| 1 | Excavation in trenches not exc. 1.5 Metre wide and not exc. 1.50 Metre in depth for cable trenches/ foundation etc. or for shafts, wells, cess pits, manholes, pier holes etc. not exc. 10 Sqm on plan and not exc. 1.50 Metre in depth and getting out as in Soft/Loose Soil, complete all as specified and as directed. |
| 2 | Removing excavated Material (Soil) not exc. 50.00 Metre and depositing where directed at a level not exc. 1.50 Metre above the starting point, complete all as specified and as directed. |
| 3 | Returning, Filling in, including Spreading, Levelling, Watering and Well Ramming in Layers not exc. 25 Cm as in Soft/Loose Soil, complete all as specified and as directed. |
| 4 | Supply and laying dry coarse sand as in cushioning of under ground electric cable in trenches, laid to a uniform thickness of 23 Cm (15 Cm under the cable & 8 Cm over the cable) and gently punned down to 18 Cm thickness complete all as specified and as directed by the Engr-in-Charge.Note:- Thickness after punning down shall be measured for payment. |
| 5 | M&L for Brick Sub Class 'B' locally available best quality laid in trenches with width equal to length of the bricks, above sand cushioning for cable protection complete all as specified and as directed. |
| 6 | M&L 100 mm bore GI tubing light grade for protection of cable including necessary joint including taking down old u/s one complete all as specified and as directed. |
| 7 | S&F in replacement steel water tubing 40 mm dia of bore light grade galvanised with all fittings laid in trenches / fixing with surface of wall after drawn through electric cable by means of nuts bolt and washers all as directed . |
| 8 | M&L for Boring/Drilling (Horizontally) manually/mechanically under existing road (Maximum 10 M in width) suitable for passing GI tubing of 40 to 150 mm bore complete all as specified and directed. |
| 9 | Supply and laying XLPE insulated PVC sheathed, armoured, aluminium conductor cable 1100 Volt grade 300 Sqmm 3.5 core in trenches/ duct/floor/wall with provision of saddle and lugs, joints etc including connection complete all as specified and directed by the Engr-in-Charge. |
| 10 | Supply and laying XLPE insulated PVC sheathed, armoured, aluminium conductor cable 1100 Volt grade 120 Sqmm 3.5 core in trenches/ duct/floor/wall with provision of saddle and lugs, joints etc including connection complete all as specified and directed by the Engr-in-Charge. |
| 11 | Supply and laying XLPE insulated PVC sheathed, armoured, aluminium conductor cable 1100 Volt grade 95 Sqmm 3.5 core in trenches/ duct/floor/wall with provision of saddle and lugs, joints etc including connection complete all as specified and directed by the Engr-in-Charge. |
| 12 | Supply and laying XLPE insulated PVC sheathed, armoured, aluminium conductor cable 1100 Volt grade 50 Sqmm 3.5 core in trenches/ duct/floor/wall with provision of saddle and lugs, joints etc including connection complete all as specified and directed by the Engr-in-Charge. |
| 13 | Supply and laying XLPE insulated PVC sheathed, armoured, aluminium conductor cable 1100 Volt grade 25 Sqmm 3.5 core in trenches/ duct/floor/wall with provision of saddle and lugs, joints etc including connection complete all as specified and directed by the Engr-in-Charge. |
| 14 | Supply and laying XLPE insulated PVC sheathed, armoured, aluminium conductor cable 1100 Volt grade 25 Sqmm 4 core in trenches/ duct/floor/wall with provision of saddle and lugs, joints etc including connection complete all as specified and directed by the Engr-in-Charge. |
| 15 | Supply and laying XLPE insulated PVC sheathed, armoured, aluminium conductor cable 1100 Volt grade 16 Sqmm 4 core in trenches/ duct/floor/wall with provision of saddle and lugs, joints etc including connection complete all as specified and directed by the Engr-in-Charge. |
| 16 | Supply and laying XLPE insulated PVC sheathed, armoured, aluminium conductor cable 1100 Volt grade 16 Sqmm 2 core in trenches/ duct/floor/wall with provision of saddle and lugs, joints etc including connection complete all as specified and directed by the Engr-in-Charge. |
