| 1 | Excavating in trenches, n exc 1.5 m wide and n exc 1.5m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, in cable tench etc. n exc 10 sqm on plan and getting out soft / loose soil complete all as directed. |
| 2 | Returning, filling in incl spreading, leveling, watering and well ramming in layers n exc 25 cm complete all as specified & directed. |
| 3 | Removing excavated material to a distance n exc 50 mtr and depositing where directed at a level n exc 1.50 mtr above the starting point complete all as specified & directed. |
| 4 | M & L for sand cushioning under trenches as in cable protection complete all as specified and directe.(Note: Punned thickness shall measured for payment purpose) |
| 5 | Supplying and laying bricks common burnt clay building bricks sub class 'B' bricks for cable protection complete all as specified & directed. |
| 6 | S&F steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (overall 9.00 metres long) conforming to IS IS 2713 (Parts 1 to 3) 1980 duly painted with two coats of aluminium paint externally above planting depth and two coats of bituminous paint internally and externally upto planting depth including taking down old unserviceable pole complete all as specified and directed.(Note: Necessary earthwork, PCC work etc necessary for fixing of pole shall be measured and paid separately in relevant item.) |
| 7 | M&L for PCC 1:2:4 type B1 (Using 20 mm graded stone aggregate) as in coping of pole complete all as specified and directed. |
| 8 | M&L for PCC 1:2:4 type B2 (Using 40 mm graded stone aggregate) as in foundation of pole or mass concrete complete all as specified and directed. |
| 9 | M&L for PCC 1:3:6 type C2 (Using 40 mm graded stone aggregate) as in foundation of pole or mass concrete complete all as specified and directed. |
| 10 | Supply, laying and testing of XLPE Insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10.00 sq mm 4 core shall be laid under trench or pipe or loop or shall be fixed on wall / pole including taking out old unserviceable cable complete all as specified and directed.(Note: Earthwork , excavation, sand coushioning, GI pipe etc. shall be measured and paid separately uinder relevant item) |
| 11 | All as per item No. 10 here-in-before but 16 Sqmm , 4 core. |
| 12 | All as per item No. 10 here-in-before but 35 Sqmm , 3.5 core. |
| 13 | Supply and laying 40 MM bore dia GI tubes, light grade galvanised with all fittings laid in trenches etc for protection of cable including taking up / down old unserviceable pipe complete all as specified and directed. |
| 14 | All as per item No. 13 here-in-before but 50 mm bore dia. |
| 15 | M&L applying two coat of aluminium paint on steel tubular pole 9/11 m long, including preparation old surfaces, filling cavities and lettering the Pole no in figures, complete all as specified and directed. |
| 16 | Supply and fixing in repairs FRP cable looping box of size 250 x 200 x 105 mm With connector block 4 Way , including provision for 1 Nos of MCB SP 6 Amp, copper shorting strips etc including suitable stainless steel gland, including provision for connecting earth continuity conductor etc. complete all as specified and directed. |
| 17 | Supply and fixing in repairs FRP cable looping box of size not less than 130 x 130 x 75 mm With connector block 4 Way , including provision for 1 Nos of MCB SP 6 Amp, copper shorting strips etc including suitable stainless steel gland, including provision for connecting earth continuity conductor etc. complete all as specified and directed. |
| 18 | Supply and fixing in repairs LED street light fitting 90 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed. |
| 19 | All as per item No. 18 here-in-before but 70 Watt. |
| 20 | All as per item No. 18 here-in-before but 25 / 35 Watt. |
| 21 | Supply and fixing in repairs LED flood light 50 / 70 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66/65 protection, with impact and corrosion resistant complete with driver and lamp complete all as specified and directed. |
| 22 | Supply and fixing in repairs LED flood light 210 / 250 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66/65 protection, with impact and corrosion resistant complete with driver and lamp. |
| 23 | Supply and fixing in repairs LED Post top Gate light fittings of 40 Watts energy saving, environmental friendly, long life aesthetically designed landscape IP 65/66 luminaire for diffused lighting with high power LED as light source dia not less than 450mm complete all as specified and as directed. Make: LPTO-40-CDL of Crompton /Havells/ Surya/Bajaj or equivalent |
| 24 | Supply and fixing in repairs mushroom LED light fittings 16 Watts energy saving, environmental friendly, long life aesthetically designed landscape IP 54 luminaire for diffused lighting with high power LED as light source including connection wire from pole box to light complete all as specified and as directed. Make: Cat Part No. MUSHROOMBL16WLED757SSYMTOPC OF Havells OR Equivalent model of Crompton/Surya/Bajaj or equivalent |
| 25 | S & F in repairs GI Bracket made out of 40 mm dia medium grade GI tube up to 1.5 m long bend to shape 115 degree off set shape, fixed with 2 nos of suitable MS Flat clame of size 40x6 mm with necessary nut bolts & washers duly painted with two coats of aluminum paint over one coat of zinc oxide primer for clamp complete all as specified and directed |
| 26 | Supply and fixing in repairs LED post top with decorative circular design, compliance to dark sky norms with polycarbonate opal user and IP 65 protection complete all as specified and as directed. Make: Cat Part No. BGCPNP 60 W LED CW OF Bajaj OR Equivalent model of Crompton/Surya/Havells or equivalent |
| 27 | Supply and fixing in repairs SMPS driver 400 Watt, 12 V, input 180-265 V, AC, 50 Hz, output 12 V , DC 33.3 A, power 400 Watt maximum complete all as specified and as directed. |
| 28 | Supply and fixing in repairs IP65 LED globe light energy saving, environmental friendly, long life aesthetically designed with symmetrical light distribution, spun aluminium landscape luminaire with high power LEDs as light source including connection wire from pole box to light complete all as specified and as directed. Make: Cat Part No. RUBYPT45WLED757PSYMTOPC OF Havells OR Equivalent model of Crompton/Surya/Bajaj or equivalent |
| 29 | Supply and fixing in repairs PVC copper flexible cable , three core 1.50 Sqmm for connection of street light from pole box to street light fittings complete all as specified and as directed. |
| 30 | S&F MCB 6 to 32 Amps, SP, 240 Volt \\"C\\" series, breaking capacity 10 KA complete all as specified and as directed. |
| 31 | S&F in repairs MCCB 63 Amp capacity, 4 Pole, 415Volt grade, rupturing capacity 16kA, with fixed thermal and magnetic setting, including making incoming and outgoing connections using thimbles / lugs of appropriate size, complete all as specified and directed. Make : Legrand / L&T / Siemens / ABB Please Enable Macros to View BoQ information |