| 1 | S/F of 100mmX110mm shackle insulator /100mmx80mm pin insulator including G.I. bolts spindle nuts etc. complete in all respects. |
| 2 | S/F of 230mmx32mmx1.5mm galvanized steel strips including holes for shackle insulators pins and bolts etc. complete in all respects. |
| 3 | Supply and erection of ‘D’ clamps of 50mmx6mm flat iron on steel tubular poles/steel rail poles with bolts, nuts etc. complete in all respects including painting with aluminum paint. |
| 4 | Dismantling of Existing Damage 9.5 Meter Long steel tubular pole complete in all respects.(Only Labour Rate) |
| 5 | S/F of steel tubular pole 9.50 Meter long designated 410 SP-36 in 1:3:6 cement concrete foundation including excavation back filling etc. complete in all respects. |
| 6 | Dismantling of existing overhead line ACSR conductor from poles/service bracket complete in all respects (Only Labour Rate) (627LR) |
| 7 | Refixing of existing overhead line ACSR conductor from poles/service bracket complete in all respects (Only Labour Rate) |
| 8 | S/E of overhead line with ACSR conductor on poles/service bracket including binding etc. complete in all respects |
| 9 | Supply and erection of overhead line with G. I. wire No. 8 to 4 SWG on poles/ service bracket including binding etc. complete in all respects. |
| 10 | S/L of AB conductor of size (3x120 + 1x95 + 1x16)sqmm |
| 11 | S/F of DB (UPPCL) |
| 12 | S/E of stay set at least 3.5 Meters away from the pole complete with galvanized 19 mm dia x 1.80 Meter long stay rod, 30cm x 30 cm x 6.3mm anchor plate, thimble stay clamps, stay insulator 19mmx600mm double screw tightener 7/3.15mm G.I. stay wire etc. in 1:3:6: cement concrete complete in all respects. |
| 13 | Painting of the electric pole with 2 coats of aluminum paint over red oxide primer complete in all respects. |
| 14 | S/B of safe earthing electrode T-19 (hot dip galvanized), length up to 2000mm, outer pipe 50mm, inner pipe 25mm, terminal dia 12mm, outer GI pipe of 16swg and inner pipe of 12swg with hot dip galvanization up to 100micron filled with crytalline conductive mixture (CCM) having anti corrosive & conductive property with 50kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30cm square CI frame with hinged cover & masonry housing (from electrode terminal to switch board, cost of earth lead will be extra) |
| 15 | S/fixing of one number 8 to 6 SWG G.I. Wire in 15mm dia. G.I. Pipe for earthing, laid in ground or in wall duly concealed including the cost of cement, sand labour. T and P other material required for proper completion of the work as directed at site. |
| 16 | S/F of LED Street Light Fitting with mandatory driver set having die cast aluminium body and lenses suitable for 110 to 130 watt confirming to IP 66 Protection having company logo engraved complete in all respects including labour Cat AAA, 12100 - 14300 system lumins high power LED with lenses, > 110 LM/watt, PF > 0.95, PHD<10% at full load, CRI>70, potted driver set not circuitory, face to face protection at 440 Volt and > 300 volt auto cut and restart feature, with 5 year warranty. |
| 17 | Cement concrete with 2 cm gauge grit, ballast approved coarse sand and cement in the proportion of 4:2:1 includingsuppy ofall materials, labour and T&P etc. required for proper completion of work. |
| 18 | S&F of 63 Amp. 415 V metal clad T.P.N. rewireable type switch fuse unit on angle iron bracket complete in all respect. Please Enable Macros to View BoQ information |