| 1 | Item Rate BoQ BoQ_Ver4.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: HQ CWE (AF) NAGPUR Name of Work: REPAIR/REPLACEMENT OF OLD UNSERVICEABLE UNDER GROUND HT CABLE FROM MAIN RECEIVING STATION (MRS) TO TECH AREA SUB-DTATION AT 11 BRD UNDER GE (AF) OJHAR Contract No: CWE (AF) /OJH / OF 2026-27 Name of the Bidder/ Bidding Firm / Company : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl. No. Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE inclusive of all taxes in Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Quoted Amount in Words Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT TOTAL AMOUNT In Words |
| 2 | Supply & laying in trenchs or passing through pipe, or as indicated at site, commissioning and testing XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured electric power cable (heavu duty) earthed with stranded aluminium conductor, 11000 volts, grade of size 3 core 185 Sqmm complete all as specified and as directed. Note : Contractor shall make liaison with civil authorities i.e. HAL /MSEDCL or any other Agency for getting NOC of road cutting or boring for passing GI ppipe and HT cable and permission shall be submited to AGE E/M (AF) Ojhar, if it any dispute comes on damage causes at site during execution contractor will be responsible to resolve the issues. |
| 3 | Excavation in trenches n. exc 1.5 Mtr wide and n. exc 1.5 mtr in depth and getting out in Soft soil, complete all as specified and directedNote:- Durining excavation manually/mechanically if it break any AFNET, Signal, HT LT cable or other communication cable will be repair by contractor its on arrengment without any financial claim. It is imperative for contractor to do manual excavation at certain places complete all as specified and directed |
| 4 | Returning Filling in including spreading, leveling, watering and well ramming in layers n. exc 25 Cm, complete all as specified and directed |
| 5 | Removing excavated/Surplus soil n exc 50 M and depositing where directed at a level n. exc 1.5 Mtr above the starting point, complete all as specified and directed |
| 6 | Material and labour for laying of fine, clean sand (river sand) free from sharp materials in trenches for cushioning of cable 8 cm thick under cable and 15 cm thick over the cable including gently punning for cable in trenches/cable ducts , complete all as specified and directed. Note:- The total thickness of sand shall be measured 18 cm after punning complete all as specified and directed |
| 7 | Supplying and laying reinforced precast concrete cable cover, class HV, type 1 with peak, size 300 mm x 180 mm x 40mm , complete all as specified and directed |
| 8 | Supply, installation, testing and commissioning of 12 kV Outdoor type Load Break Switch (LBS) having one incoming and out going (1 way ) configuration DV with Safe Plus Type-C cable switch module with three position load break switch, Earthing switch , busbar interlocking and Earth bar rated for 12 kV, 630 A, 21 kA . The LBS shall be provided with manual and motorized snap-action operating mechanism (24 V DC) with local ON/OFF push buttons, auxiliary contacts (LBS: 2NO+2NC, ES: 1NO+1NC), arc-proof interlocked cable covers, Interface-C (400 type) 630 A bolted cable bushings, suitable for 3 × single-core upto 300 sq.mm cables, cable support bar, Raychem make terminal protectors, and capacitive VPIS (9–15 kV). It should been closed in one tank to avoid multiple inter connections & sealed for life Inhosue robotically welded in OEM permises with SS-304 grade stainless steel tank of 2 mm thick having IP67 degree of protection. The quoted rate shall be inclusive of necessary PCC/civil foundation/ MS structure steel work and any other alteration/ modification required at site. Complete all as specified and as directed.Each Load Break switch should consist of following accessories :(i)630 Amp triple pole, single break, 3 position (ON, OFF & EARTH) Circuit Breaker; manual operated Mechanism and fully rated earth switch.(ii) Short time current - 21KA/ 3 sec (iii) Auxiliary contacts - 1NO + 1NC (iv) Making Capacity - 52.5KA (v) Power frequency withstand voltage - 38KV (vi) Impulse withstand voltage - 95KV (vii) Manual & Motor operated mechanism for breaker operation (viii) suitable Cable bushings for front only cable terminations and shall be site replacable (ix) Arc proof cable covers with self Interlocking mechanism with earth switch (x) Capacitive voltage indication fixed type system as per IEC61243 (xi) Falut passage indicator. |
