Housing Urban and Rular Development Government Departments Closing in 0 days TDR #55165428

Tender For B.O.Q For Construction Of New Server Building At Data Center Premises Bemina, Srinagar/ Infrastructure For Data Center At Srinagar B.W.O Providing 40 Kva Ups, Cabling And Other Allied Works In New Server Building At Kpdcl Data Centre Premi

Issued by Government Departments · Bemina, Jammu And Kashmir
Tender Value
29.36 Lakhs
Estimated cost
Bid Submission
04 May 2026
0 days left
EMD
58733
Bank guarantee accepted
Document Fee
1100
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Bemina → Jammu And Kashmir
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for B.O.Q For Construction Of New Server Building At Data Center Premises Bemina, Srinagar/ Infrastructure For Data Center At Srinagar B.W.O Providing 40 Kva Ups, Cabling And Other Allied Works In New Server Building At Kpdcl Data Centre Premises Pdd Complex, Bemina Srinagar

BOQ

Name of Work:- B.O.Q for Construction of New Server Building at Data Center Premises Bemina, Srinagar/ Infrastructure for Data Center at Srinagar B.W.O Providing 40 KVA UPS, Cabling and other allied works in new server building at KPDCL Data Centre premises PDD Complex, Bemina Srinagar
Sl. No. Item Description
1SITC of on-line UPS 40 KVA 3-phase IN ,3-Phase Out with 60 minutes battery back up and isolation transformer, complete with SMF VRLA type battery bank with minimum VAH of 64000 including MS battery racks, Linksets, Battery breakers, UPS to battery bank cable. ,SNMP card with each UPS.The ups & batteries shall have comprehensive warranty of 3 years from the date of successful commissioning.The specifications are mentioned below. Rating 4OKVA / Input Phase 3PH+N+PE,/Input voltage 3 phase-380/400/415V (selectable) /Input Frequency 45-55 Hz-55 H2 @ 50Hz, Auto sensing for 50/60 Hz, /Input power factor> 0.99/Generator Input support/ THDI <2% linear load/Rated output active power 72KW/Output voltage 3 phase-380/400/415 V (selectable)/Output power factor 0.9 leading/Outout wave form pure sine wave/Voltage variation +/- 1%/Load Crest Ratio>31/ Overload capacity 105%~110%-60 min~110%~125%-10 min~125%~150%-1'min/ Efficiency upto 94% double conversion mode/Operating temperature 0-45 deg C/Relative Humidity 0- 95%/ Noise level <55 Bm/Display LCD+ LED/Safety comply to CE/Backuptime 60 minutes (Minimum VAH-64000 for each UPS ), Make of UPS :- APC / VERTIV/BORRI /Eaton Make :- Make of batteries VRLA SMF AMARON Quanta / Exide/ Eq. make . The Job includes providing and fixing of Phase Sequencer correction Panels for each UPS to be installed on input supplies.The Job includes CMC Contract for ups and battery banks for a period of Two years reckoned from date of sucessful handing over of site to intending departnment (The CMC Includes replacement of damaged accessories /devices by fresh one during CMC Period)
2S/L , testing and commissioning of PVC COpper cable 650 V/1100 V Grade as per IS 7098 (Part 1) 1988 with upto Date Amendments.Havell/Eq. standard make as directed by engineer incharge and making end termination with brass compression gland and Copper lugs of required size.
3a)35 sq.mm 3.5 core ( un-armoured)
4(UPS Panel) Design,Supplying,Installation,Testing and Commissioning of Cubical Type double door, indoor LT Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars etc. as required as per the Following Description.(IP:42) General Floor Distribution Panel.The successful tenderer shall take prior approval for the panel builder/fabricator alongwith G.A. drawing, wiring diagrams, single line diagram before start of fabrication of LT panel.Circuit breaker shall be capable of carrying the full load current defined for 50 degree Celsius without any derating.The Panel Builder Shall be CPRI /ERDA/ANY NABL ACCREDITED LAB approved with latest amendments IEC-61439. Size of wiring for CTS:- 2.5 sqmm, Size of wiring for voltage sensing Metering :-4.0 Sq.mm, Size of wiring of all push buttons, indicating lamps:-1.5 Sq.mm,Types of wires:-PVC insulated 1100V grade ,Multistrand copper conductor Flexible FR-LSH, Hinged Door Earthing:-Device mounted hinged doors connected to cubicles body by means of 2.5 sqmm.green copper flexible wire, The Complete Panel Shall be Made out of 2.0 mm CRCA sheet including Frame/Partitions/Doors etc, Gland Plates to be 3.0 mm Thick. ( As per approved design,size may vary as per site requirement)
5Providing and fixing of following protection equipments and other allied accessories including connections, inter connections, with suitable size of PVC insulated copper conductor cable including earthing etc. as required.
