Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | M & L for boring hole under the road / pavement / hard standing with the help of trenchless technology using ultra sound technique and necessary machine including DWC (Double Wall Corrugated) pipe of 100mm dia suitable for 0.4 mpa working pressure not less than one metre below ground level complete all as specified & directed by Engineer-in-charge. |
| 2 | Supply and lay cable XLPE Insulated PVC sheated, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 400 sq mm 3.5 core complete laid in trenches,floors,under roads,through pipe all as specified and directed. |
| 3 | Ditto as per item no. 2, but of size 300 sq mm 3.5 core |
| 4 | Ditto as per item no. 2, but of size 240 sq mm 3.5 core |
| 5 | Ditto as per item no. 2, but of size 185 sq mm 3.5 core |
| 6 | Ditto as per item no. 2, but of size 150 sq mm 3.5 core |
| 7 | Ditto as per item no. 2, but of size 120 sq mm 3.5 core |
| 8 | Ditto as per item no. 2, but of size 95 sq mm 3.5 core |
| 9 | Ditto as per item no. 2, but of size 70 sq mm 3.5 core |
| 10 | Ditto as per item no. 2, but of size 50 sq mm 3.5 core |
| 11 | Ditto as per item no. 2, but of size 35 sq mm 3.5 core |
| 12 | Ditto as per item no. 2, but of size 25 sq mm 3.5 core |
| 13 | Ditto as per item no. 2, but of size 16 sq mm 4 core |
| 14 | Ditto as per item no. 2, but of size 10 sq mm 4 core |
| 15 | Ditto as per item no. 2, but of size 10 sq mm 2 core |
| 16 | Ditto as per item no. 2, but of size 6 sq mm 2 core |
| 17 | M&L steel conduit pipe 20 mm dia exclusive of boxes(junction/terminal) buti inclusive of all tees ,bends , elbows, reducers ,bell mouth tubs, ends and fixing , all accessories such as couplers, lock nuts, saddles, pipe hooks etc,fixed along pole all as specified and directed by Engr-in-Charge. |
| 18 | Supply & Fixing of PVC insulated three core wire stranded aluminium conductor 1100 Volt grade of size 1.0 Sqmm drawing through steel conduit for connection purpose complete all as specified and directed by the Engr-in-Charge.Note:Conduit shall be measured and paid separately. |
| 19 | Material and labour for earthing complete for LT Poles,LT panels with galvanised steel earth plate electrode 60cmx60cmx6mm thick buried directly in ground vertically at a depth not less than 2.25 metres below normal ground level with top edge of the plate at a depth not less than 1.5 metres below normal ground level, connected with and including GI wire 4 mm in and including GI pipe 15mm bore light grade as protection pipe (from top of earth plate up to the test point) by means of GI bolts, nuts, check nuts and washers of GI and thimbles, earth plate surrounded by packed layers of charcoal dust and common salt 15cm thick, all around including top and bottom and watering pipe 20mm bore of GI pipe light grade with funnel and wire mesh, PCC chamber of size 300x300x300mm(top of chamber minimum 15 cm above the normal ground level (1:3:6) using 20mm graded stone aggregate and RCC cover (1:2:4) type B-I using 20mm graded crushed stone aggregate of 25mm thick with 2 nos MS handles of 12mm dia including necessary excavation/ earth work in any type of soil/rock and as shown in Electrical plate No. 3 of SSR Part-I (2009) testing on completion complete all as specified.( Per 10 pole for 137 pole) |
| 20 | Material and labour for earthing complete for LT Panels with galvanised steel earth plate electrode 60cmx60cmx6mm thick buried directly in ground vertically at a depth not less than 2.25 metres below normal ground level, from top of earth plate up to the test point with top edge of the plate at a depth not less than 1.5 metres below normal ground level, connected with and including GI Strip 32X6 mm in and including GI pipe 40mm bore medium grade as protection pipe by means of GI bolts, nuts, check nuts and washers of GI and thimbles, earth plate surrounded by packed layers of 15 cms thick charcoal dust and common salt 15cm thick, all around including top and bottom and watering pipe 20mm dia bore of GI pipe light grade with funnel and wire mesh, PCC (1:3:6) chamber of size 300x300x300mm (top of chamber minimum 15 cm above the normal ground level using 20mm graded stone aggregate and RCC cover (1:2:4) type B-I using 20mm graded crushed stone aggregate of 40 mm thick with 2 nos MS handles of 12mm dia of size 300mm x 300 mm in angle iron frame of size 40mm x 40mm x 6mm thick including necessary excavation/ earth work in any type of soil all as shown in Electrical plate No. 3 of SSR Part-I (2009) testing on completion complete all as specified.(for panel details attached)).If result is not found below 3 ohm, then contractor will do 2nd earthing on his own cost. |
