| 1 | Electrical Works |
| 2 | Supply and Recessed wiring to sub main in 4x16 sq mm. FR PVC insulated single core multistrand copper conductor of ISI marked confirming to IS-694/1990 in 40 mm dia non metallic heavy duty PVC pipe of 1.6 mm thickness of ISI marked along with 2x6 sq mm FR PVC insulated single core multistrand copper conductor as earth wire and connection etc. including all accessories, with labour cost, T&P etc complete work as per direction of EIC. |
| 3 | Supply and Recessed wiring to sub main in 4x6 sq mm. FR PVC insulated single core multistrand copper conductor of ISI marked confirming to IS-694/1990 in 32 mm dia non metallic heavy duty PVC pipe of 1.6 mm thickness of ISI marked along with 2x6 sq mm FR PVC insulated single core multistrand copper conductor as earth wire and connection etc. including all accessories, with labour cost, T&P etc complete work as per direction of EIC. |
| 4 | Supply and Recessed wiring to sub main in 2x6 sq mm. FR PVC insulated single core multistrand copper conductor of ISI marked confirming to IS-694/1990 in 20 mm dia non metallic heavy duty PVC pipe of 1.6 mm thickness of ISI marked along with 1x6 sq mm FR PVC insulated single core multistrand copper conductor as earth wire and connection etc. including all accessories, with labour cost, T&P etc complete work as per direction of EIC. |
| 5 | Supply and Recessed wiring to sub main in 2x4 sq mm. FR PVC insulated single core multistrand copper conductor of ISI marked confirming to IS-694/1990 in 20 mm dia non metallic heavy duty PVC pipe of 1.6 mm thickness of ISI marked along with 1x4 sq mm FR PVC insulated single core multistrand copper conductor as earth wire and connection etc. including all accessories, with labour cost, T&P etc complete work as per direction of EIC. |
| 6 | Supply and fixing of Power point with 6 pin 16 Amp Modular socket outlet with 16Amp, 250 V clip in type Modular switch on separate modular box of 3 module with Modular base & cover with connection etc as required as per direction of EIC. |
| 7 | Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 30 A \\"C\\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required as per direction of EIC. |
| 8 | Supplying and fixing 20 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 20 A \\"C\\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required as per direction of EIC. |
| 9 | Supplying and fixing of 12 way (4 + 36), Double door surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . |
| 10 | Supplying and fixing of 8 way (4 + 24), Double door surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . |
| 11 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, 63 A residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc as per direction of EIC. |
| 12 | Supplying and fixing 63 A rating, Four Pole, 415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Four pole) |
| 13 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Triple pole) |
| 14 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Double pole) |
| 15 | Supply,installation and commissioning of outdoor LT penal board for made with 16 SWG MS metal sheet with 3 nos. kitkat fuse, three pole AL. Busbar, neutral busbar and earth busbar with indicator lamp, selector switch, digital Ameter &Voltmeter and required wiring duely painted.Incoming :- 125 Amp. 36 kA 4 P MCCB -1 No.,ELR DIN mounted,30mA-30A,220-415 VAC,220 VDC (Manual reset) with CBCT 120 mm ID -1noOutgoinging :- 63 Amp. 36 kA 4 P MCCB -4 No.,ELR DIN mounted,30mA-30A,220-415 VAC,220 VDC (Manual reset) with CBCT 120 mm ID -4 nos For 2 Bay including all accessories, cost of labour, T&P etc complete the work as per Direction of Engineer-In-Charge . |
| 16 | Earthing with GI Plate 600 mm x 600 mm x 3 mm thick including accessories, providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc with charcoal / coke and salt as required including all accessories, labour cost, T&P etc. complete work as per direction of EIC. |
| 17 | Supply and Laying of 3.5core 50 sq mm Aluminium XLPE insulated 1.1 kV grade armoured cable under ground including all accessories ,materials as required as per the direction of Engineer in Charge. Please Enable Macros to View BoQ information |