| 9 | Each Load Break switch should consist of following accessories :(i) 630 Amp triple pole, single break, 3 position (ON, OFF & EARTH) Circuit Breaker; manual operated Mechanism and fully rated earth switch.(ii) Short time current - 21KA/ 3 sec (iii) Auxiliary contacts - 1NO + 1NC (iv) Making Capacity - 52.5KA (v) Power frequency withstand voltage - 38KV (vi) Impulse withstand voltage - 95KV (vii) Manual & Motor operated mechanism for breaker operation (viii) suitable Cable bushings for front only cable terminations and shall be site replacable (ix) Arc proof cable covers with self Interlocking mechanism with earth switch (x) Capacitive voltage indication fixed type system as per IEC61243 (xi) Falut passage indicator.Metal Enclosed switchgear: IEC 62271-200, Circuit Breakers: IEC 62271-1, For HV Switchgear & Controlgear: IEC 62271-100, Disconnectors and Earthing switches: IEC 62271-102, HV Switches: IEC62271-103, Degree of protection: IEC 60529, Current transformer: IEC 60185, Voltage transformer: IEC 60186, Electrical Relay: IEC 60255, Pressure of SF6 gas: 1.4 bar at 20 °C, Cable bushings: DIN 47636, Temperature class: -25 °C+50 °C Service Ambient, Degree of protection:, Front cover: IP 2X, SF6 tank: IP 67, Cable cover: IP 3X, External structure (Outdoor RMU) IP 54, Busbars: 200 mm² Cu |
| 10 | Supply & fix jointing and testing HT cable jointing kit for 11 KV(earthed) grade cable heat shrink for end termination outdoor type joint complete with jointing matrial and accessaries suitable for 3 core XLPE armoured aluminium conductor cable of size 185 sqmm complete all as specified and as directed. |
| 11 | Supply & fix jointing and testing HT cable jointing kit for 11 KV(earthed) grade cable heat shrink for straight through out door type joint complete with jointing matrial and accessaries suitable for 3 core XLPE armoured aluminium conductor cable of size 185 sqmm complete all as specified and as directed. |
| 12 | M&L for cable route indicator fabricated constructed/fabricated on 600x180x40mm Precast RCC/PCC, duly painted with yellow colour synthetic enamel paint complete marking name on MS round disc silver painted duly reinforced in RCC precast route indicator with nomenclature of “HT cable 3x 120 Sq mm/HT cable Joint” in letters with suitable visible front including grouted in ground with PCC 1:4:8 type D-2 complete all as specified and directed |
| 13 | Material & labour for trenchless parallel boring by using mechanical pneumatic drilling machine under existing road, pavment, hardstanding by trenchless technology using ultra sounding technique without damaging existing road and making good the disturbed surfaces inculiding supply and insertion of 150 mm dia HDPE Pipe suitable for 0.4Mpa working pressure, not less than 0.6metre below the existing top surface complete all as specified and directed.Notes : Quoted unit rate for this item is deemed to be inclusive of necessary earth work, transportation charges of drilling plants and connected complete tools complete all as specified and directed |
| 14 | M&L for earthing including taking out GI plate with pipes earthing lead fasteners etc and earthing complete with galvanised steel earth plate electrode 600x600x6mm thick,burried directly in ground (earth pit not less than 2.25 Mtr deep below ground level ) with top edge of the pl;ate not less than 1.5 Mtr below normal ground level,connected to galvanised iron strip 32x6 mm as earth lead by means of bolts,nuts ,washer and check nut of galvanized steel, protected by and including GI pipe 50 mm bore (light grade) and connected to main switch / MCB DBs box point / LP test point as directed and including cement concret pit in 1:2:4 type B1 using 12.5mm graded aggregate, with cast iron miled steel frame embedded in the concrete enclouser fineshed flushed & CI cover 10 mm thick of size (300mmx300mm CI) having locking arrengment hinged to CI frame all as shown under electrical plate of SSR Pt - I 2009 and as directed including painting the external surface of chamber & cover with enamel paint in diffrent colour as directed and writing earth results & date of test carried out with white paint on black painted background, wiremesh funnel 20 mm bore GI pipe medium grade for watering adequate quantity of charcol and common salt in alternate layer of 15cm 3ft x 3ft thick all around the electrode including necessery excavation & earth work in any type of soil complete testing on completion all as directed. Note:- (i) Filling the pit with black cottan soil brought at site. ii) The excavated soil will be removed & paid separtely. |
| 15 | Note : The amount against Schedule of Credit on Page No. 24 shall be deducted from the total amount quoted against Sch 'A' while deriving Contract Sum for Acceptance. Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |