| 1 | Supply and fix street light TIMER control panel, 3 phase with contactor rating 65 A TP and MCB rating 63 A TPN,maximum load 12 KW with DIGITAL 24 hours switch pole/wall mounting or embedded in foundation as per site requirement made out of 3.15 mm CRCA sheet duly powder coated with locking arrangement, conforms to IS/IEC 61439 & 60529 with IP 54 protection, class H insulation ,including internal wiring complete with bypass arrangements and in built short circuit protection complete as per manufactures recommendation and design complete all as specified and as directed. |
| 2 | Supply ,laying & testing UG cables in trenches, or fixing on walls or passing through cable duct / pipe XLPE insulated, screened, PVC bedded galvanized steel strip or wire armored electric power cables (heavy-duty) with aluminum conductor, 1100 volts, grade having cross sectional area 3.5 core 35 sqmm with necessary thimble, suitable cable gland, complete all as specified and as directed. |
| 3 | All as per item No 02 here-in-before but cable of size 16 Sqmm 4 core complete all as specified and as directed. |
| 4 | Material and labour for 3 single core copper cable of size 1.5sqmm (Red,Black and Green ) from junction box of the pole to light fitting and connecting to the electrical system complete all as specified and as directed. |
| 5 | Excavation in trenches soft/loose soil not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth and getting out excavated soil/sand/unseviceable LT Cable for laying of cable complete all as specified and as directed. |
| 6 | Returning filling in including spreading levelling watering and well ramming in layers not exceeding 25 cm in soft /loose soil complete all as specified and as directed |
| 7 | Removing excavated material not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified as directed |
| 8 | Supply and laying of DWC (Double wall corrugated) pipes of size 50 mm outer dia,IS:16205(Part-24) laid in trenches for underground cable protection complete all as specified and as directed. |
| 9 | Cutting existing road/hardstand/concrete blocks/slabs/brick work or stone masonry of any type by using crow bar chisel up to a depth of 30cm for laying GI pipe including making good the surface by returning filling watering ramming in layers cold mix bitumen over 200 mm thick hard core of broken bricks/stones over returning filling watering ramming in layers not exceeding 25 cm thick complete all as specified and as directed |
| 10 | Material and labour for GI tubing medium grade (ISI marked) of size 40mm dia with all fitting/acessories for protection of cable on pole/wall and under road crossing including clamps, nut bolt etc complete all as specified and as directed. |
| 11 | Material and labour for earthing complete with galvanized iron or steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 Mtrs below ground level) with top edge of earth plate not less than 1.5 Mtrs below ground level connected to galvanized iron strip 32x6 mm by means of nuts, bolts, thimbles, chuck nuts, washers of GI or steel, including PCC (concrete chamber) shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate, with fair finish internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4, funnel with wire gauge of (0.68mm) 8 mesh per liner inch, 80 mm thick RCC pit cover 320 mm x 320 mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with XPM, JALLI and charcoal dust and common salt all as shown in electrical plate No 3 of MES SSR Part-I and specified including provision of earth wire protected by 40mm dia medium grade GI pipe and watering pipe shall be 20mm bore medium grade GI pipe, and including all excavation and earth work & connecting the earthing to an earthing test point /transformer nuetral/body/ Lt panel etc. and testing on completion, complete all as specified and directed |
| 12 | Material and labour for dismantling floor,hearth or wall tiling including cement mortar bedding(but not backing) removing servicable tiles to store and rubbish off the premises complete all as specified and directed |
| 13 | Providing and laying 80 mm thick factory made chamfered edge cement concrete paver block of M-30 grade with approved color,design & pattern as in footpath,parks,lawns,drive ways or light traffic parking etc of required strength,thickness & size/shape made by table vibratory method using PU mould,laid in required color & pattern over and including 50 mm thick compacted bed of coarse sand,compacting and proper embedding/laying of interlocking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator,filling the joints with fine sand and cutting of paver block as required size and pattern,finishing and sweeping extra sand complete all as specified and directed |
| 14 | Material and labour for chequered cement concrete tiles 20cmx20cmx25cm thick,set,jointed and pointed in neat cement slurry in floors complete all as specified and directed Please Enable Macros to View BoQ information |