6Normal INCOMING
7a)160A 4P MCCB 36 KA including spreader links including spreader links, icu=ics=100% ( Adjustable thermal and Adjustable magnetic release ) Legrand/ Shinider/Semiens/ABB/ eq. make to be approved by EIC.
8b) 4 No. of Aluminium Bus Bar of 200 Amp.
9c)Digital meters and phase indicators -1 set.
10OUTGOING:
11d) onload Change over switch 100 Amp for generator.Front operated.
12b) 4 No. of Aluminium Bus Bar of 200 Amp.
13c)Digital meters and phase indicators -1 set.
14c) 63amp DP MCB 10 KA Legrand/ Shinider/ABB/L&T/ eq. make. sample to be approved before installation..
15c) space for 12 way MCB's
16Design,Supplying,Installation,Testing and Commissioning of Cubical Type double door, outdoor LT Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars etc. as required as per the Following Description.(IP:42) General Floor Distribution Panel.The successful tenderer shall take prior approval for the panel builder/fabricator alongwith G.A. drawing, wiring diagrams, single line diagram before start of fabrication of LT panel.Circuit breaker shall be capable of carrying the full load current defined for 50 degree Celsius without any derating.The Panel Builder Shall be CPRI /ERDA/ANY NABL ACCREDITED LAB approved. with latest amendments IEC-61439 .Size of wiring for CTS:- 2.5 sqmm, Size of wiring for voltage sensing Metering :-4.0 Sq.mm, Size of wiring of all push buttons, indicating lamps:-1.5 Sq.mm,Types of wires:-PVC insulated 1100V grade ,Multistrand copper conductor Flexible FR-LSH, Hinged Door Earthing:-Device mounted hinged doors connected to cubicles body by means of 2.5 sqmm.green copper flexible wire, The Complete Panel Shall be Made out of 2.0 mm CRCA sheet including Frame/Partitions/Doors etc, Gland Plates to be 3.0 mm Thick. ( As per approved design,size may vary as per site requirement)
17Providing and fixing of following protection equipments and other allied accessories including connections, inter connections, with suitable size of PVC insulated copper conductor cable including earthing etc. as required.
18Normal INCOMING:
19a)400 Amp TPN MCCB 50 K including spreader links including spreader links, icu=ics=100% ( Adjustable thermal and Adjustable magnetic release ) Legrand/ Shinider/Semiens / eq. make to be approved by EIC..
20b) 630 amp 4 strip bus 1 No.
21c) Digital A/V meters set/indicators/ selector switches
22OUTGOING:
23a)250 Amp TPN MCCB 50 K including spreader links including spreader links, icu=ics=100% ( Adjustable thermal and Adjustable magnetic release ) Legrand/ Shinider/Semiens / eq. make to be approved by EIC..
24a)160A 4P MCCB 36 KA including spreader links including spreader links, icu=ics=100% ( Adjustable thermal and Adjustable magnetic release ) Legrand/ Shinider/Semiens/ABB / eq. make to be approved by EIC..
25a)100A 4P MCCB 36 KA including spreader links including spreader links, icu=ics=100% ( Adjustable thermal and Adjustable magnetic release ) Legrand/ Shinider/Semiens/ABB / eq. make to be approved by EIC..
26Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor (Havell/Polycab/ Fenolex/ Anchor / eq. make to be approved by EIC..), single core cable in surface/ recessed medium class PVC conduit/duct as required.
