| 1 | Excavation in trenches not exc 1.5m wide and not exc 1.5m in depth for laying of cables, pole, stays foundation and getting out in soft loose soil all as specified and directed by Engr-in-Charge |
| 2 | Excavation in trenches not exc 1.5m wide and not exc 1.5m in depth for laying of cables, pole, stays, foundation and getting out in soft disintegrated rock all as specified and directed by Engr-in-Charge. |
| 3 | Excavation in trenches not exceeding 1.5 m width and not exc 3m in depth getting out in soft disintegrated rock all as specified and directed by Engr-in-Charge. |
| 4 | Returning, filling in including spreading, levelling, watering and well ramming in layers n.exc 25cm thick all as specified and directed by Engr-in-Charge. |
| 5 | Removal of excavated material of soil not exc 50m and depositing where directed at a level not exc 1.5m above the starting point all as specified and directed by Engr-in-Charge. |
| 6 | M&L PCC (1:3:6) type C-2 (using 40mm graded crushed stone aggregate) as in foundation filling and mass concrete for foundation of Pole, transformer, Panel board, stay, post top lantern, repairs to road cutting, drain, path all as specified and directed by Engr-in-Charge. |
| 7 | M&L PCC (1:2:4) type B-1 (using 20mm graded crushed stone aggregate) as in coping of new pole / reconstruction of old damaged copings etc, including necessary form work all as specified and directed by Engr-in-Charge |
| 8 | M&L for road cutting upto 300mm deep and 200mm wide for crossing GI water pipe line through road including making good the disturbed surface by filling mass concrete complete all as specified and directed by Engr-in-Charge.Note: Mass concrete will be measured and paid as seperate item. |
| 9 | M&L for sand cushioning in trenches for cable protection all as directed and specified. |
| 10 | Supply and lay PCC cable cover class LV type I flat size 250mm x150mmx40mm all as directed and specified |
| 11 | M&L for fixing or passing through pipe, laid in trenches or fixed to pole/wall or fixed to LT panel board, 1100 volts grade heavy duty cable with PVC insulated stranded aluminium conductor served with inner sheathing of PVC tape, armoured with galvanised steel wire or tape and overall PVC sheathed 6 sqmm 2 core with required aluminium cable lugs, heat shrink joints, Colour code heat shrink sleeves at both cable ends all as specified and directed.Make : Polycab/Asian/Finolex/Grandlay |
| 12 | All as per item No. 11 here-in-before but 10sqmm 2 core all as directed and specified |
| 13 | All as per item No. 11 here-in-before but 16sqmm 2 core all as directed and specified |
| 14 | All as per item No. 11 here-in-before but 10sqmm 4 core all as directed and specified |
| 15 | All as per item No. 11 here-in-before but 16sqmm 4 core all as directed and specified |
| 16 | All as per item No. 11 here-in-before but 25 sqmm 3.5 core all as directed and specified |
| 17 | All as per item No. 11 here-in-before but 35 sqmm 3.5 core all as directed and specified |
| 18 | All as per item No. 11 here-in-before but 50 sqmm 3.5 core all as directed and specified |
| 19 | M&L steel tubular swaged pole complete with cast iron base plate, finial taper plug bolts nuts and screws confirming to IS : 2713 made out of structural steel tube confirming to IS: 1161 and painted internally with a coat of bituminous paint and externally one primer coat and two finishing coat of aluminium paint as specified type 410 SP-31 (9 mtr long) all as specified and directed. |
| 20 | Painting of steel pole any type up to 7.5 mtr height above ground level including cross arms, clamps, stay clamps, brackets, swan neck etc with two coats of aluminium paint after surface preparation all as specified and directed. |
| 21 | M&L for numbering of LT poles serially with letter/number size width and height up to 40 mm in situ with black paint on white back ground all as specified and directed. |
| 22 | S&F GI tubing light grade 25 mm bore, on pole /wall with necessary clamps, nuts, bolts and washers/under road crossings ISI marked for cable protection all as specified and directed. |
| 23 | S&F GI tubing light grade 40mm bore, on pole /wall with necessary clamps, nuts, bolts and washers/under road crossing ISI marked for cable protection all as specified and directed. |
| 24 | S&F GI tubing light grade 50mm bore on pole /wall with necessary clamps, nuts, bolts and washers/under road crossing ISI marked, for cable protection, ISI marked, for cable protection all as specified and directed. |
| 25 | S&F GI pipe bracket with suitable clamps on existing pole made of MS flat 40x5mm and 40mm dia GI pipe (light grade) bend to 1.5 mtr in length & in any shape with all fixing arrangement, nuts, bolts and washers etc and including 4 RM copper conductor cable multi stranded size of 1.5 Sqmm PVC wire from SMC Box to Street light fitting all as specified and directed. |
