| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / heavy class PVC conduit having wall thickness minimum 2 mm, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. |
| 2 | Make:- Legrand (Myrius)/ Schneider(Livia)/Anchor Roma (Plus) |
| 3 | Group C. |
| 4 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed heavy class PVC conduit having wall thickness 2.0mm as required Make:- KEI/Anchar/ Finolex |
| 5 | 2x2.5 Sq. mm. |
| 6 | 2x4.0 Sq. mm. |
| 7 | 2x10.0 Sq. mm. |
| 8 | Wiring for circuit / sub-main with 4x4 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed PVC conduit along with 2 No.4 Sq.mm. (4X4+2X4)HRFRLS/PVC insulated single core copper conductor cable for earthing as required.Make:-KEI/Anchar/Finolex |
| 9 | Wiring for circuit / sub-main with 4x10 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed PVC conduit along with 2 No.10 Sq.mm. (4x10+2x10) HRFRLS/PVC insulated single core copper conductor cable for earthing as required.Make:-KEI/Anchar/Finolex |
| 10 | Supplying and drawing following size of PVC insulated, heat resistant, flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in existing surface / recessed, Steel/PVC conduit as required.Make:- KEI/Anchar/Finolex |
| 11 | PVC insulated HRFR LS Copper conductor 1.5 Sq. mm. |
| 12 | 3x2.5 Sq. mm. |
| 13 | Supplying and fixing G.I. Modular box of (140mmx78mmx50mm) size with modular plate and cover in recess including providing and fixing 5 pin 5/6 amps modular socket outlet and 5/6 amps, modular switch, connections etc. as required.Make:- Legrand (Myrius)/ Schneider(Livia)/Anchor Roma (Plus) |
| 14 | Supplying and fixing G.I. Modular box of (140mmx78mmx50mm) size with modular plate and cover in recess including providing and fixing 6 pin 15/16 amps modular socket outlet and 15/16 amps, modular switch, connections etc. as required.Make:- Legrand (Myrius)/ Schneider(Livia)/Anchor Roma (Plus) |
| 15 | Supplying and fixing Computer board comprising 3 nos 5 amp modular switches & Sockets and G.I Box 12 module for 5 amp switchs and 5 amp sockets comprising frame and cover plate for each 2 module and 12 module metal box including connections etc as required. |
| 16 | Make:- Legrand (Myrius)/Schneider(Livia)/Anchor Roma (Plus) |
| 17 | Supplying and fixing call bell / buzzer, suitable for D.C./A.C. single phase,230 volts complete as required:- |
| 18 | Providing and installation of exhaust fan of following sizes in the existing opening, including making the hole to suit the size of the above fan, making good the damages, connections, testing and commissioning etc. as required:- Make:-Usha/Bajaj/Anchor |
| 19 | Exhaust Fan, Light duty, (Domestic) 300 mm sweep |
| 20 | Providing, Installation, testing and commissioning of BLDC ceiling fan (5 star rating), including wiring the down rods of standard length (up to 30 cm) with 16/0.20 mm twin twisted flexible, cotton braided, copper cable, including providing and fixing phenolic laminated sheet cover on the fan box and earthing etc. as required: |
| 21 | 1200 mm sweep Make:- Usha(Technix BLDC without Regulator 5 Star ISI / Bajaj/Crompton (Warranty Five year) |
| 22 | 1400 mm sweep Make:- Usha(Technix BLDC without Regulator 5 Star ISI / Bajaj/Crompton (Warranty Five year) |
| 23 | Providing, Installation, testing and commissioning of wall fan of following size by means of suitable rag-bolt/ nuts, connections, testing and commissioning etc. as required complete in all respects to the best satisfaction of Engineer-in-charge .Make:- Usha/Bajaj/Crompton |
| 24 | Wall Fan 400 mm sweep |
| 25 | Supplying and fixing surface mounting following size LED solution suitable for surface application with the use of the latest technology 42 Watt (4200 lumen) 6000K and it should be compatible with specifications i.e. power factor ≥ 0.9, harmonic distortion ≤ 10% and efficacy ≥ 100 lumens per watt, CRI > 80, suitable for input voltage AC 220-240V, 50/60 Hz complete with all accessories, connections, testing and commissioning etc. as required. |
| 26 | Make:-Panasonic/ BAJAJ/WiproLeksa Lighting |
| 27 | Sauver (Surface)-42W/1ft.x4ft. |
| 28 | Cat No:LSVR003S042XC |
