| 1 | Electrical Works |
| 2 | Supplying, laying, testing and Commissioning of 3.5 core x 300 sq mm Aluminium armoured cable of PVC insulated XLPE shethed / strip armoured aluminium cables of 1100 volt grade laid in three run through existing HDPE Pipe cpmplete with making good to the damages as required and as per direction of Engineer-in-charge. |
| 3 | Laying of 300 Sq mm 1.1kV XLPE Cable in ground including Excavation, sand cushioning, protective covering and refilling the trench complete with making good to the damages as required and as per direction of Engineer-in-charge. |
| 4 | Laying of 300 Sq mm 1.1kV XLPE Cable on existing Cable Tray as required and as per direction of Engineer-in-charge. |
| 5 | Supplying, laying, testing and Commissioning of 3 core x 95 sq mm Aluminium armoured cable of PVC insulated XLPE shethed / strip armoured aluminium cables of 6.6kV (UE) / 11kV (E) grade laid in two run through existing HDPE Pipe complete with making good to the damages as required and as per direction of Engineer-in-charge. |
| 6 | Supply and Laying of medium gauge HDPE Pipe of Size 110mm Dia PE80-PN8 complete with making good to the damages as required and as per direction of Engineer-in-charge. |
| 7 | Supply, installation and commissioning of Heat Shrinkable outdoor type End Termination kit for 95 Sq.mm. 3 Core 11kV cable including cable lugs, all accessories, cost of labour, T&P etc complete the work as per Direction of Engineer-In-Charge. |
| 8 | Supply, installation and commissioning of Heat Shrinkable Indoor type End Termination kit for 95 Sq.mm. 3 Core 11kV cable including cable lugs, all accessories, cost of labour, T&P etc complete the work as per Direction of Engineer-In-Charge. |
| 9 | Supply, installation and commissioning of Heat Shrinkable Indoor type End Termination kit for 300 Sq.mm. 3.5 Core 1.1kV grade cable including all accessories, cost of labour, T&P etc complete the work as per Direction of Engineer-In-Charge. |
| 10 | Supply and fixing of chemical Earthing of 3mtr long 40mm dia chemical filled comound and GI earth electrode including excavation of earth pit with highly conductive back filled chemical compund of 2 x 25kg , brick work in cement mortar masonary work with removable cover for Earth pit chamber of suitable size including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 11 | Supply, Installation & comissioning of different sizes of GI flat (25X6 mm, 50X6 mm) including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 12 | Supply, Installation, Testing & Commissioning of floor mounting front operated front access extensible Outdoor type type cubicle with hinged and lockable doors. CRCA sheets (16 SWG) including Busbars, interconnections, tinned copper crimping lugs, bonding to earth and painting suitable for use at 415 V, 3phase 4 wire 50 Hz system, and to withstand a fault level of 25 k Amp symmetrical for 1 sec at 415 V complete as per below specifications, as required as per direction of EIC.Changeover Panel1250 Amp 4 Pole 415V Changeover Panel with Operating Handle Kit -1 No.R-Y-B LED Indicating lamp for two sources -6 Nos,6Amp SP MCB, 10KA (B-curve)-6 Nos,100x20 mm Aluminium bus bar for connection of atleast 3 cables per phase -8 Nos,11KV drum Insulator-16 Nos.The panels shall have provision for entry of cables from the bottom as required. All live accessible parts shall be shrouded and all equipment shall be finger touch proof. The bus bars shall be insulated with heat shrinkable sleeves. |
| 13 | Supply, Installation, Testing and Commissioning of 4 Pole, 415V, 630 Amp Thermal Magnetic Release type MCCB having Breaking Capacity of 50 kA including all accessories and connection at the existing LV compartment of 630 kVA CSS with incoming bus bar arrangement of 2 Run 50 X 10 mm Aluminum Bus Bar as per direction of Engineer in Charge. The outgoing busbar should have provision for connecting atlest 3 Nos. of 300 Sq mm 4 Core 1.1kV grade Aluminum cable. Dismantling of existing 400 Amp MCCB and minior modification required in the existing panel is in the scope of the executing agency. |
| 14 | Sundries for Installtion of 630 kVA CSS by Mechanical means, branch trimming, small size nut & bolt with washer , Aluminum Binding Tape, Danger Board etc including all accessories, cost of labour, T&P etc complete the work as per Direction of Engineer-In-Charge. Please Enable Macros to View BoQ information |