| 1 | Excavating in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth in any type of soil for laying of cables, pipes etc. and getting out complete all as specified and directed . |
| 2 | Disconnecting & taking out defective under ground cable of any size from trenches, pole, pipe, floor, wall etc and removing from site complete all as specified and directed. Note:- Excavation & earth work shall be measured & paid separately |
| 3 | M&L for sand cushioning with a layer of dry river sand, 80mm thick before laying of cable and 150mm thick (punned down to 100mm thick) after laying of cables, in trenches/ducts, complete all as specified and directed. Note : Punned down thickness (overall 18cm), shall be considered for measurement and payment. |
| 4 | Supplying and laying, factory made unreinforced precast concrete cable cover LV type-1, flat, of size 250x150x40mm, laid flat and dry in trenches over the cable for protection, length perpendicular to the direction of cable adjacent to each other, complete all as specified and directed. |
| 5 | Returning, filling in, including spreading, leveling ,watering and well ramming in layers not exc 25cm in any type of soil complete all as specified and directed . |
| 6 | Removing excavated material or surplus soil to a distance not exc 50 meter and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed . |
| 7 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated, armoured, heavy duty, electric power cable, cross sectional area 10 Sqmm, 2 core, aluminum conductor, 1100 volts grade under ground cable including both side connection with lugs/thimbles of suitable size etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note: (i) Returning filling, earth work, sand cushioning and cable cover for protection of cable shall be measured and paid separately. . |
| 8 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated, armoured, heavy duty, electric power cable, cross sectional area 10 Sqmm, 4 core, aluminum conductor, 1100 volts grade under ground cable including both side connection with lugs/thimbles of suitable size etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note: (i) Returning filling, earth work, sand cushioning and cable cover for protection of cable shall be measured and paid separately. . |
| 9 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated, armoured, heavy duty, electric power cable, cross sectional area 16 Sqmm, 2 core, aluminum conductor, 1100 volts grade under ground cable including both side connection with lugs/thimbles of suitable size etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note: (i) Returning filling, earth work, sand cushioning and cable cover for protection of cable shall be measured and paid separately. . |
| 10 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated, armoured, heavy duty, electric power cable, cross sectional area 16 Sqmm, 4 core, aluminum conductor, 1100 volts grade under ground cable including both side connection with lugs/thimbles of suitable size etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note: (i) Returning filling, earth work, sand cushioning and cable cover for protection of cable shall be measured and paid separately. . |
| 11 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated, armoured, heavy duty, electric power cable, cross sectional area 25 Sqmm, 3.5 core, aluminum conductor, 1100 volts grade under ground cable including both side connection with lugs/thimbles of suitable size etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note: (i) Returning filling, earth work, sand cushioning and cable cover for protection of cable shall be measured and paid separately. . |
| 12 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated, armoured, heavy duty, electric power cable, cross sectional area 35 Sqmm, 3.5 core, aluminum conductor, 1100 volts grade under ground cable including both side connection with lugs/thimbles of suitable size etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note: (i) Returning filling, earth work, sand cushioning and cable cover for protection of cable shall be measured and paid separately. . |
| 13 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated, armoured, heavy duty, electric power cable, cross sectional area 50 Sqmm, 3.5 core, aluminum conductor, 1100 volts grade under ground cable including both side connection with lugs/thimbles of suitable size etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note: (i) Returning filling, earth work, sand cushioning and cable cover for protection of cable shall be measured and paid separately. . |
| 14 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated, armoured, heavy duty, electric power cable, cross sectional area 70 Sqmm, 3.5 core, aluminum conductor, 1100 volts grade under ground cable including both side connection with lugs/thimbles of suitable size etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note: (i) Returning filling, earth work, sand cushioning and cable cover for protection of cable shall be measured and paid separately. . |