| 17 | Supply and laying XLPE insulated PVC sheathed, armoured, aluminium conductor cable 1100 Volt grade 10 Sqmm 4 core in trenches/ duct/floor/wall with provision of saddle and lugs, joints etc including connection complete all as specified and directed by the Engr-in-Charge. |
| 18 | Supply and laying XLPE insulated PVC sheathed, armoured, aluminium conductor cable 1100 Volt grade 10 Sqmm 2 core in trenches/ duct/floor/wall with provision of saddle and lugs, joints etc including connection complete all as specified and directed by the Engr-in-Charge. |
| 19 | Supply and fixing LED Street lights not less than 25 W with a single piece of pressure die cast aluminium housing and secondary optics and individual LEDs for a better light distribution and control with IP66 degree of protection and integrated driver with 10KV surge protection complete as per manufacturer's instructions including taking down old unsv light complete all as specified and as directed. |
| 20 | Supply and fixing LED Street lights not less than 60 W with a single piece of pressure die cast aluminium housing and secondary optics and individual LEDs for a better light distribution and control with IP66 degree of protection and integrated driver with 10KV surge protection complete as per manufacturer's instructions including taking down old unsv light complete all as specified and as directed. |
| 21 | Supply and fixing LED Street lights not less than 90 W with a single piece of pressure die cast aluminium housing and secondary optics and individual LEDs for a better light distribution and control with IP66 degree of protection and integrated driver with 10KV surge protection complete as per manufacturer's instructions including taking down old unsv light complete all as specified and as directed. |
| 22 | Supply and fixing of LED flood light fitting light not less than 70 watt with IP66 protection new generation energy saving very high efficiency,enviormental friendly ,long life with fixing accessories such as braket made out by GI strip ,nutts bolts and washer complete making all connection all as specified and directed including taking down old unsv light complete all as specified and as directed. |
| 23 | Supply and fixing of LED flood light fitting light not less than 120 watt with IP66 protection new generation energy saving very high efficiency,enviormental friendly ,long life with fixing accessories such as braket made out by GI strip ,nutts bolts and washer complete making all connection all as specified and directed including taking down old unsv light complete all as specified and as directed. |
| 24 | Supply and fixingof New generation, post-top, energy saving, environmental friendly, long life aesthetically designed with symmetrical light distribution, spun aluminium landscape luminaire with high power LED light 35 Watt made up of high grade unbreakable polycorbonate material including taking down old unsv light complete all as specified and as directed. |
| 25 | Supply and fixing LED not less than 8W, 5700 K, 0.6 M long LED bollard for pathways and gardens are made with aluminium extrusion for sturdiness and better finish, UV stabilized injuction moulded oval polycarbonate diffuser for spot-free lighting and IP 65 degree of protection with fixing accessories complete as per manufacturer's instructions including taking down old unsv light complete all as specified and as directed. |
| 26 | S&F in repair of Crown shaped gate/garden light in soothing opal finish made up of unbreakable Polycarbonate material, including 15 W LED Lamp (B-22 base) complete all as specified and as directed. |
| 27 | Material and labour for painting to steel tubular pole 9.0/8.5 metre long with two coats of synthetic enamel paint up to 1.20 metre height from ground level in 15 cm alternative black and yellow strips and remaining portion with aluminum paint and MS frames like channel, clamps, angle, D-clamps etc with two coats of aluminum paint complete all as specified and as directed. |
| 28 | Dismantling existing steel or cement poles/ struts, any size carefully including necessary excavation demolition of concrete etc. and removing the old unserviceable rubbish etc, complete all as specified and as directed. |