| 26 | S&F in repairs LED security fitting 60 watt with LED to shine even brighter. the light also has an inbuilt surge protection IP 66 all as specified and directed including dismentling taking down unserviceable fitting any type all as specified and directed. NOTE: The contractor must produce the IK10 and LM79 - LM80 test report of the batch of fittings before installation.Make: Havells or techno commercial Equivalent in Philips/Wipro. |
| 27 | S&F in repairs LED security fitting 90 watt with LED street light with aluminium PDC housing and toughened glass cover with IP 66 protection, secondary lenes for individual LED for roadways application including dismentling taking down unserveable fitting any type all as specified and directed.NOTE: The contractor must produce the IK10 and LM79 - LM80 test report of the batch of fittings before installation.Make: Havells or techno commercial Equivalent in Philips/Wipro. |
| 28 | S&F in repairs LED security fitting 120 watt with LED street light with aluminium PDC housing and toughened glass cover with IP 66 protection, secondary lenes for individual LED for roadways application including dismentling taking down unserviceable fitting any type all as specified and directed.NOTE: The contractor must produce the IK10 and LM79 - LM80 test report of the batch of fittings before installation.Make: Havells or techno commercial Equivalent in Philips/Wipro. |
| 29 | S&F in repairs LED flood light fitting 200 watt with LED driver and lense complete with all fittings including 2.5 sqmm three core copper flexible conductor cable including dismentling taking down unserviceable fitting any type all as specified and directed.NOTE: The contractor must produce the IK10 and LM79 - LM80 test report of the batch of fittings before installation.Make: Havells or techno commercial Equivalent in Philips/Wipro. |
| 30 | Supply, installation, commissioning and testing of outdoor type feeder pillar panel box, platform mounted, suitable for 3 phase 4 wire, 415 volts AC supply and having 4 Nos Aluminium bus bar, of capacity 200 Amps fabricated in factory having modern fabrication duly powder coated painting, dust and vermin proof and degree of protection not less than IP-55 . The panel shall be made out of 3.00mm thick CRCA mild steel sheet, front door (01 layer) and rear Door (01 layer) opening facility and 4 side slanting canopy type roof on top and suitable angle iron mounting base frame at bottom min 0.6 Mtr above ground level including PCC work. The feeder pillar shall be comprising of the followings:- Incomming : (a) MCCB 160 amps 25 KA Outgoing : (a) MCCB 63 Amps -01 Nos (b) MCB TP 32 to 40 Amp. -03 Nos(c) DX3 Power Contactor , 3 phase- 4NO (d) Alpha rex digital type Timer switch (f) Intelligent panel meter (g) Indicator lamp set of three (LOCATION TB -II ) |
| 31 | Supply, installation, commissioning and testing of outdoor type feeder pillar panel box, platform mounted, suitable for 3 phase 4 wire, 415 volts AC supply and having 4 Nos Aluminium bus bar, of capacity 100 Amps fabricated in factory having modern fabrication duly powder coated painting, dust and vermin proof and degree of protection not less than IP-55. The panel shall be made out of 3.00mm thick CRCA mild steel sheet , front door (01 layer) and rear Door (01 layer) opening facility and 4 side slanting canopy type roof on top and suitable angle iron mounting base frame at bottom min 0.6 Mtr above ground level including PCC work. The feeder pillar shall be comprising of the followings:- Incomer : (a) MCCB 63 amps 16 KA Outgoing : (b) MCB TP 32 to 40 Amp.- 03 Nos(c) DX3 Power Contactor , 3 phase 4NO (d) Alpha rex digital type Timer switch (e) Intelligent panel meter (f) Indicator lamp set of three (LOC -: 1X BI CAMP & 1X TB II) |
| 32 | M&L for fabrication, supply & install LT Panel out door type with 3.15 mm thick MS sheet of size (1.20X1.20X0.50Mtr) factory made and angle iron of size 50x50x5 mm angle iron frame, weather proof ventilated with locking arrangement with following accessories. :- ( for BI CAMP)(a ) MCCB 160 Amps 4pole 25 KA - 01 N0s. (I/C)(b) MCCB 3 Pole 63 Amps 16 KA 415 volts - 03 Nos. (c) Digital type Voltmeter with selector switch 0 to 500 volts - 1 No.(d) Indicating lamps with assembly - 3 nos.(e) Aluminium bus bar upto 600 Amps for 3 phase and neutral- 1 set .(f) Digital Ammeter of range (0 to 500) Amps, flush mounting type with CT, of ratio 500/5 and selector switch -01Nos. |
| 33 | M&L 16 meter High galvanized high mast light suitable for 09 lantern symmetrically fitted a high galvanized mast made out of heavy duty MS pipe section reducing from bottom 360 mm (A/F) to top 150 mm (A/F) thick bottom plate fixing arrangement with 20mm dia foundation bolts grouted in PCC foundation including necessary civil work etc complete with fixing arrangements for 09 in Nos LED Flood light 200 watt symmetrically fixed along with their control gear and having two point suspension system with steel wire rope of grade AISI 316 of 6mm dia & double drum winch & dismantling of old unserviceable one comprising of following :-(a) provision of wiring from panel to light fitting with single/multi core 4 sqmm copper conductor cable drawn through MS rigid/flexible conduit with necessary fitting etc.(b) provision of single pointed air termination rod and necessary fitment required for protection against lightening protection (Earthing shall be measured and paid separately)(c) provision of motorized hoisting and lowering of lights carriage for repairs. Make: Cat part No. HM-16A-LM-ACC of Crompton or equivalent |
