| 1 | Supply, installation, testing and commissioning of Split air conditioning unit 1.50 TR (INVERTER TYPE) capacity with HD filter complete with cordless remote control, minimum 5 star labelled,latest energy efficient model eco friendly refrigerant gas,4500 Kcal/Hr,50 Hz,240 volts,air cooled condenser with all accessories varied speed including fixing the outdoor unit on outdoor wall mounting brackets or on stand on terrace as per site requirement and fixing of room(high wall) unit on wall with necessary wall cutting/making hole(core cutting) to pass the refrigerant pipes,drain pipes,cables etc and making good to match with existing finishing complete,providing and making indoor to outdoor communication cable & copper tube connection upto a distance of 3 mtrs as provided by OEM, power cablling (Max 3.0 mtrs from enclosure) to unit, first charging of refrigerant gas including cordless remote, providing drain piping of suitable size from unit upto ground level with proper clamping to wall and covering both drain and rerfrigerant tubes, communication cables through casing capping of minimum size 100X50 mm or as per site requirement inside the room complete all as specified and directed.Make: LG, Daikin, Hitachi, Blue Star |
| 2 | Note for Sl item No 1.00:-1) The ACs are to be installed in Server rooms equipped with many sophisticated electronic equipments. The rooms are located in different units of MIC&S. Shutdown/ work time permission shall be obtained from the office before starting the work. The contractor shall required to pause the work and resume as per site requirements and complete shut down of the equipments will not be permitted. 2) Due care shall be ensured during the installation work. The wall and floor to be covered with protective sheets to prevent scratches and damages. Dust and debris to be removed properly with vacuum cleaner after completion of work. After work, wall/ panels to be repaired/ replaced and to be match with existing surfaces.3) The entire work shall be carried out in presence of a qualified supervisor.The Contractor shall visit the site before bidding to check and understand the site feasibilty. No claim shall be entertained on this account after quoting of the tender. |
| 3 | Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 3.0 KVA suitable for inverter type AC complete all as specified and as directed. Makes :- Automatic electrical (AE) / Vinitec / APLAB / V Guard / Volina |
| 4 | S&F Copper tubes (size 1/4 inch for liquid line and 1/2 inch for suction line or as per OEM recommendation) including nitrile rubber insulation suitable for 1.5 Ton inverter Split AC including necessary fittings/clamps for fixing on wall and connection to outdoor/indoor units complete leak test as per OEM and all as directed.Note: Suction pipe, discharge pipe with nitrile rubber insulation together shall be measured as one unit. |
| 5 | Taking down carefully by disconnecting and unscrewing from boards/outlet boxes,electric meter from any location and sizes and depositing to MES store yard,maintaining proper records,reading of OLD meters,ser no, date and time of removal and submitted to AGE E/M office complete all as specified and directed. |
| 6 | M & L for sub main wiring with 2 runs of 6 sqmm, single core, PVC insulated & unsheathed FRLS cable conforming to IS-694, 1100 volts with copper conductor, multi stranded drawn in and including suitable size heavy grade casing caping (ISI marked) with all accessories such as Tees, Elbows, junction box, reducers etc as requied alongwith one run of 6 sqmm single core PVC insulated & unsheathed FRLS copper conductor as continuos earth wire dolly and connecting to existing main switch board / distribution board of each building / qtr as ordered and testing on completion including taking down old submain wiring and any type of conduit complete all as specified and as directed. NOTE: 1.Proper colour coding shall adopted for wiring (for phase-RED,YELLOW,BLUE for Earth-Green and Neutral-Black)2.Three runs of 6 sq.mm cable and one run of PVC casing & caping shall be measured as one unit.3.The item has been considered for connecting submain wring from MCB to meter/as per site reqiurements and direction of Engr-in-charge. |
| 7 | S&F in repairs, MCB SP, AC 240 V, 6 to 32 Amps, 10 KA capacity ,'C' series, making connection with suitable size of copper lugs etc complete all as specified and as directed. |
| 8 | S&F in repairs, MCB SPN, AC 240 V, 6 to 32 Amps, 10 KA capacity ,'C' series, making connection with suitable size of copper lugs etc complete all as specified and as directed. |
