| 1 | WORK NAME |
| 2 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 185.0 Sq. mm 3.5 Core |
| 3 | Supply and fixing of 11 KV Outdoor 4 way feeder pillar Box confirming to Discom specifications and made of 3.15 mm thick powder coated CRCA sheet enclosure confirming to IS 14772/IEC 60670 (1989) of Size 1000 mm x 1000 mm x 1500 mm, Both front and rear doors should have 3 heavy duty M.S. hinges with Brass pin inserted inside and locking arrangements.The bottom foundation frame stand should be made from 65x65x6mm MS Angle with four legs of 200mm height provided with 150x150x6mm flats grouted with C.C. of M-10 grade to achieve the height of 2.0 feet above the road level suitable for four outgoing. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR |
| 4 | Plate Earthing as per IS:3043 with copper Earth plate of purity >95% of size 600mm x 600mm x 3.0mm by embodying 3 mtr. below the ground level with 20 mm dia. G.I. 'B' class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required & must record by engineer in-charge during site visit and ensure to enter in measurment book. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 5 | Pipe Earthing as per IS:3043- 1987 with 3.0 Mtr. Long, 40 mm dia. ' B ' class G.I. Pipe IS: 1239 (Part-1) 2004, Equivalent to BS : 1387 with perforated holes of 12 mm dia ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required & must record by engineer in-charge during site visit and ensure to enter in measurment book.All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 6 | Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . 25mm x 3mm copper strip |
| 7 | Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection with GI/Cu purity purity >95% thimble etc. as required. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR .8 SWG G.I. ( Hot Dipped ) Wire |
| 8 | Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulator with standard short circuit withstand capacity , high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . Electrolytic grade Aluminium bus bar 6010 grade |
| 9 | Electrolytic grade (Cu-ETP) Tin Coated annealed copper bus bars IACS 100% grade |
| 10 | P & Fixing Powder coated CRCA sheet enclosures on existing angle iron frame by means of nuts and bolts and making holes , Din rail etc. as required.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 1.6 mm thick |
| 11 | Providing & Laying XLPE insulated three core Armoured Aluminium cable for working voltage 11 K.V.(E) confirming IS :7098 P - 2 with H4- Grade electrolytic aluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810 All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR 3 core 300.0 Sq.mm |
| 12 | SITC of 11kV 630 Amps 21KA for 3 Sec. SF6 insulated, outdoor duty (IP54) , Extensible / Non extensible type Ring main unit (RMU) manually operated in combination of VCB modules and Load Break switch consisting of Copper busbar in SF6 insulated 304 (Non Ferrite Non-Magnetic Grade) stainless steel enclosure of thickness 2.5mm with manometer. The HV switchgear and control gear should be confirming to IEC-62271-100, IEC-62271-200-2003 & IEC-60694-1996. The RMU should be internal arc tested for 21KA for 1Second with IAC-AFL classification for gas tank. Vacum Interrupter of VCB should be RMU Manufacturer’s own make. Each feeder of RMU should have voltage presence indicator and compring of followings:- 1 no. microprocessor based Self powered numerical relay with over Current/ earth fault & short circuit protection with each VCB feeder. - 3 Nos. Protection CT shall be of Burden 2.5VA, ratio 50/1A, Class of Accuracy class 5P10 for O/C and E/F protection for each VCB.- 1 No. Manometer for each tank,- 1 nos. Fault Passage indicator,-Right angle boots for all the feeder Modules All the type test certificates as per IEC from Third party NABL / CPRI / ERDA accrediated lab to be submitted. (Cost of RCC Foundation / Steel Structure to be paid Extra) All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR Extensible 3 way RMU with 1 no. VCB & 2 No. Load Break Switch |
| 13 | 150 mm DN/ID HDPE DWC (External Annular Corrugated and smooth internal walls) SN-8 as per IS 16098 part 2 |
| 14 | Dismantling of existing LT/HTelectric lines including poles/towers, ACSR conductors, guard wires, stay wire, insulators and other electrical items of the pole coming along the alignment of the road or in the plant premises and removal and transportation as well as disposal of all the items as per the direction of engineer incharge.(Serviceable material or can-dum material.) Dismantling of 11KV Lattice Tower with all accessoriesbrackets, tophamper, chakri, V-Cross arms guard bracket, stay, insulators (pin /disc) etc. |
| 15 | Dismantling of 11KVRail/cement Pole /joist/(RSJ - 9 or 10 mtr height with earth wire and brackets, tophamper, chakri, V-Cross arms guard bracket, stay, insulators (pin /disc) etc |
| 16 | Dismantling and rerolling of 11KV conductor any type |
| 17 | Dismantling and rerolling of LT conductor any type |
| 18 | Dismantling and rerolling of earth conductor any type |
