| 1 | Please Enable Macros to View BoQ information |
| 2 | For Pole Shifting and Height Raising of 33 KV, 11KV, LT-Line and DTR Due to Construction, Widening of Bridges and Roads under PWD E/M Sub Division M-2, Bhopal (Detail Schedule Attached) SECTION 4 BILL OF QUANTITIES (BOQ) General Description of work : For Pole Shifting and Height Raising of 33 KV, 11KV, LT-Line and DTR Due to Construction, Widening of Bridges and Roads under PWD E/M Sub Division M-2, Bhopal 1st Call. P. A. C. 5000000.00 on Electrical SOR 01-01-2024 SOR, Completion period 365 Days (i/c rainy season) Probable Amount of Contract : (Rs. In Figure) :- 5000000.0 (Rs. In Words) :- Fifty Lakh Only SOR Item No. Particulars of Item of Work Unit Rate Quantity Amount (in figure) Amount (in words) Remarks I II III IV V VI VIII IX |
| 3 | Supply & fixing of High Breaking Capacity (HBC) Fuse Links knife (DIN) type as per IS : 13703 : 1993 & IEC : 60269 :1986 with 80 kA breaking capacity of approved make 25.15.1 20 Amp. to 100 Amp Each 212.0 15.0 3180.0 25.15.2 125 Amp to 160 Amp Each 275.0 20.0 5500.0 25.15.3 200 Amp to 315 Amp Each 487.0 34.0 16558.0 |
| 4 | Supply of ISI marked and approved make of moulded case circuit breaker (MCCB) suitable for 3 phase,3 pole, 50 Hz, 415 Volts, AC supply with respective interrupting capacity (KA) at 415 Volts cited against their range standard conforming to IS – 8828 27.1.1 MCCB current rating – upto 63 Amp, 10kA, 3P 415V AC Each 2721.0 5.0 13605.0 27.1.4 MCCB 25kA current rating, 3P -125Amp & 80% -100% adjustable Each 9953.0 3.0 29859.0 27.1.6 MCCB 25kA current rating, 3P -200Amp & 80% -100% adjustable Each 16061.0 5.0 80305.0 |
| 5 | Supply & fixing of High Breaking Capacity (HBC) Fuse Links knife (DIN) type as per IS : 13703 : 1993 & IEC : 60269 :1986 with 80 kA breaking capacity of approved make 25.15.1 20 Amp. to 100 Amp Each 212.0 10.0 2120.0 25.15.2 125 Amp to 160 Amp Each 275.0 12.0 3300.0 25.15.3 200 Amp to 315 Amp Each 487.0 14.0 6818.0 |
| 6 | Supply of ISI marked and approved make of moulded case circuit breaker (MCCB) suitable for 3 phase,3 pole, 50 Hz, 415 Volts, AC supply with respective interrupting capacity (KA) at 415 Volts cited against their range standard conforming to IS – 8828 27.1.1 MCCB current rating – upto 63 Amp, 10kA, 3P 415V AC Each 2721.0 10.0 27210.0 27.1.4 MCCB 25kA current rating, 3P -125Amp & 80% -100% adjustable Each 9953.0 5.0 49765.0 27.1.6 MCCB 25kA current rating, 3P -200Amp & 80% -100% adjustable Each 16061.0 8.0 128488.0 |
| 7 | Supply of XLPE insulated power cable (conforming IS-7098 Part-I) 1100 Volt grade, 1 core/2 core/3½ core/4 core ISI marked with alu. stranded /solid conductor 41.1.1.2 25 sq. mm. Metre 69.0 10.0 690.0 41.1.1.4 50 sq. mm. Metre 109.0 10.0 1090.0 41.1.1.7 120 sq. mm. Metre 223.0 10.0 2230.0 41.1.1.9 300 Sq. Mm. Metre 483.0 10.0 4830.0 41.1.4 Armoured 2 core 41.1.4.3 6 sq. mm. Metre 100.0 10.0 1000.0 41.1.9 4 core unarmoured 41.1.9.2 10 sq. mm. Metre 119.0 10.0 1190.0 41.15.7 Laying of one number armoured / unarmoured power cable 1:1 KV grade of size not exceeding 25 sq. mm in the existing RCC hume/stone ware/G.I. pipe/ DWC Pipe/ surface in existing trench as required. Metre 28.0 13.0 364.0 |
| 8 | Supply and fixing street light with high power LED of 3 to 6 Watt each on existing bracket assembled on single MCPCB and additional unique peanut lens on each LED, system lumens output with efficacy>120 lm/Watt. luminiare having color temp upto 6500K & 50000 hrs. burning life with minimum @ L 70, The colour rendering index of LED light should be more than 70. Luminiare comprises of driver, PF> 0.95 & surge protection 10KV. Housing made of pressure die cast aluminium with heat resistant flat glass, IP65 protection. Submission LM 79-08/IS16106 (2012), IEC60598, IEC61347 i/c connection wire, testing etc. to complete the job. 31.13.3 90Watt, color temp 3000-6500k as required. Each 14173.0 15.0 212595.0 31.13.4 120Watt, color temp 3000-6500k as required. Each 21183.0 10.0 211830.0 |
| 9 | Dismantling of existing steel pole, R.S. Joist, girder with bracket clamp insulator or stay from the cement concrete foundation and making the site clear by refilling the pit to ground level i/c transportation to required destination within township. |