| 9 | S&F in repairs, sheet metal enclosure (Factory made), double door shutter type for distribution board (when MCBs are to be used), Tripple pole and neutral, 415 volts, 4 way, protection class IP-42, suitable for fixing MCBs, Isolators etc, confirming As per IEC 61439-3, suitable for flush mounting and surface mounting, with 100 Amps rated copper busbar, with Neutral bar, Earthbar and cable alley for cable managment, fully shrouded, Neutral bars, prefittes masking sheet complete all as specified and as directed. |
| 10 | S&F in repairs ISOLATOR TPN, AC 415 V, 63 amps, 10 KA capacity ,'C' series, making connection with suitabl size of copper lugs etc complete all as specified and as directed. |
| 11 | Supply and fix electronic energy meters tamper proof with LCD display and polycarbonate cover 230 V, 10-60Amp, accuracy class-I 50Hz, conforming to IS 13779, IP-54, with parameters to show data, time, current reading, PF, voltage and KWH complete all as specified and as directed.Make: L&T Model EM101+ Cat no:WM101BC7DDH or equivalent model of makes specified. |
| 12 | Excavation in trenches by manual/ mechanical means (Hydraulic excavator) not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying of pipe, foundation etc. or for Shafts, wells, cesspits, manholes, pier holes, etc not exceeding 10 Sq m on plan, including dresssing of sides and ramming of bottoms, lift upto 1.5 m, including getting out in any type of soil (soft/hard/dense soil) and disposal of surplus excavated soil to a distance not exceeding 50 m complete all as specified and as directed. |
| 13 | Returning, filling in excavated material (soil) including spreading, levelling, watering and well ramming in layers not exc 25 cm all as specified and as directed. |
| 14 | Dismantling of ACSR or AAC conductors of any size and any description from any height/ poles or any location complete all as specified and as directed by Engr in Charge. |
| 15 | Dismantling of Unserviceable LT insulators Pin/ shackle/ Disc & loop type from existing OH lines complete all as specified and directed by Engr in Charge. |
| 16 | Dismantling of unserviceable steel structure such as cross arms, bracings, supports, clamps etc from LT pole of any type/shape complete all as specified and directed. |
| 17 | Dismantling old existing LT stay assembly all as specified and as directed. |
| 18 | Taking out existing LT UG XLPE cable of any size and type from trenches/poles etc, alongwith protection covers all as specified and as directed. |
| 19 | Supply and laying Double Walled Corrugated (DWC) HDPE pipe of nominal bore 50mm including 90 degree bends with coupler and rubber ring, conforming to IS :16205 Part 24 Type 450N, laid in trenches for cable protection complete, all as specified and as directed. |
| 20 | Supply and laying in trenches or fixing or passing through pipe, 1100 Volts grade, armoured, heavy duty LT UG cable of size 50 Sqmm, 3.5 core with XLPE insulated stranded aluminium conductor including cable gland, lugs, testing and commissioning complete all as specified and as directed. |
| 21 | Supply and laying in trenches or fixing or passing through pipe, 1100 Volts grade, armoured, heavy duty LT UG cable of size 25 Sqmm, 3.5 core with XLPE insulated stranded aluminium conductor including cable gland, lugs, testing and commissioning complete all as specified and as directed. |
| 22 | Supply and laying in trenches or fixing or passing through pipe, 1100 Volts grade, armoured, heavy duty LT UG cable of size 10 Sqmm, 3.5 core with XLPE insulated stranded aluminium conductor including cable gland, lugs, testing and commissioning complete all as specified and as directed. |
| 23 | Supply, install, testing and commissioning in replacement, factory made and tested (including CPRI type tested certified) LT feeder pillar box (KIOSK) out door type, floor mounted, compartmantalised and IP-54 suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber with insulated Aluminium bus bars 150 amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 50x50x6mm angle iron , powder coated, Front and rear opening type with aprons for cable entry with double door shutter and locking arrangement with including cable gland, lugs, jointing material etc and jointing, connecting, testing and commissioning and including items/ accessories given below :- (Notes :The rate quoted shall include for Cost of dismantling/ taking down old unserviceable LT feeder piller, earth work & excavation for angle iron frame for foundation of panel board upto 0.50 m below GL in any type of soil & PCC (1:4:8), D2 filling in foundation the ground clearance of panel board shall be 0.40 m GL to the bottom of panel board ). |
