| 1 | Part A11kV Iine DP Structure with STP Annexure DP for 11 KV |
| 2 | 11KV Lightening Arrestor : |
| 3 | Supply, installation, testing and commissioning of single piece non-linear resistor type lightning arrestor suitable for 3 wire, 11KV O/H line, rated. Voltage of 12 KV (rms) with a nominal discharge current rating of 10 KA (station class) and complete with galvanised clamping arrangement G.I. bolts, nuts, washers etc. as required (to be provided on all phases). |
| 4 | Supply of ACSR Rabbit conductor |
| 5 | Supply of material for 400 KVA Copper wound oil type Transfarmer (atleast level 2 rating ) |
| 6 | S/O Material required for installation 400 KVA transformer making plinth etc. Complete |
| 7 | S/O Al. (3x185) sqmm XLPE 11 KV |
| 8 | S/O ST Pole 11 Mtr- IS 410 SP-55 |
| 9 | S/O 11 KV 65x65x6mm V-Type |
| 10 | S/O X-arm Holding Clamp |
| 11 | S/O Cable Jointing kit straight through 11 KV 3Cx185 sqmm |
| 12 | S/O Cable Jointing kit outdoor through 11 KV 3Cx185 sqmm |
| 13 | S/O 11 Kv Polymeric Pin Insulator with nut |
| 14 | S/O 11 kv Pin with nut |
| 15 | Supply of GI Pipe 6 inch dia |
| 16 | Supply of HDPE 120 mm |
| 17 | Supply of Al binding wire |
| 18 | S/O Danger Board with Clamp Nut and Bolt |
| 19 | S/O Number Plate with Fitting |
| 20 | S/O Aluminum Paint |
| 21 | S/O Red Oxide |
| 22 | S/O Stay Set Complete |
| 23 | S/O Concreting of Pole |
| 24 | S/O Earthing Complete |
| 25 | S/O Bolt & nut All Size (LS) |
| 26 | 11KV DO fuse set |
| 27 | 11KV TPMO with Polymer Insulator |
| 28 | Cable Al (3 C 120) Sqmm XLPE 11 KV |
| 29 | 4 X 25 Sqmm XLPE Al. Cable |
| 30 | 4 X 10 Sqmm XLPE Al. Cable |
| 31 | Supply of ABC Cable (3x120+1x95+1x16) sqmm |
| 32 | STP 9 Mtr IS 410 SP-33 |
| 33 | S/O Fencing for Transformer |
| 34 | Supply and laying of 25mm x 5mm G.I. strip on Surface or in recess for connection etc as required |
| 35 | SITC of fabricated connection box 14 SWG CRCA sheet with and powder coated paint with 300Amp aluminium bus bar with insulator and connection and connection arrengement, out door type as per drawing with suitable. |
| 36 | S/O Material for shifting of existing transformer 16 KVA, 25 KVA & 63 KVA |
| 37 | 11KV 3x185 sq mm Cable laying by HDD |
| 38 | Labour Charges @ 30% of SI.No. 1 to 35 item no 6 is taken 600 mtr Dismentling of old line / material and Deposit to Store including cartage Erection with T&P Laying, Testing & Commissioning etc.Amount 9920638.00 |
| 39 | Part BSupply, Installation Testing and Commissioning of Decorative square pole made out of MS Tube as per Catalogue No VSTP 68, complete in all respects. The pole shall be of single section having size 150 mm x 150 mm x 5000 mm height, provided with a base plate of size 260 mm x 260 mm x 12 mm thickness duly welded at the bottom. The pole shall be supplied with foundation bolts of 16 mm diameter x 600 mm length, 4 numbers with nuts and washers. An inbuilt control box shall be provided at the bottom of the pole with adequate space for housing MCB and terminal strip. The pole shall be equipped with inbuilt lighting arrangement including post top LED lights of 100W, 4 numbers, with complete internal wiring. The surface of the pole shall be properly prepared and finished with polyurethane (PU) |
| 40 | paint in approved color shade suitable for outdoor conditions. The scope shall also include supply of all necessary electrical accessories such as MCB, Wire, Backlite sheet, etc. |
| 41 | Supply and laying of Aluminum Conductor PVC insulated armored served sheathed cables 1100V grade at a depth of 750mm below ground level over a cushion of 75mm thick sand all around and protected with burnt bricks on sides and on top as directed by Engineer in Charge complete in all respect including excavation and refilling. The armoring of the cable shall be properly connected with the earth conductor by clamps etc. |
| 42 | 16 Sqmm 4 Core |
| 43 | 25 Sqmm 3.5 Core |
| 44 | 35 Sqmm 3.5 Core |
| 45 | SITC of 32A Outdoor Sub Feeder Panel fabricated out of 2.0/1.6mm thick CRCA sheet steel, painted with Powder coated paint of shade as per the direction of Engineer In-Charge after proper sheet treatment process of sheet steel. The Feeder Pillar shall be provided with Neoprene Gasket to achieve Degree of Protection IP:55 as per IS : 8623 suitable for Outdoor Installation. All Indicating Lights shall be LED type and all wiring shall be done from PVC Insulated copper flexible wire. The Panel shall be completed in all respect and shall consist of following material.Incomer : 32A, 4P, 36 kA MCCB with Thermal O/L & S/C Protection Release along with Incoming Phase Indicating Lights, & Contactor, Timer Switch on off Push Button etc.Outgoing : 32A 4P 10 K MCB with O/L and S/C Protection 2 Nos |
| 46 | SITC of 63A Indoor Sub Feeder Panel fabricated out of 2.0/1.6mm thick CRCA sheet steel, painted with Powder coated paint of shade as per the direction of Engineer In-Charge after proper sheet treatment process of sheet steel. The Feeder Pillar shall be provided with Neoprene Gasket to achieve Degree of Protection IP:55 as per IS : 8623 suitable for Outdoor Installation. All Indicating Lights shall be LED type and all wiring shall be done from PVC Insulated copper flexible wire. The Panel shall be completed in all respect and shall consist of following material. Incomer : 63A, 4P, 36 kA MCCB with Thermal O/L & S/C Protection Release along with Incoming Phase Indicating Lights, & Contactor, Timer Switch on off Push Button etc.Outgoing : 32A 4P MCCB with O/L and S/C Protection 2 Nos |
| 47 | Making connections of each street light fitting by S/L of 2.5 sqmm 3 core flexible copper cable from pole busbar box to fitting |
| 48 | Supply and making end termination with brass compression gland and aluminum lugs for following size of PVC insulated and PVC sheathed / XLPE aluminum conductor cable of 1.1 KV grade as required. |
| 49 | 16 sq. mm 4 core |
| 50 | 25 sq. mm 3-1/2 core |
| 51 | 35 sq. mm 3-1/2 core |
| 52 | Providing & Fixing 25mm x 5mm G.I strip on surface or in recess for Connection etc. as required . |
| 53 | Earthing with G.I earth Pipe form earth 4.5 meter long, 40mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc with charcoal/ a coke and salt as required. |
| 54 | Supplying and fixing 5A to 32A rating, 240/415V, 10kA, \\"C\\" curve, miniature circuit breaker suitabel for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Double Pole |
| 55 | Providing laying and fixing following dia G.I pipe (medium class) in ground complete with G.I fittings including trenching (75cm deep) and re-filling etc as required 100mm dia |
| 56 | S/L of Following Size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. Direct in ground (75cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc. complete in all respect 63 mm dia (OD-63mm & ID-51mm nominal) |
| 57 | GST @ 18% Extra Please Enable Macros to View BoQ information |