| 10 | Dismantling of existing overhead ACSR, AAAC, GI, conductor and making the site clear i/c transportation to required destination within township. |
| 11 | Supply of support for overhead line RS joist of I.S. standard including drilling of required hole etc. complete as required. 42.2.2 R.S. Joist 175x85 - 19.3 kg/metre Metre 1467.0 1638.0 2402946.0 42.2.6 H - Beam 152x152mm, Std weight 37.1 Kg/Mtr Metre 2843.0 2571.0 7309353.0 |
| 12 | Supplying and drawing all aluminium alloy conductor (AAAC) of approved make conforming to IS 398-1979 Pt. IV, including binding at existing insulator, jointing, jumpering, tearing off, connecting etc. as required including clearing of obstacles (if any) 42.5.3 AAAC 0.075 sq inch (80 sq.mm Al. EQ.)- (Raccoon) Km. 79735.0 9.5 757482.5 42.5.4 AAAC 0.1 sq inch (100 sq.mm Al. EQ.)- (Dog) Km. 104339.0 28.1 2931925.9 |
| 13 | Supplying, drawing and testing of XLPE insulated covered aluminium conductor of approved make, stringing, making off complete with binding at existing insulator, jointing, jumpering, tearing off, connecting etc. as required and clearing of obstacles (if any) etc. 42.7.1 70 Sqmm XLPE 11KV grade Km. 541000.0 7.4 4003400.0 42.7.2 99 Sqmm XLPE 33KV grade Km. 679000.0 4.2 2851800.0 |
| 14 | Supply of approved high-tension XLPE cable (conforming IS-7098/II/85) as per ISI standard single core armoured with alu. solid/stranded conductor ISI marked as required 41.2.1 Single core XLPE cable 11 Kv grade 41.2.1.1 50 sq. mm Metre 302.0 119.0 35938.0 41.2.1.2 70 sq. mm Metre 354.0 160.0 56640.0 41.2.1.5 150 sq. mm. Metre 592.0 120.0 71040.0 41.2.1.8 300 sq. mm. Metre 885.0 80.0 70800.0 |
| 15 | Supplying & drawing/laying of PVC insulated XLPE aerial bunch power cable conductor H2/H4 grade aluminium solid/stranded conforming to IS-14255- 1995, alu. alloy insulated messenger 1100 volts grade cable of approved make in air with necessary material as per specification of required size as mentioned below – 42.90.2 Single core cable(insulated neutral messenger) 42.90.2.4 3x70 sq.mm, 1x16(st. light), 1x35(insulated neutral messenger) P.Mt. 525.0 1250.0 656250.0 42.90.2.6 3x120 sq.mm, 1x16(st. light), 1x70(insulated neutral messenger) P.Mt. 808.0 9550.0 7716400.0 |
| 16 | Erection of RS Joist pole/'H' beam/steel tubular/steel rail pole of length 7 metres but not exceeding 10 metres in cement concrete 1:3:6 (1 cement : 3 core sand: 6 graded stone aggregate 40mm nominal size) base, foundation, muffing including excavation and back refilling etc. as required. |
| 17 | Erection of RS Joist pole/'H' beam/steel tubular/steel rail pole of length exceeding 10 metres but not exceeding 15 metres in cement concrete M-10 (1 cement:3 core sand: 6 graded stone aggregate 40mm nominal size) base, foundation, muffing including excavation and back refilling etc. as required. |
| 18 | Supplying and erection of 11KV (5 KN) polymer pin insulator complete with long steel head G.I. pin, nut, washer etc. as required. |
| 19 | Supplying and erection of 11KV (45 KN) Polymer disc insulator for 11KV overhead lines with galvanized insulator fittings, ball and socket type, and complete with galvanized strain clamp, bolts, nuts washer etc. as required. |
| 20 | Supplying and erection of 33KV (10 KN) polymer pin insulator complete with long steel head G.I. pin, nut, washer etc. as required |
| 21 | Supplying and erection of 33KV (45 KN) polymer disc insulators for 33KV overhead lines with galvanized insulator fittings, ball and socket type, and complete with galvanized strain clamp, bolts, nuts, washers etc. as required. |
| 22 | Supplying and drawing guard wire/earth wire/bearer wire 13 sq mm (4mm. dia) G.I. including stringing, binding at existing insulators or brackets, jointing, jumpering, connecting & cradle etc. as required and clearing of obstacles (if any) |
| 23 | Supplying and erection of stay set complete with 16mm.dia 1.8 metre long stay rod, turn buckle, anchor plate of size 200mm x 200mm x 6.0mm, stay clamp, bow tightener, 7/3.15 dia G.I. stay wire etc. in cement concrete M-10 (1 cement: 3 coarse and: 6 granded stone aggregate 40mm nominal size) foundation including excavation and back refilling etc. as required. |
