| 1 | Supplying of 1.1 kV, XLPE or Heat resistant PVC insulated, PVC exutruted Inner Seath Armoured LTUG Cable as per IS-1554 (Part-1) or IS-7098 Part-1, Armouring strip thickness and resistivity as per IS-3975 |
| 2 | 3.5C x 150 sq.mm Aluminium Conductor |
| 3 | 1Cx95 sq.mm copper flexible Conductor |
| 4 | 1C x 50 sq.mm copper flexible Conductor |
| 5 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 6 | Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 7 | Above 95 sq. mm and upto 185 sq. mm (clamped with25/40x3mm MS flat clamp) |
| 8 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METALpipe as required. |
| 9 | Above 95 sq. mm and upto 185 sq. mm |
| 10 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. |
| 11 | 90 mm dia (OD-90 mm & ID-76 mm nominal) |
| 12 | Removal of interlocking stones, excavation of the surface, backfilling and closing the surface above DWC pipe of 7 mtrs length, followed by proper refixing of interlocking stones to restore the surface to a neat and complete condition. |
| 13 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel with MCCB incomer, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar,common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 14 | 6 way (4 + 24), Double door |
| 15 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"D\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required |
| 16 | 32A DP MCB |
| 17 | 32A TPN MCB |
| 18 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. |
| 19 | 250 A,36KA,FPMCCB |
| 20 | 150 A, 36 KA, FPMCCB |
| 21 | Providing and fixing Metal Enclosure on wall of suitable size for instalation of 250 A MCCB and directions of Engineer-in-Charge |
| 22 | Supplying and making end termination with brass compression gland and Copper/Aluminium lugs for following size of PVC insulated and PVC sheathed / XLPEaluminium conductor cable of 1.1 KV grade as required. |
| 23 | 4 X 50 sq. mm (35mm) for Copper Flexible cable |
| 24 | 4 X 95 sq. mm (38mm) for copper flexible cable |
| 25 | 3½ X 150 sq. mm (50mm) for Armoured aluminium cable |
| 26 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required |
| 27 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt& spring washer spaced at 50mm) |
| 28 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required |
| 29 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required. |
| 30 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & springwasher spaced at 50mm) |
| 31 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 32 | Supply and fixing 50mm X 50mm PVC trunking system along with all required jointing accessories includes internal angle, external angle, body cover, body joint, coupler, end cap on the wall with necessary screws and complete. |
| 33 | Removing the existing casing and capping over a 20-metre length on the wall, and relaying the existing wires through the trunking system on the wall, including all necessary connections, fixing, and making good the surface Please Enable Macros to View BoQ information |