| 15 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated, armoured, heavy duty, electric power cable, cross sectional area 95 Sqmm, 3.5 core, aluminum conductor, 1100 volts grade under ground cable including both side connection with lugs/thimbles of suitable size etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note: (i) Returning filling, earth work, sand cushioning and cable cover for protection of cable shall be measured and paid separately. . |
| 16 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated, armoured, heavy duty, electric power cable, cross sectional area 120 Sqmm, 3.5 core, aluminum conductor, 1100 volts grade under ground cable including both side connection with lugs/thimbles of suitable size etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note: (i) Returning filling, earth work, sand cushioning and cable cover for protection of cable shall be measured and paid separately. . |
| 17 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated, armoured, heavy duty, electric power cable, cross sectional area 150 Sqmm, 3.5 core, aluminum conductor, 1100 volts grade under ground cable including both side connection with lugs/thimbles of suitable size etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note: (i) Returning filling, earth work, sand cushioning and cable cover for protection of cable shall be measured and paid separately. . |
| 18 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated, armoured, heavy duty, electric power cable, cross sectional area 185 Sqmm, 3.5 core, aluminum conductor, 1100 volts grade under ground cable including both side connection with lugs/thimbles of suitable size etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note: (i) Returning filling, earth work, sand cushioning and cable cover for protection of cable shall be measured and paid separately. . |
| 19 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated, armoured, heavy duty, electric power cable, cross sectional area 240 Sqmm, 3.5 core, aluminum conductor, 1100 volts grade under ground cable including both side connection with lugs/thimbles of suitable size etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note: (i) Returning filling, earth work, sand cushioning and cable cover for protection of cable shall be measured and paid separately. . |
| 20 | Supply and laying / fixing ,GI pipe, light grade, 40mm dia bore for cable protection fixed to pole/wall with MS clamps, nuts, bolts etc or laid under floor/road/pavement, including taking out old unserviceable pipe complete all as specified and directed. |
| 21 | Supply and laying / fixing ,GI pipe, light grade, 50mm dia bore for cable protection fixed to pole/wall with MS clamps, nuts, bolts etc or laid under floor/road/pavement, including taking out old unserviceable pipe complete all as specified and directed. |
| 22 | Supply and laying / fixing ,GI pipe, light grade, 80mm dia bore for cable protection fixed to pole/wall with MS clamps, nuts, bolts etc or laid under floor/road/pavement, including taking out old unserviceable pipe complete all as specified and directed. |
| 23 | S&F in repair cable end termination jointing kit, indoor/outdoor type, heat shrinkable type including all jointing material & accessories suitable for 1100 Volt grade aluminium conductor cable of size 6 to16 sqmm ,4 core complete all as specified and directed . |
| 24 | S&F cable end termination jointing kit, indoor/outdoor type, heat shrinkable type including all jointing material & accessories suitable for 1100 Volt grade aluminium conductor cable of size 25 to 50 sqmm ,3.5/4 core complete all as specified and directed . |
| 25 | S&F cable end termination jointing kit, indoor/outdoor type, heat shrinkable type including all jointing material & accessories suitable for 1100 Volt grade aluminium conductor cable of size 70 to 150 sqmm ,3.5 core complete all as specified and directed . |
| 26 | S&F cable end termination jointing kit, indoor/outdoor type, heat shrinkable type including all jointing material & accessories suitable for 1100 Volt grade aluminium conductor cable of size 185 to 300 sqmm ,3.5 core complete all as specified and directed . |
| 27 | S&F in replacement aluminium lugs suitable for XLPE cable 16 sqmm complete all as specified and directed |
| 28 | S&F in replacement aluminium lugs suitable for XLPE cable 25 sqmm complete all as specified and directed |
| 29 | S&F in replacement aluminium lugs suitable for XLPE cable 50 sqmm complete all as specified and directed |
| 30 | S&F in replacement aluminium lugs suitable for XLPE cable 70 sqmm complete all as specified and directed |
| 31 | S&F in replacement aluminium lugs suitable for XLPE cable 95 sqmm complete all as specified and directed |
| 32 | S&F in replacement aluminium lugs suitable for XLPE cable 120 sqmm complete all as specified and directed |
| 33 | S&F in replacement aluminium lugs suitable for XLPE cable 150 sqmm complete all as specified and directed |
| 34 | S&F in replacement aluminium lugs suitable for XLPE cable 185 sqmm complete all as specified and directed |