| 29 | Providing and fixing decorative extruded tube fixture having high quality design suitable for LED tube up to 20Watt (2000 lumen) 6500K and it should be compatible with specifications i.e. power factor ≥ 0.9, harmonic distortion ≤ 10% and efficacy ≥ 100 lumens per watt, CRI > 80, suitable for input voltage AC 220-240V, 50/60 Hz, including one no. tube rod 20 Watt complete with all accessories, connections, testing and commissioning etc. as required.Make- Bajaj,Panasonic,Wipro/Leksa Lighting |
| 30 | LED Tube Fixture 20Watt |
| 31 | Cat No: BCLAB 20W LED P |
| 32 | Supplying and fixing surface mounting following size LED solution suitable for surface application with the use of the latest technology 6/12/18 Watt (600/1200/1800 lumen) 6500K and it should be compatible with specifications i.e. power factor ≥ 0.9, harmonic distortion ≤ 10% and efficacy ≥ 100 lumens per watt, CRI > 80, suitable for input voltage AC 220-240V, 50/60 Hz complete with all accessories, connections, testing and commissioning etc. as required. |
| 33 | Make:-Bajaj/Panasonic/ Wipro/Leksa Lighting |
| 34 | LED 12 Watt Square |
| 35 | Supplying and fixing Surface mounting following size LED solution suitable for surface application with the use of the latest technology 24 Watt (2400 lumen) 6500K and it should be compatible with specifications i.e. power factor ≥ 0.9, harmonic distortion ≤ 10% and efficacy ≥ 100 lumens per watt, CRI > 80, suitable for input voltage AC 220-240V, 50/60 Hz complete with all accessories, connections, testing and commissioning etc.including 5 year warrenty as required.Make-:Bajaj/Panasonic/Wipro/Leksa Lighting |
| 36 | LED Panel Light 1'x1' |
| 37 | Cat No. LD66S-301-XX-65-SM |
| 38 | Providing and Fixing of LED fixture 600mmX600mm 36 Watt +/- 1W Recess mounted fixture with HET Plastic diffuser with minimum system lumen efficacy of 100 lm/W with CRCA housing having P.F.>0.95 with THD<10% ,CRI 80.The LED with Useful life of 50000 Hrs at L70. The LEDs used in the luminaire shall have CCT of 5700 K with CRI of minimum 80. The Input voltage range shall be 150V to 270V, 50/60 HZ complete with all accessories, including connections, testing and commissioning etc.as required complete in all respects. |
| 39 | Make:Panasonic/Wipro/Leksa Lighting |
| 40 | LED Panel 2'x2' 36 watt |
| 41 | Cat. No.PBLM22368C |
| 42 | Providing and fixing of IP65 Bulkhead led fixture 10 W +/- 1 W Wall Mounted with minimum system lumen efficacy of 100 lm/W with Pressure Die Cast Aluminum housing, Polycarbonate Opal Diffuser and P.F.>0.95 with THD<10% ,CRI 80.The LED shall be tested with LM80-08 standard with Useful life of 50000 Hrs at L70 .The LEDs used in the luminaire shall have CCT of ANSI Bin 5700 K only with CRI of minimum 80.The Input voltage range shall be 140V to 280V, 50/60 HZ complete with all accessories, including connections, testing and commissioning etc.as required complete in all respects. Make:Panasonic/Wipro/Leksa Lighting |
| 43 | LED Bulk head 10Watt Wipro Cat No:LW07-141-XXX-57-G1 |
| 44 | Providing and errection of LED 45 watt Street light luminaries powder coated pressure die-cast aluminium Make:-Jaquar/Panasonic/ WiproMDLED Street light with heat resistant toughened glass including connections, testing and commisioning etc; as required complete in all respects.Make:-Panasonic/ Wipro/Bajaj/Leksa Lighting |
| 45 | LED Street Light, 45 Watt |
| 46 | Cat No: PSTM27458 |
| 47 | plying & fixing following type of Surface mounted luminaires, white power coated CRCA housing diffusser to avoid glaire,it should be compatible with specification i.e. Power Factor > 0.9, Harmonic Distortion < 20% and efficacy > 100 Lumens per watt, CRI rating> 70 suitable for input voltage: AC 220-240 V, 50 Hz, complete with all accessories, connections, testing and commissioning etc. as required. Make- Bajaj,Panasonic,Wipro/Leksa Lighting |
| 48 | Mirror light LED 10Watt Cat No: LL20-111-111-XXX-65NE3 |
| 49 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess i/c providing and fixing 25 amp modular socket outlet and 25 Amps modular SP MCB, “C” curve including connection, painting etc. as required:- Make:- Legrand (Myrius)Schneider(Livia)/Anchor Roma (Plus) |
