spacers and binders etc complete all as specified and directed. |
| 51 | M & L for Type B1 1:2:4 RCC nominal mix as in Columns, pillars, piers, posts and struts etc complete all as specified and directed. |
| 52 | M&L for Formwork to sides of pillars, posts, struts, piers, columns and stanchionsa complete all as specified and directed. |
| 53 | M&L for Brick work with sub-class `B' bricks, straight or curved on plan exc 6m mean radius built in cement mortor (1:6) complete all as specified and directeddirected. |
| 54 | M & L for Type B1 1:2:4 RCC nominal mix as in Beams, cantilevers, bressummers, lintels over 1.5m span etc complete all as specified and directed. |
| 55 | M & L for form work as in roof beams etc complete all as specified and directed. |
| 56 | M & L for Type B1 1:2:4 RCC nominal mix For Slabs supported on walls, beams and columns in floors, roofs, landings, balconies, canopies, deck slabs and in shelves and omplete all as specified and directed. |
| 57 | M& L for Formwork to soffits of suspended slabs such as roof slabs, floor slabs, landings and similar work; not exceeding 200mm thick (Horizontal or sloping) etc all specified and directed. |
| 58 | M & L for rendering 15 mm thick in CM 1:6 on brick or concrete surfaces fair finished even and smooth w/o using extra cement complete all as specified and directed. |
| 59 | M & L for Rendering 5mm thick in CM (1:3) on fair faces on ceilling concrete surfaces to be finished even and smooth without using extra cement complete all as specified and directed |
| 60 | M & L for rendering 15 mm thick in CM 1:4 on brick or concrete surfaces fair finished even and smooth w/o using extra cement complete all as specified and directed. |
| 61 | M & L for preparation of new plastered surfaces of wall and applying two coats of OBD over a coat of 1mm thick wall care putty on internal wall surface complete all as specified and directed. |
| 62 | M & L for preparation of new plastered surfaces of ceiling and applying three coats of white wash on ceilling complete all as specified and directed. |
| 63 | M & L for preparation of new plastered surfaces of walls and applying two coats of cement base paint over one coat of alkali resistant priming paint complete all as specified and as directed. |
| 64 | M&L for 75mm thick Cement concrete type B-1 , 1:2:4 (using 20 mm graded stone aggregate) as in flooring over 75 mm thick cement concrete type D-2, 1:4:8 (using 40 mm graded stone aggregate) as in sub base complete all as specified and directed Please Enable Macros to View BoQ information |
| 65 | M&L for 75mm thick Cement concrete type B-1 , 1:2:4 (using 20 mm graded stone aggregate) as in flooring over 75 mm thick cement concrete type D-2, 1:4:8 (using 40 mm graded stone aggregate) as in sub base complete all as specified and directed Please Enable Macros to View BoQ information |