| 1 | Taking down carefully from poles cross arms of any size including clamps, nuts, bolts, etc, complete all as specified and directed. |
| 2 | Taking down carefully from poles HT insulators, any type, complete all as specified and directed. |
| 3 | Taking down carefully from poles ACSR conductor, any size, complete all as specified and directed. |
| 4 | Excavation in trenches in soft loose soil including cutting road surfaces n.exc 1.5 mtr wide and n.exc. 1.5 mtr in depth for poles, stay, cable, pipe etc getting out, complete all as specified and directed. |
| 5 | Returning, filling in, including spreading,leveling,watering and well ramming in layers each n.exc 25 cm thick in soft loose soil, complete all as specified and directed. |
| 6 | Removing excavated material n exc. 50mtr and depositing where directed at a level n exc. 1.5 mtr above, the starting point, complete all as specified and directed. |
| 7 | Supply and lay un-reinforced precast concrete cable cover, class HV, type I, flat, size 300 mm x 180 mm x 40 mm laid flat in trenches over the cable with the length of cable cover perpendicular to the direction of cable length, adjacent/abutting each other, complete all as specified and directed. |
| 8 | Material and Labour for Sand cushioning trenches using fine sand to under ground cable, laid in two layers 8cm before laying the cable & 15cm after laying the cable, complete all as specified SSR Part - I and directed.Note: Punned thickness shall be used for measurement. |
| 9 | Material and Labour for cable protection GI tubing light grade fixed long the pole/under road/along the wall of size 80mm bore with necessary clamps, complete all as specified and directed. |
| 10 | Supply and lay in replacement of underground XLPE insulated, screened, PVC bedded galvanised steelstrip or wire armoured heavy duty electric power cable with stranded aluminim conductor 11000 volts Earthed grade of cross sectional area 95 Sqmm 3 core laid in trenches/ducts/through pipes/in floor/road/along the pole etc, complete all as specified and directed. |
| 11 | Material and Labour for end termination kit outdoor Heat shrinkable joint suitable for 11KV cable 95 sqmm 3 core, complete all as specified and directed. |
| 12 | Material and Labour in replacement danger notice plate for HT pole of size 25 cm x 20 cm of 1.6 mm thick mild steel sheet vitreous enamelled white with letters figur and conventional skull and bones \\"DANGER\\" (English, Punjabi and Hindi) in signal red colour and fixed with MS clamps made of 25mm x 3mm MS flat Iron bolts nuts complete all as specified and directed. |
| 13 | Material and Labour for precast cement concrete RCC (1:2:4 type B-1 route indicator of size 150x150x900mm with 8 mm dia steel reinforcement @ 100mm c/c both ways duly engraved \\" HT CABLE/HT JOINT /FEEDER NO \\" with two coats synthetic enamel paint first quality fixd with (PCC 1:3:6) below ground level of size 30x30x300mm, complete all as specified and directed.Note : Quoted unit rate is deemed to be included the necessary cost of excavation, returning filling and removal etc. |
| 14 | Labour for drilling hole under the road with the help of bocki / manually or by machine for crossing GI tubing of any size for cable protection, complete all as specified and directed. Please Enable Macros to View BoQ information |