| 21 | Material and labour for earthing complete for LT Panels with galvanised steel earth plate electrode 60cmx60cmx6mm thick buried directly in ground vertically at a depth not less than 2.25 metres below normal ground level, from top of earth plate up to the test point with top edge of the plate at a depth not less than 1.5 metres below normal ground level, connected with and including GI Strip 25x4mm in and including GI pipe 40mm bore medium grade as protection pipe by means of GI bolts, nuts, check nuts and washers of GI and thimbles, earth plate surrounded by packed layers of 15 cms thick charcoal dust and common salt 15cm thick, all around including top and bottom and watering pipe 20mm dia bore of GI pipe light grade with funnel and wire mesh, PCC (1:3:6) chamber of size 300x300x300mm (top of chamber minimum 15 cm above the normal ground level using 20mm graded stone aggregate and RCC cover (1:2:4) type B-I using 20mm graded crushed stone aggregate of 40 mm thick with 2 nos MS handles of 12mm dia of size 300mm x 300 mm in angle iron frame of size 40mm x 40mm x 6mm thick including necessary excavation/ earth work in any type of soil all as shown in Electrical plate No. 3 of SSR Part-I (2009) testing on completion complete all as specified.(for panel details attached)).If result is not found below 3 ohm, then contractor will do 2nd earthing on his own cost. |
| 22 | Supply and fix GI pipe 40 mm bore light grade for protection of cable including provn of MS flat bends/clamps complete for fixing along GI pipe along wall/ pole/laid under the road/ floor complete all as specified and directred by Engr-in-Charge. |
| 23 | Supply & Fix single piece moulded SMC junction box of min. size 230 x 170 x 105 mm outer dimension consisting of one SP MCB 6 Amps & one 4 way connector, including all necessary fixing arrangemets for fixing to LT Pole ie necessary Clamps, nut, bolts & Washers of suitable size including dismantling old unserviceable complete all as specified and as directed. |
| 24 | Dsimantling of old Pole for disposes off or resuse comple all as specified and directed. |
| 25 | Taking down cross arms, channels, angle iron, clamps, nut, bolts, stay wire, stay assembly, GI wire, anti climbing devices, danger notice boards etc complete all as speicified and directed by Engineer-in-Charge. |
| 26 | Dismantling insulators any type, any size from existing LT poles street light feeders complete. |
| 27 | Dismantling of old ACSR or AAC conductors from existing street light feeders or LT feeder supply by opening binding wire complete including removing connection services cable complete. |
| 28 | Taken out old LT cable off any sizes for resue and disposed off complete all as specified and directed.Note GE will detail a BOO before comencement of work to ascertain qty of serviceable and UNSV cable,UNSV cable will be issued to contractor as per Sch of credit.Serviceable cable shall be utilized by deptt as per procedure. |
| 29 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly powder coated with seven tank process internally and externally supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- (Main Panel ) :-(Puran road) |
| 30 | (i) Bus bar strip,four pole and capacity 1000 Amps aluminium bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleeves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 31 | (ii) INCOMING : - |
| 32 | (a)S & F ACB 630 A pole, 35 kA with Adjustable thermal Adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 33 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Kwh,volts and amps duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 34 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 35 | (iii) OUTGOING:- |
| 36 | (a) MCCB 350Amps, 4 pole, 35 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links and required nut, bolts or other fixing accessories complete. -01 Nos. |
| 37 | (b) MCCB 160Amps, 4 pole, 25 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links and required nut, bolts or other fixing accessories complete. -02 Nos. |
| 38 | (c) MCCB 125Amps, 4 pole, 25 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links and required nut, bolts or other fixing accessories complete. -01 Nos. |
| 39 | (d) MCCB 32 Amps, 4 pole, 16 kA with , Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links and required nut, bolts or other fixing accessories complete. -04 Nos. |
| 40 | (e) MCB TPN 32Amp, 415 V, 10 KA- 01 Nos |
| 41 | (f) 3 phase astronomical timer with contactor 3P 32 Amp and suitable MCB & connection to override timer for manual ON/OFF of lights- 01 Nos |
| 42 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside of panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & powder coated with seven tank process internally and externally supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- (LT Panel 1) :-(Puran road) |
