| 1 | Annual Maintenance Contract of Fire Hydrant including all pumps, panels, cables, piping , Hydrants etc. , intelligent type analogue addressable Fire Alarm system and Sprinkler system including all pumps, panels, cables, piping, sprinklers etc. at Aurangabad Airport for all preventive maintenance and checks as per manufacturers manual including attending to complaints/ Faults/ break down and taking rectification action, ensuring serviceability/ satisfactory working conditions of the system, maintenance of all records, documentation etc. as per the detailed specifications, terms & conditions covered under this contract on all days including sundays and holidays as per requirements of AAI. | Annual Maintenance Contract of Fire Hydrant including all pumps, panels, cables, piping , Hydrants etc. , intelligent type analogue addressable Fire Alarm system and Sprinkler system including all pumps, panels, cables, piping, sprinklers etc. at Aurangabad Airport for all preventive maintenance and checks as per manufacturers manual including attending to complaints/ Faults/ break down and taking rectification action, ensuring serviceability/ satisfactory working conditions of the system, maintenance of all records, documentation etc. as per the detailed specifications, terms & conditions covered under this contract on all days including sundays and holidays as per requirements of AAI. |
| 2 | Annual maintenance contract of Kirloskar make DG pump set (with specification mentioned under (A)) i/c engine control panel and other accessories of DG pump set.Job includes monthly visits for carrying out preventive maintenance, attending any number of breakdown calls when required, carrying out \\"B\\" and \\"C\\" check, minor repairs etc. as per manufacturer's recommendations / standard practice and as per the scope of work, complete as required. A) Engine type - 6R1080, Rating - 79 hp, RPM - 1500, governing class - M2. | Annual maintenance contract of Kirloskar make DG pump set (with specification mentioned under (A)) i/c engine control panel and other accessories of DG pump set.Job includes monthly visits for carrying out preventive maintenance, attending any number of breakdown calls when required, carrying out \\"B\\" and \\"C\\" check, minor repairs etc. as per manufacturer's recommendations / standard practice and as per the scope of work, complete as required. A) Engine type - 6R1080, Rating - 79 hp, RPM - 1500, governing class - M2. |
| 3 | Supplying, installation, testing & commissioning of Conventional Photo Electric Smoke detector with builtin LED and mounting base complete with all connections complying to relevant IS etc. as required.(Approved Makes : APOLLO/ EDWARDS (UTC)/ SIEMENS/ BOSCH/ NOTIFIRE/ SYSTEM SENSOR/ MORLY IAS). | Supplying, installation, testing & commissioning of Conventional Photo Electric Smoke detector with builtin LED and mounting base complete with all connections complying to relevant IS etc. as required.(Approved Makes : APOLLO/ EDWARDS (UTC)/ SIEMENS/ BOSCH/ NOTIFIRE/ SYSTEM SENSOR/ MORLY IAS). |
| 4 | Supplying, installation, testing & commissioning of addressable Photo Electric Smoke detector with builtin LED and mounting base complete with all connections complying to relevant IS etc. as required. (Approved Makes : APOLLO/ EDWARDS (UTC)/ SIEMENS/ BOSCH/ NOTIFIRE/ SYSTEM SENSOR/ MORLY IAS). | Supplying, installation, testing & commissioning of addressable Photo Electric Smoke detector with builtin LED and mounting base complete with all connections complying to relevant IS etc. as required. (Approved Makes : APOLLO/ EDWARDS (UTC)/ SIEMENS/ BOSCH/ NOTIFIRE/ SYSTEM SENSOR/ MORLY IAS). |
