| 1 | DAMAGED EQUIPMENTS AT DIFFERENT RECEIVNG STATION DURING FLASH FLOODS OCCURRED DURING THE MONTH OF AUG 2025 IN RESPECT OF STD-III KATHUA. |
| 2 | SITC OF 11KV VCB Panel sets (incomer 12 KV, 1250 A,25 KA, 750/375/5-5A and outgoing 12 KV, 1250 A,25 KA, 400/200/5-5A) with vaccum circuit breaker & control panel including cast resin CT,PT,E/F, master Trip Relay &O/C relay(IEC 61850) Mimic diagram, voltmeter, , DLMS compliant with RS-485 port, Annunciation window with annunication relays and other accessories etc as per TS, scope of work & approved drawings along with mandatory spares i.e. O/C + E/F relay, Vaccum Interupter 2000 Amps, master Trip relay etc.(SCADA Compatible) at R/Stations: Paharpur (1+3), Ghagwal (1),challan pranjali (1), Lahri Kudhter (1+2), Hiranagar (1), Basholi (2 Outgoing), Hatlimorh-I (1+2) & Ramkot (1+2) along with Bus Adapter for compatibility with existing Panels at every station.(Bus Bar should be Copper made).(Dismanteling of Old and Installation with New) |
| 3 | SITC OF 11KV LA, i.e Gapless surge arrestor 9 KV, 10 KA, LA with polymar housing . Station type for 11 KV Line (3LAs in 1 set) with conventional earthing(4Nos.), Hot dipped galvanized 600mmx600mmx6mm thick plate welded with GI Strips for earthing of size 50mmX6mm for connection of lightening arrestor as per IS2629/85, GI Nuts and bolts,refilled with good earth, charcoal dust, salt, etc inside the Pit as per the direction of site engineer, enhancement material and earth chamber made of brick masonar with RCC slab cover (3LAs in 1 set) at R/Stations: Paharpur (2 Set), Hiranagar (2 Set), Palli (2 Set), Hatlimorh-I (2 Set). (Dismanteling of Old and Installation with New) |
| 4 | SITC OF 11KV XPLE 3 core 95 sq.mm , round wire armoured cable, FRLS confirming to IS 7098 ( part-II)- 1985 standards at R/Stations: Sherpur (30 Mtr), Paharpur (30 Mtr), Channi (40 Mtr) for Auxillary Transformers. (Dismanteling of Old and Installation with New) |
| 5 | SITC OF 11KV XPLE 3 core 300 sq.mm , round wire armoured cable, FRLS confirming to IS 7098 ( part-II)- 1985 standards at R/Stations: Ghagwal (100 Mtr), Paharpur (120 Mtr), Rajpura (70 Mtr), Hiranagar-I (140 Mtr), Palli (70 Mtr), Hatlimorh-I (70 Mtr), Marheen (70 Mtr) & Phinter (70 Mtr). (Dismanteling of Old and Installation with New) |
| 6 | SITC OF 11KV XPLE Single core 630 sq.mm, round wire armoured cable, FRLS confirming to IS 7098 ( part-II)- 1985 standards at R/Stations: Rajpura (150 Mtr) & Hiranagar-I (150 Mtr). (Dismanteling of Old and Installation with New) |
| 7 | SITC OF 11 KV Cable Kits Three Core, 95 mm2 ‐Outdoor (CPRI tested) with bar coding printed on it |
| 8 | SITC OF 11 KV Cable Kits Three Core, 95 mm2 ‐Indoor (CPRI tested) with bar coding printed on it |
| 9 | SITC OF 11 KV Cable Kits Three Core, 300 mm2 ‐Outdoor (CPRI tested) with bar coding printed on it |
| 10 | SITC OF 11 KV Cable Kits Three Core, 300 mm2 ‐Indoor (CPRI tested) with bar coding printed on it |
| 11 | SITC OF 11 KV Cable Kits Single Core, 630 mm2 ‐Outdoor (CPRI tested) with bar coding printed on it |
| 12 | SITC OF 11 KV Cable Kits Single Core, 630 mm2 ‐Indoor (CPRI tested) with bar coding printed on it |
| 13 | SITC of (A) Battery Bank 30V-100AH, 18 No. cells of 2 Volt each, sealed maintenance free VRLA Type, high impact poly prophelene copolymer container,flame retardent of reputed make, with suitable rack and all other accessories and connectors as per TS. SITC of (B) 30-Volts, Float cum boost battery charger with full wave rectification for 220V, Charging Current 20 A Minimum, 1Phase, 50Hz AC input. as per TS. at R/Stations: Sherpur & Basantpur (Dismanteling of Old and Replacement with New) |
| 14 | SITC of 66KV SF6 Breaker 72.5 kV, 1250 A, 31.5 KA 3-Phase outdoor type circuit breaker alongwith support Structures, Marshalling box terminal connectors, closing and tripping coils 30V DC and required accessories complete as per technical specification scope of work and approved drawings confirmed to IS Standards Note;- at R/Stations: Paharpur & TPK. (Dismanteling of Old and Replacement with New) |