| 43 | (i) Bus bar strip,four pole and capacity 250 Amps aluminium bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleeves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 44 | (ii) INCOMING : - |
| 45 | (a) MCCB160A, 4 pole, 25 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 46 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,volt,amp,Kwh duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 47 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 48 | (iii) OUTGOING:- |
| 49 | (a) MCCB 32 Amps, 4 pole,16 kA with , Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -08Nos. |
| 50 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & dulypowder coated with seven tank process internally and externally supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- (LTPanel 3:-(Puran road) |
| 51 | (i) Bus bar strip,four pole and capacity 500 Amps aluminium bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleeves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 52 | (ii) INCOMING : - |
| 53 | (a) MCCB 350 A, 4 pole, 35 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 54 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,KWh,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 55 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 56 | (iii) OUTGOING:- |
| 57 | (a) MCCB 200Amps, 4 pole,25kA with Adjustable thermal adj magnetic release, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -01 Nos. |
| 58 | (b)MCCB 63 Amps, 4 pole,16 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links other fixing accessories complete. -01 Nos. |
| 59 | (c)MCCB 32 Amps, 4 pole,16 kA with , Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links other fixing accessories complete. -01 Nos. |
| 60 | (d) MCB SPN 40Amp, 415 V, 10 KA- 01 Nos |
| 61 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly powder coated with seven tank process internally and externally supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- (LTPanel 4 ) :-(Puran road) |
| 62 | (i) Bus bar strip,four pole and capacity 200 Amps aluminium bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleeves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 63 | (ii) INCOMING : - |
| 64 | (a) MCCB 125A, 4 pole, 25 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 65 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,KWh,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 66 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 67 | (iii) OUTGOING:- |
| 68 | (a) MCCB 32Amps, 4 pole,16 kA with, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -06 Nos. |
| 69 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly powder coated with seven tank process internally and externally supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- FP I PURAN ROAD |
| 70 | (i) Bus bar strip,four pole and capacity 150 Amps Al bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 71 | (ii) INCOMING : - |
| 72 | (a) MCCB 100A, 4 pole, 16 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 73 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Kwh,Voltmeter,Ammeter, duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 74 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 75 | (iii) OUTGOING:- |
| 76 | (a) MCCB 32Amps, 4 pole,16 kA with , Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -02 Nos. |
| 77 | (b) MCB SPN 40Amp, 415 V, 10 KA- 03 Nos |
| 78 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly powder coated with seven tank process internally and externally supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- FP-II PURAN ROAD |
| 79 | (i) Bus bar strip,four pole and capacity 300 Amps aluminium bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 80 | (ii) INCOMING : - |
| 81 | (a) MCCB 200A, 4 pole, 25 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 82 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 83 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 84 | (iii)OUTGOING:- |
| 85 | (a) MCCB 32Amps, 4 pole,16 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -08 Nos. |
| 86 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly spray painted with seven tank process internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- (Main Panel ) :-(Brig House)o old Bhim Road. |
| 87 | (i) Bus bar strip,four pole and capacity 200 Amps Al bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 88 | (ii) INCOMING : - |
| 89 | (a) MCCB 125A, 4 pole, 25 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 90 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 91 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 92 | (iii) OUTGOING:- |