| 5 | Supplying, installation, testing & commissioning of Conventional Multi Sensor detector with builtin LED and mounting base complete with all connections complying to relevant IS etc. as required.(Approved Makes : APOLLO/ EDWARDS (UTC)/ SIEMENS/ BOSCH/ NOTIFIRE/ SYSTEM SENSOR/ MORLY IAS). | Supplying, installation, testing & commissioning of Conventional Multi Sensor detector with builtin LED and mounting base complete with all connections complying to relevant IS etc. as required.(Approved Makes : APOLLO/ EDWARDS (UTC)/ SIEMENS/ BOSCH/ NOTIFIRE/ SYSTEM SENSOR/ MORLY IAS). |
| 6 | Supply, Installation, Testing & commissioning of UL / EN listed (latest version) intelligent addressable multi criteria detector {Smoke + heat } with inbuilt fault isolator / isolator base and with unique optical sensing chamber, visible LED, fully coated circuit board, superior RF / Transient protection suitable for 2 wires loop connection, complete with plug into common separate base & housing constructed of LEXAN (or polycarbonate) complete with connections etc. as required and to be installed below / above false ceiling roof and concealed space and as per enclosed specifications ,complete as required. (Cost of plug in common base shall deemed to be included in cost of detectors) | Supply, Installation, Testing & commissioning of UL / EN listed (latest version) intelligent addressable multi criteria detector {Smoke + heat } with inbuilt fault isolator / isolator base and with unique optical sensing chamber, visible LED, fully coated circuit board, superior RF / Transient protection suitable for 2 wires loop connection, complete with plug into common separate base & housing constructed of LEXAN (or polycarbonate) complete with connections etc. as required and to be installed below / above false ceiling roof and concealed space and as per enclosed specifications ,complete as required. (Cost of plug in common base shall deemed to be included in cost of detectors) |
| 7 | Supplying, installation, testing & commissioning of conventional manual call box of ABS type in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc.complying to relevant IS etc. as required.(Approved Makes : APOLLO/EDWARDS (UTC)/ SIEMENS/ BOSCH/ NOTIFIRE/ MORLEY IAS/SYSTEM SENSOR/GROUP4/ MINIMAX). | Supplying, installation, testing & commissioning of conventional manual call box of ABS type in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc.complying to relevant IS etc. as required.(Approved Makes : APOLLO/EDWARDS (UTC)/ SIEMENS/ BOSCH/ NOTIFIRE/ MORLEY IAS/SYSTEM SENSOR/GROUP4/ MINIMAX). |
| 8 | Supplying, installation, testing & commissioning of conventional response indicator on surface/recess MS box having two LEDs metallic cover complete with all connections etc. complying to relevant IS etc. as required. (Approved Makes : APOLLO/EDWARDS (UTC)/ SIEMENS/ BOSCH/ NOTIFIRE/ MORLEY IAS/SYSTEM SENSOR/GROUP4/ MINIMAX). | Supplying, installation, testing & commissioning of conventional response indicator on surface/recess MS box having two LEDs metallic cover complete with all connections etc. complying to relevant IS etc. as required. (Approved Makes : APOLLO/EDWARDS (UTC)/ SIEMENS/ BOSCH/ NOTIFIRE/ MORLEY IAS/SYSTEM SENSOR/GROUP4/ MINIMAX). |
| 9 | Supplying, installation, testing & commissioning fire alarmsounder with facility to make announcement, mounted in M.S.box (16 SWG) with hinged cover plate & suitable for operationwith amplifier i/c line matching transformer etc. complete asrequired.(Approved Makes : APOLLO/EDWARDS (UTC)/ SIEMENS/ BOSCH/ NOTIFIRE/ MORLEY IAS/SYSTEM SENSOR/GROUP4/ MINIMAX). | Supplying, installation, testing & commissioning fire alarmsounder with facility to make announcement, mounted in M.S.box (16 SWG) with hinged cover plate & suitable for operationwith amplifier i/c line matching transformer etc. complete asrequired.(Approved Makes : APOLLO/EDWARDS (UTC)/ SIEMENS/ BOSCH/ NOTIFIRE/ MORLEY IAS/SYSTEM SENSOR/GROUP4/ MINIMAX). |