| 50 | Supplying and fixing of following way, single pole and neutral sheet steel MCB distribution board, 240 volts, on surface / recess, complete with tinned copper bus- bar, wire-set, neutral link, earth bar, din-bar, detachable gland plate, blanking plate, cable, identification labels interconnections, phosphatized and powder painted, including earthing etc. as required:-Make: Anchor, Legrand, Schneider. |
| 51 | Double door-12 way |
| 52 | Double door-16 way |
| 53 | Supplying and erection of 6 amps. to 32 amps. rating, 10 KA breaking capacity, 240 volts, 'C' curves, miniature circuit breaker of Single pole in the existing MCB DB complete with connections etc. as required:- Make: Anchor, Legrand, Schneider. |
| 54 | Supplying and fixing 63 Amps. rating, double pole (single phase & neutral) 240 volts, residual current circuit breaker (RCCB), having a sensitivity current up to 300 miliampers in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Make:- Anchor/ Legrand/ Schneider) |
| 55 | Supplying and fixing 63 Amps. rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Make:- Anchor/Legrand/Schneider) |
| 56 | Supply,Favirication,installation,testing,commissioning and electrically connected Factory (CPRI approved) made,LT panel Board of approved size as 600x600x225mm (LxHxD) as recommended by IS & CPRI norms,indoor type,Floor Mounted 1100 Volt,made out off CRCA sheet 1.6mm thick with IP-54 protection ,for 415 volts, (Certified not older than 2 Years) for volts 3 phase,4 wire AC supply,complete all as specified including provision of following accessary/components housed in it -: (1) 200 Amps rated copper bus bar with colour code TPN mounted on epoxy insulator : 01 set (set for 04 bus bar. (ii) LED indication lamp (set of 04 bus bar) (iii) Internal wiring with 1100 volt grade unsheahed PVC insuladed copper conductor of suitable size, cable as per colour coding or suitable size of bus bar for all connections with suitable lugs as required as per specified.(v) Earthing teminals and cable glands.(vi) Danger notice plate for LT with conventional skull and riveted/pasted to the panel door.Confirming to IS:-64139 and tested/approved from CPRI Lab Make:- Hark Power Control/ Power system control |
| 57 | The Panel shall include the following Switchgear & accessories; as per the Make of L & T,Schneider, C&S etc. |
| 58 | Incoming-: |
| 59 | (1) MCCB 200- Amps,4P 36KA Adjustable Thermal and fixed Magnetic MCCB (Spreader Links Inc.) |
| 60 | Providing and fixing Enclosure for MCCBs suitable for 3Pole & 4Pole MCCBs etc. as required complete in all respect. Make: L&T/Legrand. |
| 61 | Providing and fixing following rating and breaking capacity MCCB in the existing cubical panel board including drilling holes in the cubicle panel, making connections, etc. as required. |
| 62 | Make:- L&T/Legrand/Schneider |
| 63 | 63 Amp. Category-A |
| 64 | Supplying and fixing TP&N copper bus-bar chamber suitable for 415 volts capacity with 4 No. copper strip bus-bars each of length and x-section suitable for following current carrying capacities, enclosure made of sheet steel, dust protected, duly powder painted with detachable gland plate and other accessories including drilling holes on the board, making connections, earthing etc. as required. |
| 65 | 63 Amp. Category-A |
| 66 | Providing and fixing following rating, four pole, 415 volts, On-Load change over switch unit, AC 23 A duty, in sheet steel enclosure, with side handle operation, including drilling holes on the board, making connections, etc. as required.Make:- L&T/Legrand/Schneider |
| 67 | 100 Amps. |
| 68 | 200 Amps. |
| 69 | Earthing with G.I. earth plate 600 mmx600 mmx 6 mm thick, including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt ) as required. |
| 70 | Supplying and laying 6 SWG G.I. wire at 0.50 mtr. below ground level for earth electrode conductor, including soldering etc. as required. |
| 71 | Providing & Laying of one number aluminium conductor, PVC insulated and PVC sheathed armoured/ XLPE power cable, 1.1 KV grade of following sizes on wall surface as required. |
| 72 | Make:- KEI/Polycab/ L&T/Havells. |
| 73 | Armoured cable 95 sq. mm (3.5 core) Please Enable Macros to View BoQ information |