27(d)2 X 6 sq. mm + 1 X 6 sq. mm earth wire
28C) 4 X 4 sq. mm + 2 X 4 SQ.MM Earth Wire
29D)4 X 10 sq. mm + 2 X 6 sq. mm earth wire
30e) 4 X 16 sq. mm + 2 X 6 sq. mm earth wire
31Providing and fixing of 6-16mm Cu thimbles duly cramped at cable ends.
32Supplying and fixing of following sizes of medium class PVC conduit/Channel/duct( Anchor/ Ravindra/ eq. make to be approved by EIC.)along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required, complete.
33S/L , testing and commissioning of PVC XLPE insulated alluminium armoured cable 650 V/1100 V Grade as per IS 7098 (Part 1) 1988 with upto Date Amendments.Havell/Eq. standard make as directed by engineer incharge and making end termination with brass compression gland and aluminium lugs of required size.
34a)240 sq.mm 3.5 core
35b)50 sq.mm 3.5 core
36b)35 sq.mm 3.5 core
37Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board,( legrand/ Scheinider/Hager / eq. make to be approved by EIC.) 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earth bar,din bar, interconnections, powder painted including earthing etc.as required. (But without MCB/RCCB/Isolator)
386 way, Double door ( 18+4)
39Providing and fixing of following protection equipments and other allied accessories including connections, inter connections, with suitable size of PVC insulated copper conductor cable including earthing etc. as required.
40a)100A 4P MCCB 36 KA including spreader links including spreader links, icu=ics=100% ( Adjustable thermal and Adjustable magnetic release ) Legrand/ Shinider/Semiens/ABB / eq. make to be approved by EIC..
41Wiring for light point/ fan point/ exhaust fan point/ call bell point with 2X 1.5 sq.mm FRLS PVC insulated copper conductor ( Havells lifeguard/Salzer/ Fenolex/polycab green/ equivalent as directed by engineer incharge.) single core cable in surface / recessed medium class PVC conduit( Anchor/ Polycab /Ravindra/equivalent make as directed by engineer incharge.)( Excluding the cost of conduit), with modular switch ( Anchor roma plus/Legrand Mylinc /SSK NV/schneider Zencelo /Crabtree athena / eq. make to be approved by EIC..), modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
42Wiring for light/ power plug with 2X4 sq. mm + 1X 4 sq. mm earth wire , FRLS PVC insulated copper conductor ( Havell/Salzer/ Fenolex/ equivalent as directed by engineer incharge.) single core cable in surface/recessed medium class PVC conduit ( Anchor/ Polycab /Ravindra/equivalent make as directed by engineer incharge.) ( Excluding the cost of conduit)
43Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. Modular Switch & Socket:- ( Anchor roma plus/Legrand Mylinc /SSK NV/schneider Zencelo /Crabtree athena / eq. make to be approved by EIC..)
44Wiring for 6- 10 amp power plug/ lighting ckts/ inverter ckts with 2X2.5 sq. mm FRLS PVC insulated copper conductor ( Havell/Polycab/ Fenolex/Anchor/ equivalent as directed by engineer incharge.) single core cable in surface/recessed ( Excluding the cost of conduit) alongwith 1 No. 2.5 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
45Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings). Modular Switch & Socket:- ( Anchor roma plus/Legrand Mylinc /SSK NV/schneider Zencelo /Crabtree athena / eq. make to be approved by EIC..)
46Supplying & fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required.
47Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
48Supply installation testing and commissioning of 18 W + LED Surface/recess, square or round Mounted light luminary fitting shape with minimum system lumen efficacy of 100 lm/W with Pressure Die cast Aluminium body and Heat Sink and P.F.>0.95 ,THD<10% ,CCT 5700K, CRI 80.The LED with Useful life of 50000 Hrs at L70, seperate driver, heat sink, earthing provision.. The Input voltage range shall be 150V to 270V .The Fixture should have In-built Surge Protection of 2kV. Certification:- LM79 & LM80 test report should be from govt approved In-house NABL lab/ government of India. The job includes AMC (reckoned from date of successful commissioning) of lighting fixtures for a period of Two years ,which includes replacement of fixtures of Philips/ Havell/ Helonix /Wipro/ eq. make. sample to be approved before installation..