| 93 | (a) MCCB 63 Amps, 4 pole,16 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -01Nos. |
| 94 | (b)MCCB 32/40 Amps, 4 pole,16 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links other fixing accessories complete. -04 Nos. |
| 95 | (c) MCB TPN 32Amp, 415 V, 10 KA- 01 Nos |
| 96 | (d) 3 phase astronomical timer with contactor and suitable MCB and connection to override timer for switching lights ON/OFF manually- 01 Nos |
| 97 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly powder coated with seven tank process internally and externally supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- (FP-I ) :-(Brig House ) old Bhim Road |
| 98 | (i) Bus bar strip,four pole and capacity 100 Amps aluminium bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 99 | (ii) INCOMING : - |
| 100 | (a)S & F for in replacement MCCB 63A, 4 pole, 16 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 101 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 102 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 103 | (iii) OUTGOING:- |
| 104 | (a) MCCB 32 Amps, 4 pole,16 kA with , Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -03 Nos. |
| 105 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly powder coated with seven tank process internally and externally supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- (LT Panel 1) :-(Col Bunglow Nalwa road ) |
| 106 | (i) Bus bar strip,four pole and capacity 300 Amps Al bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 107 | (ii) INCOMING : - |
| 108 | (a)S & F for in replacement MCCB 160A, 4 pole, 25 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 109 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 110 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 111 | (iii) OUTGOING:- |
| 112 | (a) MCCB 63 Amps, 4 pole,16 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -02Nos. |
| 113 | (b) MCCB 32 Amps, 4 pole,16 kA with , Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -05Nos. |
| 114 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly powder coated with seven tank process internally and externally supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- (FP1 Panel ) Col Bunglow Nalwa Road |
| 115 | (i) Bus bar strip,four pole and capacity 150 Amps Al bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 116 | (ii) INCOMING : - |
| 117 | (a)S & F for in replacement MCCB 63A, 4 pole, 16 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 118 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 119 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 120 | (iii) OUTGOING:- |
| 121 | (a) MCCB 32 Amps, 4 pole,16 kA with , Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -04 Nos. |
| 122 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly powder coated with seven tank process internally and externally supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- (FP3 Panel ) Col Bunglow Nalwa Road |
| 123 | (i) Bus bar strip,four pole and capacity 150 Amps aluminium bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 124 | (ii) INCOMING : - |
| 125 | (a)S & F for in replacement MCCB 63A, 4 pole, 16 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 126 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 127 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 128 | (iii) OUTGOING:- |
| 129 | (a) MCCB 32 Amps, 4 pole,16 kA with , Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -02 Nos. |
| 130 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly powder coated with seven tank process internally and externally supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories:-Main LT panel 401 Fd Hospital |
| 131 | (i) Bus bar strip,four pole and capacity 600 Amps aluminium strip of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 132 | (ii) INCOMING : - |
| 133 | (a) MCCB 4P 400 Amps, Adj. thermal adj magnetic type,415 V, 3 phase, 50 Hz, 4 pole, 36KA with ICS=100% ICU - 01 No |
| 134 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Voltmeter,Ammeter, duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 135 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 136 | (iii) OUTGOING:- |
| 137 | (a) MCCB TPN 160Amp- 01 Nos with Adj. thermal adj magnetic type,415 V, 3 phase, 50 Hz, 4 pole, 25KA with ICS=100% ICU |
| 138 | (b) MCCB TPN 125Amp- 01Nos with Adj. thermal adj magnetic type,415 V, 3 phase, 50 Hz, 4 pole, 25KA with ICS=100% ICU |
| 139 | (c) MCCB TPN 63Amp- 02 Nos with Adj. thermal adj magnetic type,415 V, 3 phase, 50 Hz, 4 pole, 16KA with ICS=100% ICU |
| 140 | (d) MCCB TPN 32Amp, 415 V, 16 KA- 02 Nos with Adj. thermal magnetic type,415 V, 3 phase, 50 Hz, 4 pole with ICS=100% ICU |