| 29 | Supply and erecting steel tubular swaged pole complete with cast iron base plate, finial taper plug, bolts, nuts and screw as specified, type 410 SP-31, 9 Metre long including two coats of aluminium paint over one coat of red oxide primer complete all as specified and as directed by the Engr-in-Charge. Note:- Rates quoted shall be deemed to be inclusive of following works:-(a) Material and labour for painting of pole externally with one coat of black bituminous paint (upto planting depth) and above plinth block concrete collar with two coats of aluminium paint over a coat of red oxide primer including preparation of surface. (b) Material and labour for writing letter or figures (Block, Roman, Italic as Indian) with thick synthetic enamelled paint of apprised shade n exc 5 Cm height including numbering of pole all as directed by EIC. |
| 30 | M&L PCC (1:3:6) type C2 using 40mm graded aggregate as in foundation for stay set /Pole/ Panels etc including fair finish even and fir to exposed surfaces without using extra cement complete all as specified and as directed. |
| 31 | M & L PCC (1:2:4) type B-1 (with using 20 mm graded stone aggregate) as coping of pole/panel including necessary form work as required, complete all as specified and as directed. |
| 32 | S&F in repair 1100 Volts grade heavy duty cable PVC insulated standred twin core flat or circular aluminium conductor of size 2.5 Sqmm, served with inner sheathing of PVC tape and overall PVC sheathed in service connections, complete all as specified and as directed. |
| 33 | S&F in repair1100 Volts grade heavy duty cable PVC insulated standred twin core flat or circular aluminium conductor of size 4.0 Sqmm, served with inner sheathing of PVC tape and overall PVC sheathed in service connections, complete all as specified and as directed. |
| 34 | Supply and fixing in repair of loop in loop out junction box, IP 65 / IP 66 protection halogen free and weather proof of minimum size (130 x 180 x 77) mm, fixed to Pole with suitable clamp including nuts and bolts and washers incl provision of connector fixed to pole, complete all as specified and as directed. |
| 35 | Supply and fixing in repair PVC medium grade conduit 20 mm dia for drawing cable between pole junction box and light fitting brakect including fixing clamp made of GI strips and nut and bolts (Minimum 3 clamp in each pole to be provided) complete all as specified and as directed. |
| 36 | Supply and fixing in repair 1100 volts grade PVC insulated weather proof sheathed copper cable 1.5 sqmm size 3 core between pole junction box and light fitting complete all as specified and as directed. |
| 37 | Supply & fixing in repair bracket of size 32 mm GI pipe for mounting street light at top of existing LT pole including Clamp, cutting, welding, reaming, finishing ,bending in appropriate size at existing location as directed, complete all as specified and as directed. . |
| 38 | Material and Labour for overhauling/servicing of DG set of capacity 125 KVA all as per manufacturer instructions, carrying out the changing of oil filter, air filter, checking of nut, bolts, washers, gaskets, screws, hose clamps, including draining out old engine oil and filling in new engine oil, filling in/top up coolent in radiators of water cooled engine, taking out air filter element cleaning the same with compressed air for the removing the dust or replace unserviceable element with new element, cleaning of waste oil or coolent from engine complete testing after repair for its smooth functioning, complete all as specified and as directed. Note : (i) Replacement of minor spare parts like nut, bolt shall be deemed in the quaoted rated. (ii) Oil filter, Air Filter, engine oil, coolent, distiled water and other required item will be paid under relevant item as supply only |
| 39 | Material and Labour for servicing of DG set of capacity 100 KVA all as per manufacturer instructions, carrying out the changing of oil filter, airf ilter, checking of nut, bolts, washers, gaskets, screws, hose clamps, including draining out old engine oil and filling in new engine oil, filling in/top up coolent in radiators of water cooled engine, taking out air filter element cleaning the same with compressed air for the removing the dust or replace unserviceable element with new element, cleaning of waste oil or coolent from engine complete testing after repair for its smooth functioning, complete all as specified and as directed. Note : (i) Replacement of minor spare parts like nut, bolt, gasket, 'o' ring shall be deemed in the quaoted rated. (ii) Oil filter, Air Filter, engine oil, coolent, distiled water, will be paid under relevant item as supply only |