| 35 | S&F in replacement aluminium lugs suitable for XLPE cable 240 sqmm complete all as specified and directed |
| 36 | S&F in replacement aluminium lugs suitable for XLPE cable 300 sqmm complete all as specified and directed |
| 37 | S&F in replacement aluminium lugs suitable for XLPE cable 630 sqmm complete all as specified and directed |
| 38 | S&F in replacement cable jointing kit for 11KV grade cable for straight through indoor/outdoor heat shrink type joint including all jointing material & accessories suitable for aluminium conductor cable of size 70 to 120 sqmm,3.5 core complete all as specified and directed . |
| 39 | S&F in replacement cable jointing kit for 11KV grade cable for straight through indoor/outdoor heat shrink type joint including all jointing material & accessories suitable for aluminium conductor cable of size 150 to 185 sqmm,3.5 core complete all as specified and directed . |
| 40 | S&F in replacement cable jointing kit for 11KV grade cable for straight through indoor/outdoor heat shrink type joint including all jointing material & accessories suitable for aluminium conductor cable of size 240 to 300 sqmm,3.5 core complete all as specified and directed . |
| 41 | M&L for cutting of bituminous road / floor/culvert/hard standing for laying of pipe / cables, not exceeding 1.5 meter wide and not exceeding 1.5 meter deep including refilling the material ,watering, well ramming / compacting and making good with 100 mm thick PCC 1:2:4,type B-1 complete all as specified and directed. |
| 42 | Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including providing new HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed |
| 43 | Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including providing new HDPE pipe of 100 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed |
| 44 | Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including providing new HDPE pipe of 80 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed |
| 45 | Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including providing new HDPE pipe of 50 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed |
| 46 | M&L in replacement for Bus bar chamber of size 750 x 600 x 500 mm outdoor type, pedestal type, factory made, powder coated, made out of 3.15 mm thick CRCA sheet, dust and vermin proof complete with openable shutter in front and rear having proper locking arrangement, duly powder coated with 250 Amp, 415V, 4 pole, MCCB as incommer control and including 500 Amps, 4 pole Aluminium bus bar mounted on insulator, suitable for 3 phase, 415 volts, 50 Hz AC supply including control wiring to panel with suitable size of PVC insulated and sheathed copper cable, duly mounted on frame of angle iron size 50x50x6 mm including necessary PCC, earth work in all respect with phase indicator lamps (R, Y. B) – 01 Set. complete all as specified and directed. |
| 47 | M&L in replacement for Bus bar chamber of size 750 x 600 x 500 mm outdoor typr, pedestal type, factory made, powder coated, made out of 3.15 mm thick CRCA sheet, dust and vermin proof complete with openable shutter in front and rear having proper locking arrangement, duly powder coated including 300 Amps, 4 pole Aluminium bus bar mounted on insulator, suitable for 3 phase, 415 volts, 50 Hz AC supply including control wiring to panel with suitable size of PVC insulated and sheathed copper cable with outgoing of 5 holes in one aluminium bus bar fixing to cable, duly mounted on frame of angle iron size 50x50x6 mm including necessary PCC, earth work in all respect with phase indicator lamps (R, Y. B) – 01 Set. complete all as specified and directed. |
| 48 | M&L in replacement for thermoplastic polystyrene polycarbonate junction box of size 210 X 155 X 92 mm, shock proof with IP 66 protection with suitable connector for three phase loop in loop out branch out and vibration proof connection and fixing on LT/HT poles using MS clamp made out of 25mm x 3mm MS flat (02 Nos) and nuts & bolts of required size complete all as specified and directed . |
| 49 | M&L for complete earthing with galvanised mild steel earth plate electrode of size 600x600x6mm thick, burried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of the earth plate not less than 1.5 mtr below ground level connected to galvanised earth lead wire 4mm dia (8 SWG) by means of nut, bolt, check nuts and washer of galvanised iron including PCC pit in PCC 1:2:4 type B-1, precast RCC cover slab using reinfocement with XPM weighing not less than 1.87 kg/Sqm with suitable handle made of 12mm round bar including necessary excavation and earth work in any type of soil, 20mm dia medium grade galvanised steel tube for watering with one end fixed with cast iron funnel and wire mesh ,15mm dia light grade galvanised steel tubing upto 7.5 m length for drawing earth lead wire protection, common salt, charcoal, etc complete all as shown in electrical plate No 3 of SSR Part-I and testing on completion complete all as specified and directed Please Enable Macros to View BoQ information |