| 34 | S&F LED post top lantern 40 watt complete with 40/50 mm GI Pipe Light grade, clamps,nut, bolt and washers, including 1.5 sqmm three core copper flexible conductor cable all as specified and directed. NOTE: The contractor must produce the LM79 - LM80 test report of the batch of fittings before installation.Make: CG Cat no: LPTC-40-WW or techno commercial Equivalent in Philips/Wipro |
| 35 | S&F LED Bollard light with optically design reflactor and indirect-direct, downward directional, high performance, smartly designed asymmetric lighting landscapes of 10 watt, 230 Volt , AC with all fittings complete on PCC foundation all as specified and directed by Engr-in-Charge..Make : Wipro Cat no: LB13-131-XXX-65-08 or techno commercial Equivalent in Philips/Jaguar . |
| 36 | S&F in replacement old unserviceable LED cylinder Bollard of 10 watt made of extruded aluminium housing having IP65 protection mounting on PCC 1:3:6 of suitbale size with 3 nos anchor fastner and wiring all as specified and directed. Make : Jaquar Cat No. LBLDCYL010XW or its equivalent in Wipro/ Philips. |
| 37 | S&F in replacement old unserviceable LED Monaco Bollard light fitting made of extruded aluminium housing with better light quality and enhance architectural design, rated IP-65 of 10 watt, 230 Volt AC with all fittings mounting on PCC 1:3:6 of suitbale size with 3 nos anchor fastner and wiring all as specified and directed.Make : Jaquar Cat No: 34044NGG or Equivalent in Philips/Wipro. |
| 38 | S&F sheet moulding compound junction (SMC) suitable for terminating 2 Nos 2 x 6/10 Sqmm UG cable including cable glandes- 2 Nos, and two way connector 1 No, size 6\\" x6\\" including MCB SP 10 Amps10 KA Make ; Sintex. |
| 39 | M&L rigid non-mettalic PVC conduit of size 20mm inclusive of all fittings i.e. tees, bends, elbows, well mount tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks all as specified and directed. |
| 40 | S&F Heat shrinkable straight through joint LT 1100 volts grade 6 sqmm, 2 core all as specified and directed. Make- Raychem, Cat No-EPKJ0081 or techno commercial equivalent of M-Seal/MS Seal/3M |
| 41 | Supply and fix Heat shrink straight through joint LT 1100 volts grade 10-16 sqmm, 2 core, make-Raychem, Cat No-EPKJ0081 or techno commercial equivalent of M-Seal/MS Seal/3M |
| 42 | S&F Heat shrinkable straight through joint LT 1100 volts grade 10-16 sqmm, 4 core all as specified and directed. make- Raychem, Cat No-EPKJ0123 or techno commercial equivelant of M-Seal/MS Seal/3M |
| 43 | Supply and fix Heat shrinkable straight through joint LT 1100 volts grade 25-50 sqmm, 4 core all as specified and directed. make- Raychem, Cat No-EPKJ0130 or techno commercial equivalent of M-Seal/MS Seal/3M |
| 44 | M&L for Earthing complete with galvanised steel pipe electrode, 40 mm bore, medium grade, 3 mtr long burried directly and vertically in ground with top edge at ground level after making bore hole of size not less than 300 mm dia and 3.0 Mtr long using suitable mechanical drilling rig (for drilling near the specified bldg), connected with galvanised steel earthing lead of 4mm dia all as shown in Plate No-2, connected to the earthing test point, concrete pit in PCC 1:3:6 type C-2with RCC precast pit cover slab 400mmx400mmx80mm with handle for lifting made out of 8mm dia MS rod, funnel, wiremesh, 15 mm dia light grade GI tubing for protection of GI wire 4mm dia, charcoal and salt in alternate 150mm thick layers around GI earth pipe, including necessary returning filling in & removal all as specified or indicated in SSR Part-I, including testing to achieve earth resistance value as per IS specification on completion all as specified and directed. |
| 45 | M&L for Earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below ground level, connected to galvanized iron strip of size 26 x 6 mm as earthing lead by means of nut/bolt and washer of galvanized iron or steel drawn through 40 mm dia light grade GI pipe as shown in electrical plate no 3 of SSR part I of 2009 including necessary excavation and earh work GI pipe 20 mm dia medium grade for watering PCC chamber with PCC cover in cement concreate 1:2:4 Type B1 (using 20 mm graded crushed stone aggregate), funnel, wire mesh, charcoal dust, salt etc connected to panel board/ Gen set as indicated including testing complete all as specified and as directed. Note:- Earth protection pipe & earthing strip upto and including 7.5 m lenth is deemed included in unit rate quoted by the contractor. |
| 46 | M&L PVC insulated, PVC sheathed twin core 1100 volts grade, 2.5 sqmm aluminium stranded conductor (including PVC conduit pipe as per suitable size) all as specified and directed by Engr-in-Charge.Make : Finolex/Polycab/RR cable |
| 47 | All as per item No 46 above but of size of cable 4 sqmm. Please Enable Macros to View BoQ information |