| 40 | Material and Labour for servicing of DG set of capacity 62.5 KVA all as per manufacturer instructions, carrying out the changing of oil filter, airf ilter, checking of nut, bolts, washers, gaskets, screws, hose clamps, including draining out old engine oil and filling in new engine oil, filling in/top up coolent in radiators of water cooled engine, taking out air filter element cleaning the same with compressed air for the removing the dust or replace unserviceable element with new element, cleaning of waste oil or coolent from engine complete testing after repair for its smooth functioning all as specifed and directed. Note : (i) Replacement of minor spare parts like nut, bolt, gasket, 'o' ring shall be deemed in the quaoted rated. (ii) Oil filter, Air Filter, engine oil, coolent, distilled water will be paid under relevant item as supply only |
| 41 | Material and Labour for servicing of DG set of capacity 40 KVA all as per manufacturer instructions, carrying out the changing of oil filter, airf ilter, checking of nut, bolts, washers, gaskets, screws, hose clamps, including draining out old engine oil and filling in new engine oil, filling in/top up coolent in radiators of water cooled engine, taking out air filter element cleaning the same with compressed air for the removing the dust or replace unserviceable element with new element, cleaning of waste oil or coolent from engine complete testing after repair for its smooth functioning, complete all as specified and as directed. Note : (i) Replacement of minor spare parts like nut, bolt, gasket, 'o' ring shall be deemed in the quaoted rated. (ii) Oil filter, Air Filter, engine oil, coolent, distilled water will be paid under relevant item as supply only |
| 42 | Material and Labour for overhauling/servicing of DG set of capacity 180 KVA all as per manufacturer instructions, carrying out the changing of oil filter, air filter, checking of nut, bolts, washers, gaskets, screws, hose clamps, including draining out old engine oil and filling in new engine oil, filling in/top up coolent in radiators of water cooled engine, taking out air filter element cleaning the same with compressed air for the removing the dust or replace unserviceable element with new element, cleaning of waste oil or coolent from engine complete testing after repair for its smooth functioning all as specifed and directed. Note : (i) Replacement of minor spare parts like nut, bolt shall be deemed in the quaoted rated. (ii) Oil filter, Air Filter, engine oil, coolent, distiled water and other required item will be paid under relevant item as supply only |
| 43 | Material and Labour for overhauling/servicing of DG set of capacity 250 KVA all as per manufacturer instructions, carrying out the changing of oil filter, air filter, checking of nut, bolts, washers, gaskets, screws, hose clamps, including draining out old engine oil and filling in new engine oil, filling in/top up coolent in radiators of water cooled engine, taking out air filter element cleaning the same with compressed air for the removing the dust or replace unserviceable element with new element, cleaning of waste oil or coolent from engine complete testing after repair for its smooth functioning, complete all as specified and as directed. Note : (i) Replacement of minor spare parts like nut, bolt shall be deemed in the quaoted rated. (ii) Oil filter, Air Filter, engine oil, coolent, distiled water and other required item will be paid under relevant item as supply only |
| 44 | Material and Labour in replacement of automatic voltage regulator suitable for 40 KVA to 125 KVA DG set complete all as specified and as directed. |
| 45 | Material and Labour in replacement of automatic voltage regulator suitable for 180 KVA to 250 KVA DG set complete all as specified and as directed. |
