| 1 | Wiring for circuit / submain wiring along with earth wire with the following sizes of PVC insulated copper conductor single core cable in surface/recessed PVC conduit as required. (4 x 4 Sq mm + 2 x 4 sq.mm) |
| 2 | Supplying and fixing of following ways surface/ recess mounting, 230 volts, SPN MCB distribution board of sheet steel, dust protected, duly powder painted, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (but without MCB's and incomer ) as required (8 way), Double door |
| 3 | Supplying and fixing 63 amps \\"D\\" curve, miniature circuit breaker suitable for DC load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. a) Double pole |
| 4 | Supplying and fixing Earth Termination copper Strip of 300 mm length of size 100mm x 5mm thichk, complete as reqd. |
| 5 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required a) 1 x70 Sqmm |
| 6 | b) 4x70 Sq.mm |
| 7 | Supplying of PVC insulated and sheathed armoured 2 core 1.5 sq.mm copper conductor 1.1 KV grade cable and laying the same on surface or in recess as reqd.(BSNL approved make). |
| 8 | Supplying and making end termination with brass compression gland for PVC insulated and sheathed copper conductor cable of 1.1 KV grade of size 2 core 1.5 sq.mm as reqd. |
| 9 | Supplying and fixing of following module, PVC enclosure along with modular base & cover plate for modular switch in recess etc as required (a) 03 module |
| 10 | Supplying and fixing following accessories in the existing Modular enclosure including connections etc as required a) 16 A 1 way modular switch |
| 11 | b) 16 A modular Socket Outlet |
| 12 | Supplying and fixing 2 way, MCB Enclosure, with double pole MCB 16A/32A, 230 V, on surface/ recess, complete including earthing etc. as required. |
| 13 | Supplying and fixing LED type 4 ft light fitting of 20 Watt, 230V, 50HZ, including making all electrical connections with suitable size PVC insulated copper conductor wire etc. as required (M/s Crompton/Havells or SS make) |
| 14 | S/F of 3 phase, 415V, 50HZ, 10-60A capacity digital energy meter including suitable enclosure, wiring the same as sub meter, complete as reqd. |
| 15 | Supplying and fixing of following ways surface/ recess mounting, Vertrical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (but without MCB's and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) = 4 way (4 + 12), Double door |
| 16 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. a) Single pole |
| 17 | Triple pole |
| 18 | Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required [63 amps] |
| 19 | Supplying and making end termination with brass compression gland for PVC insulated and sheathed Alluminium conductor cable of 1.1 KV grade of size 4 x25 sq.mm Al as reqd. |
| 20 | Supplying and Laying 4 core 25 sqmm aluminium conductor armoured cable from electriciy pole to existing meter board of BTS including routing the cable over the existing supports, securing the cable over the supports, clamping wherever necessary, providing suitable lugs, connections testing etc as required. |
| 21 | Providing and fixing 25 mm X 6 mm G.I. strip on surface or in recess for connections etc. as required |
| 22 | Supplying and fixing multi sensor smoke detector with mounting base & MS junction box as per specification attached. (BSNL approved make) |
| 23 | Supplying and fixing electronic hooter cum speaker of range 25-30 mtr with 4 watt capacity as per specification attached. (Make: BSNL approved) |
| 24 | Supplying and fixing Response indicator of TAC approved made of 16 SWG M.S.sheet approx. 90mmx6mm and having provision of cable entry with brass compression gland with lead etc. as reqd. ((BSNL approved make) |
| 25 | Supplying and fixing mannual call point i/c chain and hammer, removing the faulty one and making connections to the new testing etc as required . |
| 26 | Supplying and Fixing of 4MP IR Fixed Dome Network Camera, PoE based with 1/2.8\\" Image Sensor, 2.8mm fixed lens, IR range up to 30 mtrs, support on board card slot up to 128GB, DWDR, video compression H.265/H.264 etc as required, i/c all accessories. |
| 27 | Supply and laying of Cat -6 cable fitted with strain relief boots on either sides to connect camera to NVR including necessary conduit where reqd |
| 28 | Supplying and fixing following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. a) 20mm |
| 29 | Biometric Fingerprint Reader: Supply Installation Testing and Commissioning of IP based Biometric finger reader cum controller having inbuilt smartcard readers with pin pad complete power supply unit etc. as per the detailed technical specification attached. The reader log data should be transferred to server on real time basis. The reader should be capable of both enrolment purpose and access control purpose with minimum 500 users capacity. The access controller is to be integrated with the fire alarm system for operation. |
| 30 | EM‐LOCK FOR DOORS: SITC of Electromagnetic Locks of 600 lbs holding force suitable for operating with 12/24V DC power supply i/c providing Green /Red LED indication with built-in door monitor status as per the specification. (a) For single leaf doors |
| 31 | S/L 4-C x 1.0 Sq mm, copper conductor,Twisted Pair, multi strand, ATC shielded, armoured cable in recess/on surface/ cable tray (Gray Color) etc as required. |
| 32 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required a) 3 x16 Sqmm +1x6sq.mm Please Enable Macros to View BoQ information |