| 141 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly spray painted with seven tank process internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- LT Panel 1 401 Fd hospital |
| 142 | (i) Bus bar strip,four pole and capacity 250 Amps aluminium bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 143 | (ii) INCOMING : - |
| 144 | (a)S & F for in replacement MCCB 160 A, 4 pole, 25 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 145 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 146 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 147 | (iii) OUTGOING:- |
| 148 | (a)MCCB 63 Amps, 4 pole,16 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -02 Nos. |
| 149 | (b)MCCB 32 Amps, 4 pole,16 kA with Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -01 Nos. |
| 150 | (c) MCB TPN 32 A 10 kA -01 No. |
| 151 | (d)3 phase astronomical timer with contactor 3P 32 Amp and suitable MCB & connection to override timer for manual ON/OFF of lights- 01 Nos |
| 152 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly powder coated with seven tank process internally and externally supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- LT Panel 2 Fd Hospital |
| 153 | (i) Bus bar strip,four pole and capacity 200 Amps aluminium bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 154 | (ii) INCOMING : - |
| 155 | (a)S & F MCCB 125 A, 4 pole, 25 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 156 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 157 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 158 | (iii) OUTGOING:- |
| 159 | (a) MCCB 32 Amps, 4 pole,16 kA with Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -04 Nos. |
| 160 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly powder coated with seven tank process internally and externally supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :-FP1 Fd Hospital |
| 161 | (i) Bus bar strip,four pole and capacity 100 Amps aluminium bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 162 | (ii) INCOMING : - |
| 163 | (a)S & F for in replacement MCCB 32 A, 4 pole, 16 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 164 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 165 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 166 | (iii) OUTGOING:- |
| 167 | (a) MCB TPN 32 Amps, 4 pole,10 kA fixing accessories complete. -01 Nos. |
| 168 | (b) MCB SPN 32/40 Amps, 4 pole,10 kA fixing accessories complete. -02 Nos. |
| 169 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly powder coated with seven tank process internally and externally supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- LT PANEL Engr Regiment |
| 170 | (i) Bus bar strip,four pole and capacity 600 Amps aluminium bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 171 | (ii) INCOMING : - |
| 172 | (a)S & F MCCB 350 A, 4 pole, 36 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 173 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 174 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 175 | (iii) OUTGOING:- |
| 176 | (a) MCCB 125Amps, 4 pole,25 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -02Nos. |
| 177 | (b) MCCB 63 Amps, 4 pole,16 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -02 Nos. |
| 178 | (c) MCCB 32 Amps, 4 pole,16 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -01 Nos. |
| 179 | (c) MCB TPN 32 Amps, 4 pole,16 kA fixing accessories complete. -01 Nos. |
| 180 | (d) 3 phase astronomical timer with contactor 3P 32 Amp and suitable MCB & connection to override timer for manual ON/OFF of lights- 01 Nos |
| 181 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly powder coated with seven tank process internally and externally supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- LT PANEL Adm Block |
| 182 | (i) Bus bar strip,four pole and capacity 250 Amps aluminium bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 183 | (ii) INCOMING : - |
| 184 | (a)S & F MCCB 125 A, 4 pole, 25 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 185 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 186 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 187 | (iii) OUTGOING:- |
| 188 | (a) MCCB 63Amps, 4 pole,16 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -02Nos. |
| 189 | (b) MCB TPN 32 Amps, 4 pole,16 kA fixing accessories complete. -02Nos. |
| 190 | (c) MCB SPN 32/40 Amps, 4 pole,10 kA fixing accessories complete. -01 Nos. |
| 191 | (d) 3 phase astronomical timer with contactor 3P 32 Amp and suitable MCB & connection to override timer for manual ON/OFF of lights- 01 Nos |
| 192 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly powder coated with seven tank process internally and externally supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- LT PANEL II OR LINE |