| 46 | Material and Labour for over haulaing out Fuel injector pump from DG set carefully, transportation of the same to civil work-shop for repair & complete service of FIP pump and calibration on automatic setting machine, shifting of FIP pump from civil work-shop to worksite and re-fixing the same to DG set and testing complete of range 40 KVA to 125 KVA complete all as specified and as directed. |
| 47 | Material and Labour for over haulaing out Fuel injector pump from DG set carefully, transportation of the same to civil work-shop for repair & complete service of FIP pump and calibration on automatic setting machine, shifting of FIP pump from civil work-shop to worksite and re-fixing the same to DG set and testing complete of range 180 KVA, & 250 KVA complete all as specified and as directed. |
| 48 | Supply only engine oil suitable for diesel genrator 40 KVA to 125 KVA, complete all as specified and as directed. |
| 49 | Supply only coolent \\"K' for radiator of water cooled engines, complete all as specified and as directed. |
| 50 | Supply only Oil filter element as per existing, complete all as specified and as directed. |
| 51 | Supply only Air filter element as per existing, complete all as specified and as directed. |
| 52 | Supply only distilled water for battery or radiator of engine used with coolent, complete all as specified and as directed. |
| 53 | Supply and fixing in repair 'V' belt ribbed of (a) radiator fan belt, (b) battery charging dynomo belt, and (c) water pump belt all suitable for DG set, complete all as specified and as directed. |
| 54 | Material and Labour for Painting of DG set of capacity 62.5 KVA and 125 KVA at different location inside Misa camp through spray painting with two coats of approved fire proof metal paint, complete all as specified and as directed. |
| 55 | S&F in repair relay siutable for 125 KVA & 62.5 KVA DG AMF Panel all as specified and directed. |
| 56 | Material and Labour for finding out defects of DG set Control panel and Taking out burnt wiring including u/s and serviceable components for reuse including Rewiring of panel using existing size of copper cable, ferrule, lugs, insulating material, nut bolt washer of various sizes including testing complete. |
| 57 | S&F in repair 3 Phase LED Ammeter CL-1 flush mounting with inbuild selector switch and CT, complete all as specified and as directed. |
| 58 | S&F in repair 3 Phase LED voltmeter CL-1 flush mounting with inbuild selector switch and CT, complete all as specified and as directed. |
| 59 | Supply & fixing in repair of 180 AH Battery, complete all as specified and as directed. |
| 60 | Supply & fixing in repair of 150 AH Battery, complete all as specified and as directed. |
| 61 | Supply & fixing in repair of 120 AH Battery, complete all as specified and as directed. |
| 62 | Dismantling self starter of 40 KVA to 250 KVA DG set for repairing the starter by replacing carbon brushes, brush holder, bearings, solenoid coil, replacement of burnt aremeture, rewinding of Fd coils, replace of pinion gears etc, completer servicing and refixing after repair, testing/commissioning complete for DG Set any capacity ccomplete all as specified and as directed. (Note : Replacement of solenoid coil, armeture coil, and pinion gear Shall be deemed in quoated rate) |
| 63 | Supply and fix in repair battery leads set appx 1.0 Mtr long, PVC insulated multistranded copper conductor 16 sqmm single core, duly fixed brass clamps, copper lugs for connections from DG battery to self starter on various DG Sets of any capacity installed, complete all as specified and as directed. |
| 64 | Supply and fixing in replacement on load change over switch with advance Neutral switch in steel sheet metal enclosure 4 pole By pass Switch and 415 volts conforming to IS compact design of capacity 200 Amps complete all as specified and directed. |
