| 1 | SCHEDULE 'A' PART-I (BUILDING WORKS)Material and labour for construction of 50000 ltr capacity underground water sump complete all as specified & shown on Drg No STD-1394 Sh 1/1. |
| 2 | Material and labour for construction of drain full brick with width upto 0.60m & depth upto 1.00m complete all as specified & shown on Drg No 1234(C) . |
| 3 | Material and labour for construction of desilting tank of size 8.75x2.30x2.65m deep as per drg no TD-1320 (C) complete all as specified and directed. |
| 4 | Excavating over areas, n exc 1.5 m deep and getting out in soft/loose soil complete all as specified and directed. |
| 5 | Removing excavated material n. exc 50m & depositing where directed at a level n. exc 1.5m above starting point complete all as specified and directed. |
| 6 | Material and labour for Stone pitching laid dry hand packed tightly and grouted with cement & sand mortar 1:6 & packed tightly on ground complete all as specified and directed. |
| 7 | Material and labour for PCC (1:4:8) type D2 (40 mm graded mechanically crushed stone aggregate), 75 mm thick laid below stone pitching complete all as specified and directed. |
| 8 | Excavation in post holes (or similar holes) each n.exc 0.50 Cum, getting out in soft/loose soil, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exc 25 cm, watering and removing surplus soil to a distance n exc 50m and making good surface complete all as specified and directed. |
| 9 | Material and labour for PCC 1:4:8 type D-2 using 40mm graded mechanically crushed stone aggregate as in foundation complete all as specified and directed. |
| 10 | Supply and fixing of framed work such as grills, gratings, etc.. with ends of bars shouldered and/or riveted, or forged into spikes; framed guard bars; barred iron doors; ladders; framed balusters; walk ways; railings; framework of water tanks and similar work conforming to Fe.290.Gde-E-16 complete all as specified and directed. |
| 11 | Material and labour for preparation of new steel surfaces of any description over 10cm in girth or width & applying two coats of synthetic enamel paint over a coat of red oxide primer etc complete all as specified and directed. |
| 12 | Material and labour for Construction of plateform suitable for 20 KVA DG set of as per drg no CWE/AMB/TD-01/2026 complete all as specified and directed. |
| 13 | SCHEDULE 'A' PART-II (WATER SUPPLY WORK)Supply and fixing of non clog vertical submersible pumps with chrome CastIron impeller and cutter, non clog to pass 40mm size particles including supply, installation & testing complete with 2 yrs maintenance of 10 HP capacity with 3000 LPM and head up to 29 mtr, electric driven, 415 V, TP suitable for UG Sump and connected with 100mm dia GI flanged pipe with fittings,strainer etc complete incl fixing arrengement of pump in sump and vertical pipe alongwith sump complete all as specified and directed. |
| 14 | Supply and fixing of flat 10 Sqmm 3 core PVC insulated & PVC Sheathed copper cable 1100 volt, confirming to IS 694 for submersible pump complete all as specified and directed. |
| 15 | Supply, lay and testing of ductile iron pipe Class K-7, 150mm (6'') dia spigot and socketed including suitable size of rubber gasket/ tyton joint as per IS 8329 all as specified and directed. Note :- Tenderer to visit the site and be conversent with the route of DI pipe. Any damages to underground cable LT,HT cable, telecommunication cable,fibre cable etc shall be repaired / replaced / joint within 24 Hrs to avoid any disruption to services.This aspects should be consider by quoting unit rate of item. |
| 16 | Supply and fixing of DI fittings for 150mm spigot and socketed/ flanged pipes bends, Tees, (any type, redius and angle) tapers any type (straight, bend increasing, decreasing or double socket etc) Tee pieces single branch, cross (all sockets or socket and spigot) collars, caps and plugs as per IS 9523 incl suitable size of gaskets and nut bolts for fixing complete all as specified and directed. |
| 17 | Supply and fixing of flanged GI pipe medium grade pipe 100 mm dia as per IS 1239 ( Pt I & II ) including all fittings and fixed complete to walls and ceiling or laid in floors complete all as specified and directed. (from UG sump submersible pump to outside sump NRV. |
| 18 | Excavation in trenches, n. exc 1.5 m wide and n. exc 1.5 m in depth for foundation etc.and getting out in soft/loose soil for laying of pipe line/ UG cable complete all as specified and directed. |
| 19 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25cm for soft/loose soil complete all as specified and directed. |
| 20 | Removing excavated material n.exc 50m and depositing where directed at a level n.exc 1.5 m above the starting point complete all as specified and directed. |
| 21 | Material and labour for cutting of road /hard standings of any type/size at site for laying of UG cable/GI pipe not exc 45 cm wide and n.exc 60 cm depth including making good the disturbed/broken surfaces of road/hard standing with matching to existing concrete & stone blocks as per direction complete all as specified and directed. |
| 22 | Supply and fixing of dual plate CI wafer type reflux valve/NRV PN1.6 suitable for 150mm bore (8'') dia complete all as specified and directed. |
| 23 | Supply and fixing of CI sluice Valves, flanged type with stainless steel spindle of class PN 1.6 as per IS 14846 of 150 mm (6”)dia including suitable size of gasket and nut blots for fixing complete all as specified and directed. |
| 24 | Supply and fixing of Air release valve suitable for 150mm bore (6'') dia complete all as specified and directed. |
| 25 | SCHEDULE 'A' PART III (EXTERNAL ELECTRIC SUPPLY)Excavation in trenches in any type of soil not exc 1.5 mtrs wide and not exc 1.5 mtr in depth for laying of pipe/ cables/ poles etc and getting out complete all as specified and as directed. |
| 26 | Returning filling in any type of soil including spreading leveling watering and well ramming in layers n.exc 25 cm complete all as specified and as directed. |
| 27 | Removing excavated soils to a distance n.exc. 50 mtr and depositing where directed at a level not exc 1.5 m above the starting point complete all as specified and directed. |
| 28 | Material and labour for laying of fine, clean sand (river sand) free from sharp materials and stone particals in trenches for cushioning of cable 8 cm thick under cable and 15 cm thick over the cable including gently punning complete all as specified and directed. Note:- The total thickness of sand shall be measured 18 cm after punning. |
| 29 | Supply & lay well burnt bricks, sub class B, laid dry abutting each other with gap between adjacent slabs not exceeding 10mm, over underground LT cables for protection complete all as specified and directed. |
| 30 | Material and labour for cutting of road /hard standings of any type/size at site for laying of UG cable/GI pipe not exc 45 cm wide and n.exc 60 cm depth including making good the disturbed/broken surfaces of road/hard standing with matching to existing concrete as per direction complete all as specified and directed. |
| 31 | Supply and laying in trenches XLPE insulated , armoured heavy duty electric cable with aluminium conductore, 1100 Volts grade, cross sectional area 16 Sqmm 4 core complete all as specified and directed. |
| 32 | Material and labour for earthing complete with galvanised steel earth plate electrode of size 600X600X6 mm thick buried directly in ground (earth pit not less than 2.5 meter deep below normal ground level) with top edge of the plate not less than 2.40 mtr below the ground level connected to galvanised iron strip of 32x6 mm as earth lead by means of bolts nuts check nuts & washers of galvanised iron or steel ,surrounded by charcoal of coke and salt, protected by GI pipe 40 mm bore (light grade) and making chamber of PCC (1:4:8) type D-2 using 40 mm graded stone aggregate and coping shall be in PCC(1:3:6) type C-1 using 20 mm graded stone aggregate, 50 mm thick cover of RCC (1:2:4) type B-1 using 20 mm graded stone aggregate, reinforced with 8 mm dia TMT bars @ 80 mm c/c boath ways including excavation and earth work and removal of surplus soil to distance n exc 50 m complete all shown in electrical plate No 3 of SSR part- 2010 complete all as specified and directed. Note:- Note : 1. RCC pit cover shall be pre-cast of RCC (1:2:4) type B-I , 80mm thick reinforced with XPM weighting not less than 4 KG/sqmm in lieu of CI cover.2. Charcoal dust and common salt upto 1.5 meter depth shall be filled in layers of 15 centimeters all around the earth plate inside earth pit . On testing after completion of earthing if desired earth resistance is not achieved , the earthing will be redone at no extra cost to obtain the desired earth values less than 2 ohms. |
| 33 | Supply, installing, testing and commissioning, factory made and tested ,CPRI type tested LT feeder pillar , outdoor type floor mounted , suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and LT panel shall bemounted on angular frame work of 50x50x5mm thick angle iron base frame, and fixed with PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) in foundation for fixing panels, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side opening type, with aprons for cable entry, with double door shutter and locking arrangement and consisting of the following all as specified and consisting of the following(a) Copper bus bar 100 Amps 4 pole - 01 set (b) MCCB 4 pole 63 Amps 16KA adjustable type - 01 No (incommer) (c) MCB TPN 40 A - 03 No (for pumps and spare)(d) Changeover