| 193 | (i) Bus bar strip,four pole and capacity 200 Amps aluminium bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 194 | (ii) INCOMING : - |
| 195 | (a)S & F MCCB 125 A, 4 pole, 25 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 196 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 197 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 198 | (iii) OUTGOING:- |
| 199 | (a)MCCB 32Amps, 4 pole,16 kA with , Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -04Nos. |
| 200 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly powder coated with seven tank process internally and externally supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- LT Panel offrs mess |
| 201 | (i) Bus bar strip,four pole and capacity 200 Amps aluminium bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 202 | (ii) INCOMING : - |
| 203 | (a)S & F MCCB 63 A, 4 pole, 16 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 204 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 205 | (c)Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 206 | (iii) OUTGOING:- |
| 207 | (a) MCCB 63Amps, 4 pole,16 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -02Nos. |
| 208 | (b)MCB 32Amps,TPN,16 kA with , Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -01Nos. |
| 209 | (c)MCB SPN 40 A 10 KA-01 No. |
| 210 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly powder coated with seven tank process internally and externally supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- MAIN LT PANEL NALWA ROAD COLONY |
| 211 | (i) Bus bar strip,four pole and capacity 600 Amps aluminium bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 212 | (ii) INCOMING : - |
| 213 | (a)S & F MCCB 400 A, 4 pole, 36 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 214 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 215 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 216 | (iii) OUTGOING:- |
| 217 | (a) MCCB 250 Amps, 4 pole,36 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -01Nos. |
| 218 | (b) MCCB 160Amps, TPN,25 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -02Nos. |
| 219 | (c) MCB 32Amps, TPN,10 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -01Nos. |
| 220 | (d) contactor 3P 32 A . -01Nos. |
| 221 | (e)3 phase astronomical timer with contactor 3P 32 Amp and suitable MCB & connection to override timer for manual ON/OFF of lights- 01 Nos |
| 222 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly powder coated with seven tank process internally and externally supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- LT PANEL II |
| 223 | (i) Bus bar strip,four pole and capacity 400 Amps aluminium bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 224 | (ii) INCOMING : - |
| 225 | (a)S & F MCCB 250 A, 4 pole, 35 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 226 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 227 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 228 | (iii) OUTGOING:- |
| 229 | (a) MCCB 160 Amps, 4 pole,25 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -01Nos. |
| 230 | (b) MCCB 100Amps, TPN,16 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -01Nos. |
| 231 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly powder coated with seven tank process internally and externally supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- LT PANEL III |
| 232 | (i) Bus bar strip,four pole and capacity 250 Amps aluminium bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 233 | (ii) INCOMING : - |
| 234 | (a)S & F MCCB 160 A, 4 pole, 25 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 235 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 236 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 237 | (iii) OUTGOING:- |
| 238 | (a) MCCB 32 Amps, 4 pole,16 kA with , Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -06Nos. |
| 239 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly spray painted with seven tank process internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- FP I |
| 240 | (i) Bus bar strip,four pole and capacity 200 Amps aluminium bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 241 | (ii) INCOMING : - |
| 242 | (a)S & F for in replacement MCCB 160 A, 4 pole, 25 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 243 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 244 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 245 | (iii) OUTGOING:- |
| 246 | (a) MCCB 32 Amps, 4 pole,16 kA with , Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -06Nos. |
| 247 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly spray painted with seven tank process internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- FP-II |
