| 1 | Excavation in trenches not exceeding 1.5m wide and not exceeding 10 Sq.m on plan area and not exceeding 1.5m deep in soft/ loose soil complete all as specified and as directed. |
| 2 | Removing excavated material /soil to a distance not exceeding 50m and depositing where directed at a level not exc 1.5m above the starting point complete all as specified and directed |
| 3 | M&L for Sand filling in trenches using dry river sand as cushioning to under ground cable including spreading, levelling and consolidation complete all as specified and directed.[Note: Punned thickness of sand shall only be measured.] |
| 4 | Returning filling in, including spreading, levelling,watering and well ramming in layers not exc 25cm thickness as in soil complete all as specified and directed. |
| 5 | Supply and laying common burnt burnt building clay bricks of sub-class 'B' designation 75 old size laid along alignment of cables as protection to cables in trenches complete all as directed |
| 6 | M & L for laying 100mm dia GI pipe light grade laid for cable protection at road crossings or fixed on walls / poles secured with clamps complete all as directed |
| 7 | M & L for laying 80mm dia GI pipe light grade laid for cable protection at road crossings or fixed on walls / poles secured with clamps complete all as directed |
| 8 | M & L for laying 50mm dia GI pipe light grade laid for cable protection at road crossings or fixed on walls / poles secured with clamps complete all as directed |
| 9 | Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and PVC tape inner sheathed, 1100 Volts grade [heavy duty] with aluminium conductor of size 4 Core 16 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up including disconnecting and removal of old LT UG cable complete all as specified and as directed. |
| 10 | Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and PVC tape inner sheathed, 1100 Volts grade [heavy duty] with aluminium conductor of size 4 Core 25 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up including disconnecting and removal of old LT UG cable complete all as specified and as directed. |
| 11 | Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and PVC tape inner sheathed, 1100 Volts grade [heavy duty] with aluminium conductor of size 3.5 Core 35 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up including disconnecting and removal of old LT UG cable complete all as specified and as directed. |
| 12 | Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and PVC tape inner sheathed, 1100 Volts grade [heavy duty] with aluminium conductor of size 3.5 Core 50 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up including disconnecting and removal of old LT UG cable complete all as specified and as directed. |
| 13 | Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and PVC tape inner sheathed, 1100 Volts grade [heavy duty] with aluminium conductor of size 3.5 Core 70 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up including disconnecting and removal of old LT UG cable complete all as specified and as directed. |
| 14 | Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and PVC tape inner sheathed, 1100 Volts grade [heavy duty] with aluminium conductor of size 3.5 Core 95 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up including disconnecting and removal of old LT UG cable complete all as specified and as directed. |
| 15 | Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and PVC tape inner sheathed, 1100 Volts grade [heavy duty] with aluminium conductor of size 3.5 Core 120 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up including disconnecting and removal of old LT UG cable complete all as specified and as directed. |
| 16 | Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and PVC tape inner sheathed, 1100 Volts grade [heavy duty] with aluminium conductor of size 3.5 Core 150 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up including disconnecting and removal of old LT UG cable complete all as specified and as directed. |
| 17 | Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and PVC tape inner sheathed, 1100 Volts grade [heavy duty] with aluminium conductor of size 3.5 Core 185 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up including disconnecting and removal of old LT UG cable complete all as specified and as directed. |
| 18 | Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and PVC tape inner sheathed, 1100 Volts grade [heavy duty] with aluminium conductor of size 3.5 Core 240 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up including disconnecting and removal of old LT UG cable complete all as specified and as directed. |
| 19 | Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and PVC tape inner sheathed, 1100 Volts grade [heavy duty] with aluminium conductor of size 3.5 Core 300 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up including disconnecting and removal of old LT UG cable complete all as specified and as directed. Please Enable Macros to View BoQ information |
| 20 | Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and PVC tape inner sheathed, 1100 Volts grade [heavy duty] with aluminium conductor of size 3.5 Core 300 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up including disconnecting and removal of old LT UG cable complete all as specified and as directed. Please Enable Macros to View BoQ information |