| 1 | SUPPLY PART |
| 2 | Supply of single phase, 12 way, doubledoor (IP-43) SPN DB with DP,25A,C-type MCB and DP,25A RCCB with 30mA sensitivity as incomer.The switch board shall accommodate :Incomer - 25A MCB DP(C-curve,10KA) + 25A RCCB DP,30mA sensitivity.Outgoing : 10A SP MCB(C-curve,10KA) - 3 Nos 6A SP MCB(C-curve,10KA) - 3 Nos |
| 3 | Supply of 1.1kV, 3Cx4 Sqmm XLPE armoured Cu cable for establishing power supply to SPN 12 way DB inside security cabin. |
| 4 | Supply of 1.1kV, 3Cx2.5 Sqmm XLPE armoured Cu cable for power supply to light points from DB. |
| 5 | Supply of 1.1kV, 3Cx1.5 Sqmm XLPE armoured Cu cable for power supply to light points from DB. |
| 6 | 1)Supply of Glands & lugs for glanding & termination of the following XLPE Armoured Copper cable. Supply of heavy duty copper lugs, brass cable gland ,earthing of gland etc, complete as per the direction of the engineer in charge. All material required for the work shall be supplied by the contractor. |
| 7 | a) Supply of glands & lugs etc for 1R x 3C x 4sqmm XLPE armoured Copper cable termination. |
| 8 | b) Supply of glands & lugs etc for 1R x 3C x 2.5sqmm XLPE armoured Copper cable termination. |
| 9 | c)Supply of glands & lugs etc for 1R x 3C x 1.5sqmm XLPE armoured Copper cable termination. |
| 10 | 2)Supply of PVC gland for terminating flexible cables from light points(3cx1.5sqmm cable) to JB. |
| 11 | Supply of 2 runs 10SWG bare copper wire for DB earthing. |
| 12 | Supply of 12 SWG bare copper wire for gland earthing. |
| 13 | a)Supply of 16A SP MCB with suitable open type metallic MCB box for the control of light points as per IS standards, specification & drawing. This include supply of all MCB boxes, MCBs, fitting accessories etc.. required for installation. |
| 14 | b)Supply of 6A SP MCB with suitable open type metallic MCB box for the control of light points as per IS standards, specification & drawing. This include supply of all MCB boxes, MCBs, fitting accessories etc.. required for installation. |
| 15 | c)Supply of local control MCB metallic box with changeover switch of 6A rating C- curve (equivalent to Legrant DX3 change over switch Cat No. 412900) for dual control of normal lighting(2 numbers of light) at stair case(Legrant/Havells/BCH) |
| 16 | Supply of 10A Metal clad power socket & Pin (Legrand Cat No 507811) or equivalent with 10A SP MCB metallic enclosure as per IS standards, specification & drawings. |
| 17 | Supply of cabin fan - sweep 300mm(12\\") Power - 75W-85W Capacity : 75/72 CM/M Air delivery Noise level : 40-45db Supply : 230V,50Hz Stndard : IS Make:CG/Bajaj/USHA/Almonard/Havells |
| 18 | Supply of 4 feet/1200mm LED Batten type 18W-20W,90-100Lum/W,140-260VAC,Single phase, 50Hz light fitting for security cabin. |
| 19 | Supply of 4 feet/1200mm Industrial LED Batten type 40W,IP-65 ,140-260VAC,Single phase, 50Hz light fitting for stair case area. |
| 20 | Supply of industrial flood lights fittings complete - for outdoor lighting. Power : 80W Efficiancy : 120Lum/W Supply : 140-260VAC, Single phase, 50HZ IP : 66 THD : 20% Safety Class : I/II, CCT : 5700K, CRI:70 Standard : ISI Make : CG/Bajaj/Philips/Wipro/Havells/Osram |
| 21 | Supply of Junction Boxes metallic 100x100 ,3 way for indoor & outdoor light fixtures of watch tower. |
| 22 | INSTALLATION PART |
| 23 | Installation, testing & commissioning of single phase, 12 way, doubledoor (IP-43) SPN DB with DP,25A,C-type MCB and DP,25A RCCB with 30mA sensitivity as incomer.The switch board shall accommodate :Incomer - 25A MCB DP(C-curve,10KA) + 25A RCCB DP,30mA sensitivity.Outgoing : 10A SP MCB(C-curve,10KA) - 3 Nos 6A SP MCB(C-curve,10KA) - 3 Nos |
| 24 | Laying of 1.1kV, 3Cx4 Sqmm XLPE armoured Cu cable through trenches/walls/steel structures/ceilings using heavy duty nylon cable ties/saddles as per IS standards & specifications. |
| 25 | Laying of 1.1kV, 3Cx2.5 Sqmm XLPE armoured Cu cable through walls/steel structures/ceilings using heavy duty nylon cable ties/saddles as per IS standards & specifications. |