| 24 | Supplying and erection of stay set complete with 19/20mm.dia 1.8 metre long stay rod, turn buckle, anchor plate of size 300mm x 300mm x 7.5mm thimble stay clamp, bow tightener, 7/4.00 dia G.I. stay wire etc. in cement concrete M-10 (1 cement: 3 coarse and: 6 granded stone aggregate 40mm nominal size) foundation including excavation and back refilling etc. as required. |
| 25 | Supply, fabrication and erection of angle/channel/flat iron fitting for overhead line & sub-station etc such as 'D' bracket, cross arms, top clamp, 'V' cross arms, back/support clamp or other similar work etc. including nut bolts of required size, making holes, fabrication, welding, cutting, etc. and painting with one coat of red oxide paint & two coat of aluminium paint as required as per specification. |
| 26 | Supply & fixing anti climbing device with 2 ply G.I. barbed wire 1 Kg. per pole complete as per MPMKVVCO. Specification. |
| 27 | Supply, laying and fixing of G.I. earth coil of 4mm dia G.I. wire having 120 turns of nearly 50mm dia. and 3 mt. long tail in existing pit duly earthed with pole etc complete as required as per specification. |
| 28 | Supplying and fixing 33/11/0.4 KV enamel coated danger board size 200x250mm with clamp on existing HT/LT structure/poles. |
| 29 | Supplying & fixing of aerial bunch cable accessories suspension clamp i/c required attachment for single core cable of approved make on pole with clamp, necessary material as per specification for required size. |
| 30 | Supplying &fixing of aerial bunch cable accessories tension clamp (dead end) i/c required attachment for single core cable of approved make in air with clamp, necessary material as per specification for required size. |
| 31 | Supplying & fixing of waterproof insulation piercing connector for aerial bunch cable i/c required attachment for single core cable of approved make in air with necessary material as per specification of required size as mentioned below – 42.93.1 Main:16-95sq.mm, tap:1.5-50sq.mm Each 172.0 98.0 16856.0 42.93.2 Main:50-150sq.mm, tap:6-50sq.mm Each 220.0 78.0 17160.0 |
| 32 | Supplying &fixing of spring loaded busbar screwless connector with enclosure of approved make including required clamp, nut, bolt, connection, testing as per specification to complete the job. 42.94.1 Single phase 42.94.1.5 1Ph, 1In+7Out Each 3226.0 175.0 564550.0 42.94.2 Three Phase 42.94.2.3 3Ph, 1In+6Out Each 7276.0 83.0 603908.0 |
| 33 | Shifting, erection, & commissioning of 100/200/315/500 KVA (11/0.433 KV) distribution transformer on existing structure including Bi-metallic clamp, ACSR/AAAC Conductor i/c colour code sleeve, for connection from H.T. Line to transformer as required as per specification. 34.4.2 Prima coat over new steel and other metallic surface with red oxide zinc chromide paint complete with supply of material labour etc. including preparation of surface. Per sq meter 76.0 4820.0 366320.0 34.4.3 Prima coat with aluminium paint, brushing complete with material and labour including preparation of surface Per sq meter 96.0 4820.0 462720.0 |
| 34 | Supply & fixing fencing of chain link mesh 100 x 100 mm, 12 SWG GI wire for for D.P. structure electric sub-station switch yard including single post of angle iron size 50x50x5mm, 2.5 mt long should be provided upto 2.00 mt. apart or as required. The panel frame with required angle iron/ flat iron members/cross members including mesh welded in frame panel shall be erected between the posts. The angle iron post shall be erected in cement concrete M-15 (1:2:4) (20 mm graded metal) foundation, including excavation of pit and refilling the same. The fencing shall be provided with one entrance gate including locking arrangement as required as per specification. The height of fencing shall be 2 mt. above ground level. Fencing shall be painted with required shade. |
| 35 | Supply, fixing, testing & commissioning wall/floor mounted LT panel primer coated with powder coated paint & provided with required gasket for dust/vermin proof with degree of protection IP42 suitable for 415Volt 3 phase, 50 Hz, 4 wire system fabricated out of CRCA sheet upto 2 mm thick (1.6 mm for doors) duly compartmentalized for incomer, bus section, outgoings, cable alleys & CT, PT Ampere Metre, Volt Metre, selector switches, frequency Metre, phase indicating lamp, Energy Metre complete including cost of busbar supports, detachable cable gland plates, 2 earthing terminals, internal wiring & fixing of separately supplied MCBs, MCCBs, ACB, panel mounted changeover switch/SFUs, etc. as required but excluding cost of busbar strips, Ampere Metre, Volt Metre, selector switch as per approved design & specification |