| 15 | SITC of 33KV Vaccum Circuit Breaker designed for 36 KV 1250 Amp, 26.2 KA 3-Phase, control circuit 30V DC out door type circuit breaker along with support structures, marshalling box terminal connectors and required accessories complete as per technical specification, scope of work & approved drawings confirming to IS standards for 1. Bani Line at R/Stn. Basholi 2. Baggan Line at R/Stn. Phinter 3. Macheddi Line at R/Stn. Phinter. (Dismanteling of Old and Replacement with New) |
| 16 | SITC of 66 KV Isolator with Earthing Blade 630 Amp 25 KA,3 Phase, double break, centre rotating plate, G.O insolators alongwith Supports insulators operating mechanism, base channel down pipe and complete required accessories as per scope of works and approved drawings confirmed to IS Standards TPK Line at R/Station: TPK. |
| 17 | SITC of 33KV isolator (with earth Blade) 36KV, 800A, 25 KA, 3-Phase, double break center rotating type Gang operated isolator with support insulator, operating mechanism, base Channel down pipe & all required accessories as per TS, scope of work & approved drawings confirming to IS standards in Mahanpur to Basholi Line near Poonda, Basholi to Bhoond Line near Shara. |
| 18 | SITC of 66KV 1-phase CT, 250-125/5-5-2.89 A 3 core, dual ratio. Core I metering (400/200/5 A, 15 VA, 0.2 accuracy class), core II protection ( 250-125/5A, 15VA,5P10) Current transformer along with junction box (1 No. junction box for 3 No's CTs) Core III Differential (250/125/2.89A PS Class) as per Technical specifications, scope of work & approved drawings) (3 No. CTs in 1 set) at R/Stations: Ghagwal & Nagri. (Dismanteling of Old and Installation with New) |
| 19 | SITC of 33KV,1-phase, 400/200/5-5A CT Multi ratio multi core along with junction box (1 No. junction box for 3 No's CTs) as per Technical specifications, scope of work & approved drawings) (3 No. CTs in 1 set) at R/Station: Hiranagar (Dismanteling of Old and Replacement with New) |
| 20 | SITC of 66 KV Voltage transformer ( 66KV/110 V,2-Core, Outdoor) & all required accessories complete 0.2S Class (3PTs in one set) at R/Station: Ghagwal. (Dismanteling of Old and Installation with New) |
| 21 | SITC of 33KV, 1-Phase, 33/√3KV/110/√3V, Single Core, outdoor type Potential Transformer along with Junction box ( 1no. junction box for 3 no. of 1-phase PTs), bi metallic clamp & required accessoriesetc., complete as per technical specification, scope of work & approved drawings. (3 No. PTs in 1 set) at R/Station: Mahanpur. |
| 22 | SITC of 66KV LA, i.e Gapless Surge arrestor,polymer type, 60 KV, 10 KA, 1-Phase Class 2, Station type lightening arrestor as per IS2629/85 class 2, with mounting platform and surge counter, as per technical specfications. (3 No. LAs in 1 set) at R/Stations: Marheen (1 Set), Paharpur (1 Set), Hiranagar-I (1 Set), Hatlimorh-I (1 Set), Sherpur (1 Set). |
| 23 | SITC of 33KV LA, i.e Gapless Surge arrestor, 30 KV, 10 KA, 1-Phase, Station type lightening arrestor with mounting platform, Station Class ZnO Polymer gapless as per technical specfications (3 No. LAs in 1 set) with individual earthings at R/Stations: Phinter (1 Set), Baggan (1 Set), Mahanpur (1 Set), Kudhetar (1 Set) & Ramkot (1 Set) |
| 24 | SITC of Control & relay panel for 66/11 KV power transformer, Indoor type, SCADA compatible, remote/manual Switch, along with 01 E/F & 03 overcurrent relays and differential relays(IEC61850) voltmeter, ammeter, annunication windows with annuciation relays & other components etc as per approved drawings & Techncal specifications at R/Stations: Keerian, Ghagwal, Hatlimorh-I & Paharpur. (Dismanteling of Old and Installation with New) |
| 25 | SITC of Control & relay panel for 33 KV Baggan Line at R/Station Phinter, Indoor type, SCADA compatible, remote/manual Switch, along with E/F & overcurrent relays, voltmeter, ammeter, energymeter-5A, DLMS compliant with RS-485 port, annunication windows with annuciation relays & other components etc as per approved drawings & Techncal specifications Please Enable Macros to View BoQ information |