| 1 | PART-A |
| 2 | SITC of 400 KVA 11/0.433 kV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, (Copper wound ), and with LV Cable Box having detachable Aluminium Gland plate |
| 3 | SITC of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type |
| 4 | SITC of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type |
| 5 | SITC of 11 kV Horn Gap Fuse Set 3 Phase 200A |
| 6 | SITC 240mm²(2Ckt)/400mm² (2Ckt) Single Phase Cable,1.1K V Grade, PVC Insulated Stranded Conductor FRLS type |
| 7 | SITC 9 Mtr. Long Pole( ST-410 SP33) |
| 8 | SITC 11kV Polymeric composite Disc Insulator 12kV,min failing load 45KN, Lighting Impulse 75kV Positive and 80kV Negative, Creepage distance 320mm |
| 9 | SITC GI Channel/Angle/Flat of sizes including clamps for L.A set/G.O set/Horn Gap |
| 10 | Galvanized Nuts and Bolts. |
| 11 | Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts ,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. |
| 12 | Transformer Pad/G.I Channel Bedding |
| 13 | SITC 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lightening Impulse 75kV Positive and 80kV Negative, Creepage distance 320mm |
| 14 | SITC LT Distribution Box for 400/630 kVA DTR with MCCB for incomer & SFU's for Outgoing Circuits |
| 15 | SITC Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
| 16 | Wedge Connectors / PG Clamps |
| 17 | Danger Plates with Clamps |
| 18 | GI Barbed Wire for Anti Climbing |
| 19 | Cement bottoming 1:2:4 mix as per REC standards .5cum /pole |
| 20 | Part - B 11 KV Taping Point |
| 21 | SITC 9 Mtr. Long Pole(PCC WL-300Kg) |
| 22 | SITC G.I V cross-arm with top Bracket includingclamp |
| 23 | SITC G.I Channel/Angle lron including clamp |
| 24 | SITC 11kV GO, AB Switch 3-Phase, 3-Pole, 200Amp, Vertical Type |
| 25 | 50 mm² ACSR Conductor |
| 26 | PG Clamps for 50 mm² ACSR Conductor |
| 27 | SITC 11kV Polymeric composite Pin lnsulator 12kV, 5kN, Lighting lmpulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 28 | SITC 11kV Polymeric composite Disc lnsulator 12kV,min failing load 45kN, Lighting lmpulse 75kV Positive and 80kV Negative, creepaee distance 320mm |
| 29 | Galvanized Nuts and Bolts |
| 30 | Danger Plates with Clamps |
| 31 | Anti-Climbing Device with Clamps |
| 32 | Earthing Complete by Gl Pipe 40 mm or Gl Rod 20mm 2.5 mtr long through Gt strip. (for 2 No ST poles and 1 No GO Switch) |
| 33 | Cement bottoming 1:2:4 mix as per RECstandards .5cum /pole |
| 34 | Stone Pad (300 mm x 300 mm x 75 mm) |
| 35 | SITC Galvanised Stay Set with 5Ox8mm stay clamp, guy insulator(2Nos.), anchor plate(200x 200 x 6 mm), nutbolts, 2 Nos turn buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia Glstranded wire complete |
| 36 | PART-C 11 KV HT LINE |
| 37 | SITC 9 Mtr. Long Pole (PCC WL-300Kg , ST-410 SP33) |
| 38 | SITC 70 mm² AB (HT) Cable (3x70+1x50 mm²) XLPE (11 KV, 3C + Earth) |
| 39 | Heat Shrinkable Outdoor Cable Termination Kit |
| 40 | Suspension / Tension Clamp with eye hook |
| 41 | Galvanized Nuts and Bolts |
| 42 | Danger Plates |
| 43 | Antl-Climbing Device with Clamps |
| 44 | Earthing Complete by Gl Pipe 40 mm or Gl Rod 20mm 2.5 mtr long through Gt strip. |
| 45 | Cement bottoming 1:2:4 mix as per REC standards. .45cum/pole |
| 46 | Stone Pad (300 mm x 300 mm x 75 mm) |
| 47 | Mid span straight through Jointing Kit for 11 KV ABC |
| 48 | SITC Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos. ), anchor plate (200x 200 x 6mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia Gl stranded wire complete |
| 49 | PART -D LT EXTENSION AND STREET LIGHTING |
| 50 | Supply and erection of 9 mtr. Long PCC poles for supplying power to new possession holder customer at Roop Nagar Housing Colony by excavation and back filling the same with cement bottoming of the pole in ground in the ratio of 1:2:4 IS code for PCC pole IS 1785 (Part-I & Part-II) or 196 IS 6003 or 1983 IS 383-1970 with latest amendment (PCC WL-300KG) |
| 51 | Supply and laying of 70 mm sq. AB (LT) cable (3x70+1x16+1x50 Sqm) (1.1 KV + 31 Core Alu) |
| 52 | Supply and laying 50mm LT AB cables (3x50+1x16+1x35 mm. sq. XLPE (1.1 kV +3+1 core Alu) |
| 53 | Supply and fixing of suspension tension clamps with eye hook |
| 54 | Supply and fixing of straight through cable jointing kit |
| 55 | Supply and fixing of Gavanized Nuts and Bolts |
| 56 | Supply and fixing of Danger Plates |
| 57 | Supply and fixing of Anti-Clambing Device with Clamps |
| 58 | Earthing Complete by GI Pipe 40 mm or Gl Rod 20mm 2.5 mtr long through GI Strip. |
| 59 | Cement bottoming 1:2:4 mix as per REC standards. 45cum/pole |
| 60 | Stone Pad (300 mm x 300 mm x 75 mm) |
| 61 | Supply and fixing of Insulating Piercting Connector |
| 62 | SITC Wedge Connectors/ PG Clamps |
| 63 | SITC Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut- bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia Gl stranded wire complete |
| 64 | Supply and fixing of LT distribution box for service line of plot holders with SPN and TPN and aluminium bus bar fitted in fibre box (Complete Job). |
| 65 | Supply, Installation, Testing and Commissioning of 11 Mtr. High Mast Lights on street Tubular Pole along with ring and 04 No.150 watt LED Light at the top of ring and Electrical Panel for Control On and OFF of Lights with Pre Set timing (i.e digital timer) auto ON and OFF of light with automatic Voltage Stabilizer Copper wound single Phase Contactor S.P.N 32 Amp. 4 No. MCB 15 Amp digital Voltmeter as required Cement bottomint of Pole and Panel in the ratio of 1:2:4 Concrete. The panel must of out door type powder coated dust proof with external locking system. Providing and Laying of maintenance free Earthing Chemical type Earthing Including Excavaton of earth with base filling of same with good earth installation of 3m 14.2 Dia stainless Steel Pipe with Copper Rod and Filling of Chemical Compound (Complete Job) |
| 66 | Supply Installation Testing and Commissioning of LED Street Light 70 watt with G.I Pipe Bracket on PCC Pole including all accessories (Complete Job) |
| 67 | SITC of solar photo voltic SPV module luminious storage battery control electronic iner connecting wire ckt module to be mounted on G.I pole 4 mt. long above the ground incluidng hardware inbuilt battery with 12 wtt LED light battery tube used to be installed on pole 63mm dia embedded in the ground with cement concrete 1:2:4 ratio in the ground. Please Enable Macros to View BoQ information |