| 36 | Supply and fixing of LT panel accessories of approved make in existing LT panel including connections etc. as required as per specification. 29.28.1 Digital Ampere Metre with CTs with selector switch P.SET 2125.0 8.0 17000.0 29.28.2 Digital Volt Metre with selector switch & HRC fuse P.SET 2398.0 8.0 19184.0 29.28.5 Copper bus bar strips with PVC sleeves Kg 788.0 25.0 19700.0 29.28.6 Aluminium bus bar strips with PVC sleeves Kg 284.0 110.0 31240.0 29.28.7 LED lamp indicator Each 255.0 32.0 8160.0 |
| 37 | Supplying and erection of single piece nonlinear resistor type lighting arrestor (set of 3 nos) for 3 wire, 11KV overhead lines/sub-station with rated voltage of 9KV (rms) with a nominal discharge current rating of 5 KA and complete with galvanized clamping arrangement, G.I. bolts, nuts, washer etc. as required. |
| 38 | Supplying and erection of single piece non-linear resistor type lightning arrestor (set of 3 nos) for 3 wire, 33KV overhead lines/sub-station with rated voltage of 30KV (rms) with a nominal discharge current rating of 5 KA and complete with galvanized clamping arrangement, G.I. bolts, nuts, washer etc. as required. |
| 39 | Supplying installing, testing & commissioning of outdoor H.T., AB switch assembly set gang operated with brass contact parts, including required GI pipe operating rod, handle & locking arrangement on On-Off position conforming to IS complete with required material and installing on existing DP structure to complete the job as required as per specification.(Set of 3 nos.) 42.62.1 11 KV, 400Amp set 8989.0 12.0 107868.0 42.62.2 33KV, 600Amp set 31525.0 4.0 126100.0 |
| 40 | Supplying installing, testing & commissioning D.O. fuse assembly with brass part contact for 33 or 11/0.4 KV DP Structure set of 3 Nos. with fuse barrel i/c required fuse element & other materials as per specification on existing D.P. structure as required. 42.63.1 11KV set 4721.0 12.0 56652.0 42.63.2 33KV set 16000.0 2.0 32000.0 |
| 41 | Earthing with G.I. earth pipe 4.5 metre long and 40 mm dia with masonry encloser in cement mortar, cover plate having locking arrangement on the top etc. (but without charcoal or coke and salt) complete as required |
| 42 | Add extra for using salt and charcoal/coke for pipe earth electrode as required including excavation & refilling 37.2.1 Excavation 4.5 m by manual labour Each 1942.0 52.0 100984.0 |
| 43 | Providing and fixing 25mm X 5mm G.I. strip on surface or in recessed for connection etc. as required |
| 44 | Providing and erection of hot dipped galvanized octagonal poles in single section made from 3mm thick sheet having lockable weather proof flush door junction box, suitable size & type of foundation bolts 4 nos. 'J' type (EN8 grade) complete, erected in an approved manner on provided foundation. 42.98.5 7 meter height, 130 X 70mm A/F, 220x220x12mm base plate having weight 60 kg ± 3%, 4 nos. X 20 x 700mm bolt having weight 7.7 kg ± 3%. Each 9863.0 20.0 197260.0 |
| 45 | Providing and fixing of sword canopy type single arm GI bracket upto 2 meter Long for 70mm A/F top octagonal pole |
| 46 | Providing and fixing of sword canopy type double arm GI bracket upto 2 meter Long for 70mm A/F top octagonal pole |
| 47 | Designing & casting of open raft shallow footing foundation with M-20 cement concrete suitable for 12.5meter High Mast considering the safe soil bearing capacity at site as 10 T/sqm at 2meter depth including excavation, foundation nut bolts in an approved manner as per manufacturer drawing or Engineer-in-charge. |
| 48 | Supply, installation, testing & commissioning of LT trivector energy meter, DLMS compliant category-A (for substation/feeder metering) , 3 phase 4 wire, 440 Volts, 5 Amp, accuracy class 0.5S with GSM(GPRS compatible) modem suitable for required C.T. 5A duly tested from electricity board with uPVC box . TOTAL 50,00,000.00 Executive EngineerPWD E/M Division No. 1, Bhopal |