| 248 | (i) Bus bar strip,four pole and capacity 250 Amps aluminium bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 249 | (ii) INCOMING : - |
| 250 | (a)S & F MCCB 160A, 4 pole, 25 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 251 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 252 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 253 | (iii) OUTGOING:- |
| 254 | (a) MCCB 32 Amps, 4 pole,16 kA with , Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -06Nos. |
| 255 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly powder coated with seven tank process internally and externally supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- FP-III |
| 256 | (i) Bus bar strip,four pole and capacity 200 Amps aluminium bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 257 | (ii) INCOMING : - |
| 258 | (a)S & F MCCB 100 A, 4 pole, 16 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 259 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 260 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 261 | (iii) OUTGOING:- |
| 262 | (a) MCCB 32 Amps, 4 pole,16 kA with , Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -04Nos. |
| 263 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly powder coated with seven tank process internally and externally supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- (Main Panel ) STP road Plassey line |
| 264 | (i) Bus bar strip,four pole and capacity 1000 Amps aluminium bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 265 | (ii) INCOMING : - |
| 266 | (a)S & F ACB 630A, 4 pole, 35 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 267 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 268 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 269 | (iii) OUTGOING:- |
| 270 | (a) MCCB 200 Amps, 4 pole,25 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -02 Nos. |
| 271 | (b) MCCB 160 Amps, 4 pole,25 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -02 Nos. |
| 272 | (c) MCCB 125 Amps, 4 pole,25 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -01 Nos. |
| 273 | (d) MCCB 63 Amps, 4 pole,16 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -01 Nos. |
| 274 | (e) MCCB 32 Amps, 4 pole, 16 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links and required nut, bolts or other fixing accessories complete. -01 Nos. |
| 275 | (f) MCB TPN 32Amp, 415 V, 10 KA- 01 Nos |
| 276 | (g) 3 phase astronomical timer with contactor 3P 32 Amp and suitable MCB & connection to override timer for manual ON/OFF of lights- 01 Nos |
| 277 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly powder coated with seven tank process internally and externallysupported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- (LT Panel 1 ) STP ASSEY LINE |
| 278 | (i) Bus bar strip,four pole and capacity 250 Amps aluminium bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 279 | (ii) INCOMING : - |
| 280 | (a)S & F MCCB 160A, 4 pole, 25 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 281 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 282 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 283 | (iii) OUTGOING:- |
| 284 | (a) MCCB 32 Amps, 4 pole,16 kA with , Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -04 Nos. |
| 285 | (c)3 phase astronomical timer with contactor 3P 32 Amp and suitable MCB & connection to override timer for manual ON/OFF of lights- 01 Nos |
| 286 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly powder coated with seven tank process internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- (LT Panel 2 ) STP ASSEY LINE |
| 287 | (i) Bus bar strip,four pole and capacity 400 Amps aluminium bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 288 | (ii) INCOMING : - |
| 289 | (a)S & F MCCB 200 A, 4 pole, 25 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 290 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 291 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 292 | (iii) OUTGOING:- |
| 293 | (a) MCCB 32 Amps, 4 pole,16 kA with , Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -08 Nos. |
| 294 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly powder coated with seven tank process internally and externally supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- (LT panel 3) STP ASSEY LINE |
| 295 | (i) Bus bar strip,four pole and capacity 250 Amps aluminium bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 296 | (ii) INCOMING : - |
| 297 | (a)S & F MCCB 160A, 4 pole, 25 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 298 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 299 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 300 | (iii) OUTGOING:- |
| 301 | (a) MCCB 32 Amps, 4 pole,16 kA with, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -06 Nos. |