| 19 | Dismantling of the Double Pole structure with mounted transformers, distribution boards G.O, D.O, street light panel, stays, earthing wire pipe, cabling,etc & installing the same transformer on the structure newly erected along with distribution board along with erection, testing and commissioning |
| 20 | Dismantling and reinstallation of 11KV Feeder pillar box any type |
| 21 | Dismantling of Telephone pole (Tubular Type). |
| 22 | Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kit suitable for 11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 which covered all sequence for table 2 for termination kit and table 3 for streight through joint inclusive thermal & dynamic short circuit test, humidity test, soil fog test. Cross linking shall be done out side factory with E- beam/ peroxide technology. Extrusion process shall be in house OEM within same vicinity. including testing etc. as required of following sizes. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . 11 KV End Termination Kit Outdoor type 3 core 240/300 Sq.mm |
| 23 | 11 KV Straight Through Joint Kit 3 core 240/300 Sq.mm |
| 24 | 11 KV End Termination Kit Indoor type 3 core 240/300 Sq.mm |
| 25 | Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as required complete in all respect. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR |
| 26 | Supply & Laying following size' B ' class , G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with accessories like bend, socket etc. for laying earth conductor/ strip / cable in ground/ surface/ recess as required. All as per pre approved by Engineer in-charge. (Earth Excavation will be Paid Extra)All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annex ure \\"A\\" attached with this BSR . 150 mm dia |
| 27 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. 6.0 Sq. mm. 4 Core |
| 28 | Add Extra for Laying of one number XLPE power cable of 11/33 KV (Earthed) voltage grade direct in ground including excavation of trench of size 120 cm (Depth) x 35 cm(Width) , with procedure as per following points:- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay the cable in the middle of the trench, (c) Provide river sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth |
| 29 | Add Extra in Item no.62.3 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same |
| 30 | Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 1 x 16.0 sq.mm |
| 31 | P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class 750 N, Externally corrugated and having smooth surface inside with HDPE Coupler, Elbow, Tee at required Depth below the ground for laying cable of following Nominal Outer dia. MFR Test report from NABL accrediated is to be submitted.(Excavation of Earth & Back filling with compaction is to be Paid Extra)All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR. 63 mm |
| 32 | 90 mm |
| 33 | Dismantling of existing structures like culverts, bridges, retaining walls, CC road and other structure comprising of masonry, cement concrete, wood work, steel work, including T&P and scaffolding wherever necessary, sorting the dismantled material, disposal of unserviceable material and stacking the serviceable material with all lifts and lead of 50 metres as directed by Engineer. Cement Concrete Grade M-15 and above and PCC blocks |
| 34 | Providing and laying in position specified grade of reinforced cement concrete excluding the cost of centring, shuttering, finishing and reinforcement - All work upto plinth level :1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) |
| 35 | Supplying and making end termination with heavy aluminium lugs ( Pin / ring type ) confirming to IS 8309 -1993 & IS 8337-1976 duly crimped with crimping tool, PVC tape etc of following size.All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . 185.0 Sq.mm |
| 36 | 300.0 Sq.mm |
| 37 | 6.0 Sq.mm |
| 38 | 16.0 Sq.mm(copper) |
| 39 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in- charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR Single pole MCB (With B/C curve tripping Characteristics) 6 A to 32 A rating |
| 40 | 40 A rating |
| 41 | 50/63 A rating |
| 42 | SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2:2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, line load interchangeability, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% ICU. U imp =8 KV, rated insulation voltage 690V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connections etc. as required.OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in-charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 3 pole MCCB With Thermal Magnetic release 200 Amp , 25 kA, adjustable O/L & adjustable S/C setting, |
| 43 | 250 Amp , 35 kA, adjustable O/L & adjustable S/C setting, |
| 44 | 400 Amp , 35 kA, adjustable O/L & adjustable S/C setting, |
| 45 | Providing & Fixing of AC operated heavy duty 230 /440 Volt power contactor as per PWD specification for electrical Works, ISI marked IS/IEC 60947-4-1 : 2000 having provision of mechanical interlocking, auxilary contacts, Din rail mounting type including making connections, testing etc. as required. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR. 3 pole Power contactors with following AC 3 Rating 185 Amp |
| 46 | 250 Amp |
| 47 | 400 Amp Please Enable Macros to View BoQ information |