| 24 | Incoming: (a) MCCB 100 amps, 4 pole, 25 KA with adjustable thermal release, 50 Hz, 415 volts grade - 01 No. (b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 250 Amp, 4 pole, not less than 60cm long mounted on insulators for incoming supply-01 No.(c) Digital volt and ammeter with selector switch and CT's set - 01Set. (d) Neon indicating lamps (R, Y & B) -01 Set Outgoing: (a) MCB 40 amps, 2 pole, 16 KA with adjustable thermal release, 50 Hz, 415 volts grade - 15 No. |
| 25 | Supply, install, testing and commissioning in replacement, factory made and tested (including CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted, compartmantalised and IP-54 suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber with insulated Aluminium bus bars 150 amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 50x50x6mm angle iron , powder coated, Front and rear opening type with aprons for cable entry with double door shutter and locking arrangement with including cable gland, lugs, jointing material etc and jointing, connecting, testing and commissioning and including items/ accessories given below :- (Notes :The rate quoted shall include for Cost of dismantling/ taking down old unserviceable LT feeder piller, earth work & excavation for angle iron frame for foundation of panel board upto 0.50 m below GL in any type of soil & PCC (1:4:8), D2 filling in foundation the ground clearance of panel board shall be 0.40 m GL to the bottom of panel board ). |
| 26 | Incoming: (a) MCCB 100 amps, 4 pole, 25 KA with fixed thermal and magnetic setting, 50 Hz, 415 volts grade - 01 No. (b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 250 Amp, 4 pole, not less than 60cm long mounted on insulators for incoming supply-01 No.(c) Digital volt and ammeter with selector switch and CT's set - 01Set. (d) Neon indicating lamps (R, Y & B) -01 Set (e) 3 Phase electronic meters temper proof LCD display with polycarbonate cover 415 V, 10-60Amp, accuracy class-I 50Hz, conforming to IS13779, IP-54, with parameters to show data, time,current reading, load, PF, voltage and KWH Outgoing: (a) MCCB 63 amps, 4 pole, 16 KA with adjustable thermal release, 50 Hz, 415 volts grade - 01 No. (b) MCB 40 amps, 2 pole, 16 KA with adjustable thermal release, 50 Hz, 415 volts grade - 15 No. |
| 27 | Supply, install in replacement and testing out door wheather proof bus bar chamber of size 100 cm x 60cm x 30cm made out of 3.15mm CRCA MS sheet having one side openable hinged door shuter with locking arrangement/provn of two nos 80cm long 40x40x6mm anlge iron legs welded and 04 nos Copper bus bar of 200Amp rating including provision of one MCCB TPN 100 Amp 25 KA for controlling Electric supply complete erected on ground with necessary PCC 1:3:6 type C2 foundation complete bus bar chamber painted with two coats of approved enamel paints over one coat of primer including making cable connection with necessary gland , lugs/thimbles complete all as specified and as directed. |
| 28 | M&L in repairs/replacement earthing complete with galvanized steel earth plate electrode 60 cm X 60 cm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below ground level, connecting with GI strip of size 25mm x 4 mm, by means of nut bolts, check nuts and washer and the GI Earth strip connected upto main earth point/DBs alongwith 32mm dia GI medium grade protection pipe including provision of concrete pit in PCC (1:2:4) type B-1 using 20 mm graded stone aggregates with 40 mm thick RCC (1:2:4) cover with reinforced with XPM (weight not less than 4 Kg / Sqm) and frame of angle iron 25mm X 25 mm X 3mm with lugs 2 Nos and with 6 mm dia MS bar handle made to shape, |
| 29 | with GI light grade 20 mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate, common salt and charcoal filling, test point made out of phosphorus bronze with fixing arrangement, funnel, wire mesh and earth work in hard/dense soil, returning filling in and removal of surplus soil to a distance not exceeding than 50 mtr, all as per electric plate No 3 of SSR Part I 2009 and connection to earth test point all as specified including testing on completion. Note : Rate of GI earthwire and GI protection pipe upto 7.5 mtr length shall be deemed to be included in this item. Please Enable Macros to View BoQ information |