| 302 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly powder coated with seven tank process internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- (FP II) STP ASSEY LINE |
| 303 | (i) Bus bar strip,four pole and capacity 250 Amps aluminium bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 304 | (ii) INCOMING : - |
| 305 | (a)S & F MCCB 160A, 4 pole, 25 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 306 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 307 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 308 | (iii) OUTGOING:- |
| 309 | (a) MCCB 32 Amps, 4 pole,16 kA with , Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -04 Nos. |
| 310 | (b) MCB SPN 32 Amps,10 KA -01 Nos. |
| 311 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly powder coated with seven tank process internally and externally supported on 04 legs of 1000mm long, 400mm grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 600 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connections incoming / out going complete all as directed by Engineer-in-charge. comprising of following accessories :- (FP IV religious ) STP ASSEY LINE |
| 312 | (i) Bus bar strip,four pole and capacity 150 Amps aluminium bus bar of suitable size based on 1.0 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc |
| 313 | (ii) INCOMING : - |
| 314 | (a)S & F MCCB 63A, 4 pole, 16 kA with Adjustable thermal adj magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader links complete. -01 No. |
| 315 | (b) Multifunction meter with LCD display, accuracy class 1.0, having parameters KW, KVA, KVAh & PF,Voltmeter,Ammeter duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. |
| 316 | (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set |
| 317 | (iii) OUTGOING:- |
| 318 | (a) MCCB 32 Amps, 4 pole,16 kA with , Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader links fixing accessories complete. -04 Nos. |
| 319 | (b) Indicator with neon lamps for RYB , 3 Phase |
| 320 | (c) MCB SPN 40A-01 No. |
| 321 | Note:SI no.29 to 59 i) All LT panel front and rear door shall have steel sliding bolt |
| 322 | ii) Alll MCCB shall be provided with phase extendeds ,copper link phase separator,phase barrier,suitable point for earthing connection,danger plate front and rear shall be marked on LT panel. |
| 323 | Taking down old LT UNSV panel completely all as specified and directed. |
| 324 | Excavation in trenches in soft/loose soil not exceeding 1.50 mtr wide and not exceeding 1.50 mtr in depth for laying of cables and getting out complete all as specified and directed by Engineer-in-Charge. |
| 325 | Returning, filling in,soft/loose soil, including spreading, leveling watering and well ramming in layers not exceeding 25 cms thick each layer compete all as specified and directed by Engineer-in-Charge. |
| 326 | Removal of surplus soft/loose soil soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed by Engr-in-charge. |
| 327 | M & L for sand cushioning with clean dry sand to cables with layer of sand 8 cm before laying of cable and 15 cm thick after laying of cable complete all as specified.Note : For payment purpose punned thickness of 18 cm shall be measured against spread thickness of 23 cm as mentioned in para 19.75 of SSR part-I. |
| 328 | Supply & laying old size sub class 'B' bricks laid flat in trenches over the cable with the length of brick perpendicular to the direction of cable length, adjacent/abutting each other complete all as specified and directed by Engineer-in-charge. |
| 329 | Supply and fix GI pipe 80 mm bore light grade for protection of cable including provn of PVC heavy duty bends complete for fixing along GI pipe along wall/ pole/laid under the road/ floor complete all as specified and directred by Engr-in-Charge. |
| 330 | Supply and fix GI pipe 50 mm bore light grade for protection of cable including provn of PVC heavy duty bends complete for fixing along GI pipe along wall/ pole/laid under the road/ floor complete all as specified and directred by Engr-in-Charge. |
| 331 | Supply and fixing LT cable route indicator for LT cables , made with PCC (1:2:4) type B-1 in rectangular shape of size 30 cm x 10 cm and long 90 cm duly grouted in ground with PCC 1:3:6 type B-2 upto 30 cm and painted in white colour for LT cables and engraved \\"LT CABLE/LT JOINTS\\" in capital alphabets not less than 150mm in height complete all as directed by Engineer-in-Charge |
| 332 | Supply & fix suitable size channel of required length to support LT cables/GI Pipe in culvert or at any other location as required at site, fixing through suitable size of rack bolt. Note : Unexposed surface shall be given one coat of primer only. Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail