| 1 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. (but without charcoal/ coke and salt ) as required. |
| 2 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 3 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 4 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Upto 35 sq. mm |
| 5 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Upto 35 sq. mm |
| 6 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 7 | Supplying and fixing of light class G.I. pipe of 50 mm dia. (nominal) 3 metres length along the pole for protection of under ground cable as required |
| 8 | Providing and laying of HDPE pipe of 40 mm outer dia with PN 4 rating by hand moling/ manual method confirming to IS 4984. |
| 9 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-2C X 6 sqmm |
| 10 | Providing and fixing Stainless steel name plate of size 6×8 sq inch made of 20 gauge sheet including engraved name of area representative duly painted along with SS clamp nut bolt etc as required. |
| 11 | Providing and fixing name board made of MS sheet 90 x 60 CM , 1 mm thick with frame of MS angle 50 x 50 x 6 mm, two diagonal braces at the back of sheet of MS flat 40 x 6 mm, total height of the board above ground level 2.40 mtr, lenght of legs below ground level 0.30 mtr embedded in CC block 1 : 2 : 4 (1 cement : 2 coarce : 4 graded aggregate 20 mm nominal size) 30 x30x45 cm encluding excavation and removal of surplus earth with in 50 m lead, applying priming coat of approved steel primer, painting with synthetic enamel paint of approved quality and lettering with enamel paint of approved colour (one side) as per drawing/direction of Engineer-in- charge. |
| 12 | Fabrication, Supplying, Installation, testing, Commissioning of 12 metres semi high mast System with its accessories, Mast shaft shall be in one section, hot dip galvanized 4mm thick(Single dip) Inside & out sides &suitable for wind velocity as per IS 875 part3.There shall be in longitudinal seam weld per section and No circumferential weld. It should also included accessories For seml High Mast head frame,2 point suspension system,5 X 2.5 sqmm Copper conductor with steel wire rope 5mm dia. (7/19 construction) single drum winch ,galvanized lantern carriage arrangement suitable for 4/6 Nos. Flood Light luminaries symmetrically and its control gears boxes and lighting finial, the mast shall have integral type manual tool mounted at the base compartment of its raising and lowering operation with foundation bolts and Anchor plate and control panel housing suitable RCC (1:2:4) shallow foundation of size 1m(L) x 1m wide and 2m deep i/c excavation of earth, providing cutting, bending and placing in position, reinforcement of cold twisted bars of 12 mm dia -2100mm long (approx.) - 16 nos.and reinforcement of cold twisted bar of 8 mm dia 3700 mm (approx.) 13 nos. (with 150 mm spacing) as required with positioning of foundation bolts and providing DWC HDPE pipe for cable entry & exit as required for the semi high mast considering the safe soil bearing capacity at site as 10T/sqm at 2mts. Depth with all material i/c 4 Nos S.P MCB,1 no. Double pole 16Amp. MCB etc as reqd. Logo/Name of manufacturer shall be either embossed or Rivited plate on the pole. Galvanization as per relevant IS |
| 13 | Supply and fabrication of pole protection system made up of 8 SWG steel wire mesh of size 25mm x 75mm rectangular with 50mmx50mmx6mm MS angle iron for supporting the mesh i/c MV danger plate and grounding the protection system in suitable quality of CC etc as reqd. |
| 14 | Fabrication, supplying and fixing class B galvanised single overhang arm bracket made out of 250mm long galvanised top tube with cap and 1000mm long 32 mm dia galvanised pipe with tightening bolts complete as required |
| 15 | Fabrication, supplying and fixing class B galvanised double overhang arm bracket made out of 250mm long galvanised top tube with cap and 1000mm long 32 mm dia galvanised pipes with tightening bolts complete as required. |
| 16 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 3 x 1.5 sq. mm |
| 17 | Fabrication, supply & erection of 5.0 mtr height, 3 mm thick, bottom dia of 130mm & top dia of 70mm base plate of size 225 x 225 x 12 mm thick flange mounted hot dip galvanized octagonal pole made from HT steel plate, window with flash cover with full verticle window cover at appropriate height from the base plate on existing cement concrete pedestal as required. i/c supplying and fixing of 6 mm thick laminated mounted sheet inside the window and i/c providing and welding 3 nos. GI strips 4 mm thick of suitable length and having suitable size tapped holes as reqd, terminal block suitable for 25 sq mm conductor – 4 nos. & shorting links on DIN channel i/cpdg and fixing DIN channel of suitable length,, 6 Amp. SPMCB ‘C’ characteristics, earth stud, cable support clamp suitable for 4x25 sqmm cable.Logo/Name of manufacturer shall be embosed or rivited plate on the on the pole, galvanization as per relevant IS. code etc as reqd. |
| 18 | Providing and laying in position M25 grade reinforced cement concrete foundation of size 450 mm(L) x 450 mm wide and 1000 mm deep i/c excavation of earth, providing cutting, bending and placing in position, rewinforcement of cold twisted bars of 12 mm dia -960mm long (approx.) - 8 nos.and reinforcement of cold twisted bar of 8 mm dia - 1400 mm (approx.) - 6 nos. (with 150 mm spacing) as required with supplying and positioning of 4 nos foundation bolts of size 16 mm dia and 600 mm long, J type i/c 2 nos template anchor plates of size 225 mm x 225mm x 3 mm and providing 63 mm DWC HDPE pipe for cable entry & exit as required for 3 m and 5 mtr pole |
| 19 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy >135 lm/Watt).Supplying, Installation, Testing & Commissioning of Street light LED fixture, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 deg. C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). 45 Watt that LED junction temperature shall not rise above 90°C) . 45 watt |
| 20 | LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy >135 lm/Watt) Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection,EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement., suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin) , SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink ofaluminium housing such that LED junction temperature shall not rise above 90°C). Please Enable Macros to View BoQ information |