| 65 | Supply, install, testing and commissioning of floor mounted LT outdoor panel board AC 415 V , 50 HZ 3 Phase 4 wire of suitable size for accomodating the following accessories totally enclosed self supporting structure / cubicle , fully compartmentalized type , suitable for indoor use , with bottom cable entry with suitable cable glands structure made out of 3.15 mm thick with CPRI Approved CRCA steel sheet of suitable size with angle iron frame work and legs of ISA 50X50X5 mm , with four legs grouted to PCC (1:2:4) type B1 , foundation block with suitable mounting arrangement for bus bars voltmeter, ammeter , changeover switch and MCCBs , hinged doors at front with suitable locking arrangement , Provision of louvers at sides , structure treated under 8 - tank metal treatment process and duly powder coated , complete including taking down old unserviceable LT panel compete all as specified and directed :- BUSBAR :-(a) Copper bus bar 500 Amps , supported on non hygroscopic fibres and brass screws for mounting -04 Nos.INCOMER(a) Supply and fixing MCCB 4 pole 415 Volts of breaking capacity of 35 KA of 250 Amps with Fixed thermal and Fixed magnetic setting - 01 No.INDICATING DEVICES(a) Supply and fixing LED Indicating lamps for Main Supply indicating R, Y, B - 03 Nos(b) Supply and fixing Digital Ampere Meter 31/2 digit display , incl CT having CTR 250/5 - 01 Nos & Digital Voltmeter 0-500 Volts , SIF 96 - 01 NosOUTGOING FEEDERS(a) Supply and fixing MCCB of 4 pole , 415volts of capacity 100 amps with breaking capacity of 16 KA fixed thermal and fixed magnetic setting - 02 Nos.(b) Supply and fixing MCCB of 4 pole , 415volts of capacity 63 amps with breaking capacity of 16 KA Fixed thermal and fixed magnetic setting - 06 Nos |
| 66 | Material and labour for earthing complete with galvanized steel plate electrodes of size 600mm x 600mm x 6mm thick buried directly in ground with earth pit not less than 2.25m deep below normal ground level with top edge of plate not less than 1.5 m below normal ground level connected to galvanized iron strip of 32 mm x 6mm earth lead by means of nuts bolts check nuts GI washers earth wire protected by galvanized iron pipe 40 mm bore (light grade) including concrete pit in PCC (1:3:6) type CI, precast RCC cover slab of size 30x30x10 cm with one handle for lifting (Inside cavity to be made in Pit for placing cover slab) made out of 8 mm dia MS bar funnel wire mesh 20 mm bore galvanized iron pipe (medium grade) for watering charcoal or coke and salt in alternate layers necessary earth work in soft/loose soil complete all as shown in electrical plate No 3 of SSR part 1 including testing on completion all as specified and directed incl demolition to existing one complete. |
| 67 | Supply and fixing in repair MCCB 4 pole , 415 V Fixed type 400 Amp, with breaking capacity 35 KA including spreader link and seperator and any modification required for fixing of MCCB including taking down old unserviceable one complete all as directed. |
| 68 | Supply and fixing in repair MCCB 4 pole , 415 V Fixed type 250 Amp, with breaking capacity 35 KA including spreader link and seperator and any modification required for fixing of MCCB including taking down old unserviceable one complete all as directed. |
| 69 | Supply and fixing in repair MCCB 4 pole , 415 V Fixed type 200 Amp, with breaking capacity 25 KA including spreader link and seperator and any modification required for fixing of MCCB including taking down old unserviceable one complete all as directed. |
| 70 | Supply and fixing in repair MCCB 4 pole , 415 V Fixed type 160 Amp, with breaking capacity 25 KA including spreader link and seperator and any modification required for fixing of MCCB including taking down old unserviceable one complete all as directed. |
| 71 | Supply and fixing in repair MCCB 4 pole , 415 V Fixed type 100 Amp, with breaking capacity 16 KA including spreader link and seperator and any modification required for fixing of MCCB including taking down old unserviceable one complete all as directed. |
| 72 | Supply and fixing in repair MCCB 4 pole , 415 V Fixed type 63 Amp, with breaking capacity 16 KA including spreader link and seperator and any modification required for fixing of MCCB including taking down old unserviceable one complete all as directed. |
| 73 | Supply and fixing in repair of MCB TPN 415 Volts, 63 Amps, 50 Hz, breaking capacity 10KA, C series all as specified and directed |
| 74 | NOTES:1. The amount of schedule of credit shall be deducted from the total of this BOQ for arriving at contract sum. Please Enable Macros to View BoQ information |