switch 63 amps on load type 4 pole-01 No (e) Digital volt meter 0-500 V with selector switch - 01 No (f) Digital Ammeter 0-100Amps with selector switch - 01 No(g) Set of 3 phase RYB indicator - 01 Set (e) Star delta starter suitable for 10-15 HP submersible pump incl overload relay,auto timer with necessary electic wiring - 02 No (for Sump 1 & 2)(ii) Internal wiring with suitable size of PVC insulated stranded copper conductor cable (ISI marked FRLS, make appropved by MES) duly crimped with copper lugs & ferruled and aluminum strips for MCCB's. (iii) Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 mm thick in foundation, brick work in CM 1:6 with sub class B old sized bricks, renderung 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 1.25 meter above the nearest ground level. |
| 34 | Supply of Manufacturer or OEM (Original Eqpt Manufacturer) manufactured and tested static Diesel Engine driven generating set LIQUID COOLED capable of delivering 20 KVA ,or nearest higher rating 415 volts (AC 3 Phase, 4 wire system of supply), 50 Hz at power factor 0.8 minimum. The DG set shall consist of a diesel engine coupled through flexible coupling to a matching alternator, and mounted on Dunlop metallastik foundation pads on a common base frame and thereafter installed in the CPCB approved Acoustic enclosure (the complete set conforming to and test certified as per CPCB norms and as specified) with , fuel tank with mounting arrangement and inlet, outlet, return oil arrangement, exhaust pipe complete and shall comprise of the following: - (a) ENGINE (PRIME MOVER): Diesel engine 1500 RPM, of suitable HP as recommended by manufacturer liquid cooled, 12 volts DC electric battery start, complete with fly wheel and all standard fittings/ fixtures as per manufacturing practice including suitable engine control panel with tachometer, lub oil temp & pressure gauges, water temp gauge, and also including self starter, dynamo, fuel tank etc. (b) ALTERNATOR : AC alternator, self excited, self regulated, self ventilated, brushless design, conforming to BS 2613 / 5000, 3 phase , 415 volts, 4 wire for output PF 0.8, at 1500 RPM, insulation class ‘H’; Enclosure IP 23 / TEFC complete with AVR with + 1 % voltage regulation, directly coupled to and match the above engine. ( c) DG set shall be CPCB IV+ Norms compliance developing 25.5 BHP @ 1500 RPM Directly coupled with 20 kVA Alternator rated at 3 Phase 415 Volts ,50 Hz and 0.8 p.f. both mounted and Aligned on Common Base Frame complete with inbuilt MS Fuel Tank, Exhaust Silencer, AVM pads fitted on Base Frame 1 No's Battery of suitable capacity for 12 Volts Operating System, and Integrated Manual Panel with feature of Auto Start and Auto stop all housed in Acoustic Enclosure. Please Enable Macros to View BoQ information |
| 35 | Supply of Manufacturer or OEM (Original Eqpt Manufacturer) manufactured and tested static Diesel Engine driven generating set LIQUID COOLED capable of delivering 20 KVA ,or nearest higher rating 415 volts (AC 3 Phase, 4 wire system of supply), 50 Hz at power factor 0.8 minimum. The DG set shall consist of a diesel engine coupled through flexible coupling to a matching alternator, and mounted on Dunlop metallastik foundation pads on a common base frame and thereafter installed in the CPCB approved Acoustic enclosure (the complete set conforming to and test certified as per CPCB norms and as specified) with , fuel tank with mounting arrangement and inlet, outlet, return oil arrangement, exhaust pipe complete and shall comprise of the following: - (a) ENGINE (PRIME MOVER): Diesel engine 1500 RPM, of suitable HP as recommended by manufacturer liquid cooled, 12 volts DC electric battery start, complete with fly wheel and all standard fittings/ fixtures as per manufacturing practice including suitable engine control panel with tachometer, lub oil temp & pressure gauges, water temp gauge, and also including self starter, dynamo, fuel tank etc. (b) ALTERNATOR : AC alternator, self excited, self regulated, self ventilated, brushless design, conforming to BS 2613 / 5000, 3 phase , 415 volts, 4 wire for output PF 0.8, at 1500 RPM, insulation class ‘H’; Enclosure IP 23 / TEFC complete with AVR with + 1 % voltage regulation, directly coupled to and match the above engine. ( c) DG set shall be CPCB IV+ Norms compliance developing 25.5 BHP @ 1500 RPM Directly coupled with 20 kVA Alternator rated at 3 Phase 415 Volts ,50 Hz and 0.8 p.f. both mounted and Aligned on Common Base Frame complete with inbuilt MS Fuel Tank, Exhaust Silencer, AVM pads fitted on Base Frame 1 No's Battery of suitable capacity for 12 Volts Operating System, and Integrated Manual Panel with feature of Auto Start and Auto stop all housed in Acoustic Enclosure. Please Enable Macros to View BoQ information |