49S/F testing and comm. Of 36 W + 4 ft. wall mounted LED batten with powdered coated aluminum housing & integrated electronic driver with minimum system lumen efficacy of 100 lm/W with THD<10%.( commercial series) CCT 5700K, CRI 80.The LED with Useful life of 50000 Hrs at L70, seperate driver, heat sink, earthing provision.. The Input voltage range shall be 150V to 270V .The Fixture should have In-built Surge Protection of 2kV. Certification:- LM79 & LM80 test report should be from govt approved In-house NABL lab/ government of India. The job includes AMC (reckoned from date of successful commissioning) of lighting fixtures for a period of Two years ,which includes replacement of fixtures of Philips/ Trulux /Wipro/ eq. make. sample to be approved before installation..
50Supply installation testing and commissioning of 36 W + ( 2 ftx2 ft) LED Surface/recess, square or round Mounted light luminary fitting shape with minimum system lumen efficacy of 100 lm/W with Pressure Die cast Aluminium Heat Sink and P.F.>0.95 ,THD<10% ,CCT 5700K, CRI 80.The LED with Useful life of 50000 Hrs at L70, seperate driver, heat sink, earthing provision.. The Input voltage range shall be 150V to 270V .The Fixture should have In-built Surge Protection of 2kV. Certification:- LM79 & LM80 test report should be from govt approved In-house NABL lab/ government of India. The job includes AMC (reckoned from date of successful commissioning) of lighting fixtures for a period of Two years ,which includes replacement of fixtures of Philips/Havell/Helonix /Wipro / eq. make. sample to be approved before installation..
51Supply installation testing and comm. of flood light 100 W ( warm, white ), Epoxy powder coated die-cast aluminium housing (LM24) with elegantly designed heat sink for efficient thermal management, sturdiness & excellent corrosion resistant. PG9 gland is used for cable entry and provision for loopin-loopout class 1, IP66, IK 07, , with high power LED's as light source with Built-In Potted IP67 electronic LED driver with APFC,lower THD, toughned glass and secondary lens,Open Circuit Protection, Over Voltage Protection, Surge Voltage Protection upto 10kV With Built In SPD & other safety test as per IS 15885 Part-2/Sec 13, IEC60598-1. Preferred make: Philips/ Havell /Wipro/Crompton / eq. make to be approved by EIC.. the job also includes the angle iron stand of suitable size to be grouted in cement concrete with hold fasteners complete job.
52Supplying and fixing of following rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. legrand / Schinider/ L&T ./equivalent make as directed by engineer incharge.
53a) 6-32 Amp SP MCB
54b) 40-63amp DP MCB
55c) 40-63amp TPN MCB
56Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) including bends, Tees, cross members and allied accessories with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
57225 mm width X 50 mm depth X 1.6 mm thickness
58Providing of Chemical earthing as per IS standards by way of digging 2.5 mt. deep pit ( 3ft x 3ft) then embedding 2 meter copper bound G.I Earthing electrode , 80mm dia. connecting the electrode with main control board by copper wire/ strip ( to be paid seperately) Full thread brass nut and bolt and washers. Refilling of pit with 3 bags ( 20 kg each bag) of chemical compound.complete job. the job also includes the back filling by way of soft soil to enhance the ground resistivity. complete job.
59Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 55165428
AUTHORITY Government Departments
TENDER VALUE 29.36 Lakhs
LAST DATE 04-05-2026
Authority
Authority Name Public Works Department
Work Description Tender for B.O.Q For Construction Of New Server Building At Data Center Premises Bemina, Srinagar/ Infrastructure For Data Center At Srinagar B.W.O Providing 40 Kva Ups, Cabling And Other Allied Works In New Server Building At Kpdcl Data Centre Premises Pdd Complex, Bemina Srinagar
Basic Detail
Tender No NIT No.12//2026-27 Dt/20/04/2026
Bidding Type Tender
Location
City Bemina
State Jammu And Kashmir
Key Dates
Publish Date 20 Apr 2026
Submission Date 04 May 2026
Open Date 05 May 2026
Finance
Tender Value 29.36 Lakhs
Tender Fee 1100
EMD 58733
Exemption Not Available
Document List
9e80ac34-494e-4fa9-9a1b-775cf73b13fd.html
BOQ_999175.xls
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Apr 20, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
May 04, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Completed
May 05, 2026

Bid Opening Date

Technical bids will be opened and evaluated.