| 26 | Laying of 1.1kV, 3Cx1.5 Sqmm XLPE armoured Cu cable through walls/steel structures/ceilings using heavy duty nylon cable ties/saddles as per IS standards & specifications. |
| 27 | 1)Glanding & termination of the following XLPE Armoured Copper cable using heavy duty copper lugs, brass cable gland ,earthing of gland etc, complete as per the direction of the engineer in charge. The cable gland shall be earthed as per ISS/IER. All material required for the work shall be supplied by the contractor. |
| 28 | a) Installation of glands & lugs etc for 1R x 3C x 4sqmm XLPE armoured Copper cable termination |
| 29 | b) Installation of glands & lugs etc for 1R x 3C x 2.5sqmm XLPE armoured Copper cable termination |
| 30 | c) Installation of glands & lugs etc for 1R x 3C x 1.5sqmm XLPE armoured Copper cable termination |
| 31 | 2) Installation of PVC gland for terminating flexible cables from light points(3cx1.5sqmm cable) to JB. |
| 32 | Laying and installation of 2 runs 10SWG bare copper wire for DB earthing from nearest earth grid available at site to DB inside security cabin of watch tower by clamping trough trenches & steel structure of watch tower. |
| 33 | Laying and installation of 12 SWG bare copper wire for gland earthing. Glands shall be earthed to earth stud of metal boxes,JBs,Dbs etc. where third core(earth) of incoming cables connected. The cable gland shall be earthed as per ISS/IER. |
| 34 | a) Installation of 16A SP MCB with suitable open type metallic MCB box for the control of light points as per IS standards, specification & drawing. MCB's used for control the outdoor flood lights/Search lights shall be placed in surface mount type MCB metal box of suitable size in open condition. Neutral link shall be provided along with MCB metallic boxes for connecting neutral. |
| 35 | b) Installation of 6A SP MCB with suitable open type metallic MCB box for the control of light points as per IS standards, specification & drawing. MCB's used for control the light/fan shall be placed in surface mount type MCB metal box of suitable size in open condition. Neutral link shall be provided along with MCB metallic boxes for connecting neutral. |
| 36 | c) Installation of local control MCB metallic box with changeover switch of 6A rating C- curve (equivalent to Legrant DX3 change over switch Cat No. 412900) for dual control of normal lighting(2 numbers of light) at stair case (Legrant/Havells/BCH) |
| 37 | Installation & wiring of 10A Metal clad power socket & Pin (Legrand Cat No 507811) or equivalent with 10A SP MCB metallic enclosure as per IS standards, specification & drawings. |
| 38 | Installation of cabin fan - sweep 300mm(12\\") Power - 75W-85W Capacity : 75/72 CM/M Air delivery Noise level : 40-45db Supply : 230V,50Hz Stndard : IS Make :CG/Bajaj/USHA/Almonard/Havells |
| 39 | Installation of 4 feet/1200mm LED Batten type 18W-20W,90-100Lum/W,140-260VAC,Single phase, 50Hz light fitting for security cabin. Installation of same on ceiling or wall using clamps/fixtures/JBs etc. including supply of materials, giving connections,testing etc. as per technical specification attached. |
| 40 | Installation of 4 feet/1200mm Industrial LED Batten type 40W,IP-65 ,140-260VAC,Single phase, 50Hz light fitting for stair case area. Installation of same on ceiling or wall using clamps/fixtures/JBs etc. including supply of materials, giving connections,testing etc. as per technical specification attached. |
| 41 | Installation of industrial flood lights fittings complete for outdoor lighting. Power : 80W Efficiancy : 120Lum/W Supply : 140-260VAC, Single phase, 50HZ IP : 66 THD : 20% Safety Class : I/II, CCT : 5700K, CRI:70 Standard : ISI Make : CG/Bajaj/Philips/Wipro/Havells/Osram |
| 42 | Installation of Junction Boxes metallic 100x100 ,3 way for indoor & outdoor lighting fixtures of watch tower. It shall be suitable for loop in, loop out & termination of 3Cx2.5sqmm & 3Cx1.5Sqmm XLPE armoured cu cables. Please Enable Macros to View BoQ information |