| 10 | Supplying, installation, testing & commissioning of conventional fire alarm panel , 16 X 2 dotmatrix LCD display, suitable for eight zones, complete with visual indications for short circuit fault, open circuit fault, fire condition and all otherstandard facilities as per IS:2189, complying relevant national fire alarm code for local fire alarm system with mimic diagram for allarea/zone covered, complete with all connections. The panel shall have input of 240 volts AC power supply, automatic battery charger, 24 volts, 2 X 12 volts, 12 Ah sealed lead acid maintenance free batteries sufficient for 24 hours normal power backup & working, interconnections. The panel shall be UL listed & FM approved and shall be hookup with PA system and along with auto dialer facility etc. as required. (Approved Makes : APOLLO/ AUTRONOCA (UTC)/ EDWARDS (UTC)/ SIEMENS/ BOSCH/ NOTIFIRE/ SYSTEM SENSOR/ MORLEY IAS/ GROUP4/ MATHER & PLATT/ MINIMAX). | Supplying, installation, testing & commissioning of conventional fire alarm panel , 16 X 2 dotmatrix LCD display, suitable for eight zones, complete with visual indications for short circuit fault, open circuit fault, fire condition and all otherstandard facilities as per IS:2189, complying relevant national fire alarm code for local fire alarm system with mimic diagram for allarea/zone covered, complete with all connections. The panel shall have input of 240 volts AC power supply, automatic battery charger, 24 volts, 2 X 12 volts, 12 Ah sealed lead acid maintenance free batteries sufficient for 24 hours normal power backup & working, interconnections. The panel shall be UL listed & FM approved and shall be hookup with PA system and along with auto dialer facility etc. as required. (Approved Makes : APOLLO/ AUTRONOCA (UTC)/ EDWARDS (UTC)/ SIEMENS/ BOSCH/ NOTIFIRE/ SYSTEM SENSOR/ MORLEY IAS/ GROUP4/ MATHER & PLATT/ MINIMAX). |
| 11 | Supply, Installation, Testing & Commissioning of UL / EN listed (latest version) Modular Microprocessor based expandable intellegent Addressable Type Fire Alarm Control Panel of following loops, with minimum 320 character graphics / LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM) ,The panel should be equiped with loop capacity to take minimum 240 intellegent addressable detectors/ devices (In any combination ) in one loop. Four access levels, capable of taking Protocol Devices, Graphical Display, sufficient numbers of programmable relay controls for controlling ventilation fan, fire pump room, monitoring of fire sprinkler and fire hydrant pump, 230 volts, 50 Hz AC power supply, automatic battery charger, 24 volts sealed maintenance free lead acid batteries sufficient for 2 hours normal working and then be capable of operating the system for 30 minutes during an emergency / fault conditions along with battery stand as required. The panel shall have facility for seamless integration with PA system (For Giving triger Signal to Start pre-recorded Digital Voice Evacuation from PA system in case of fire ). The panel shall be compatible for Building Management System with open protocol BACNET / MODBUS etc. as per specification, complete as required.(Approved Makes : APOLLO/ AUTRONOCA (UTC)/ EDWARDS (UTC)/ SIEMENS/ BOSCH/ NOTIFIRE/ SYSTEM SENSOR/ MORLEY IAS/ GROUP4/ MATHER & PLATT/ MINIMAX). | Supply, Installation, Testing & Commissioning of UL / EN listed (latest version) Modular Microprocessor based expandable intellegent Addressable Type Fire Alarm Control Panel of following loops, with minimum 320 character graphics / LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM) ,The panel should be equiped with loop capacity to take minimum 240 intellegent addressable detectors/ devices (In any combination ) in one loop. Four access levels, capable of taking Protocol Devices, Graphical Display, sufficient numbers of programmable relay controls for controlling ventilation fan, fire pump room, monitoring of fire sprinkler and fire hydrant pump, 230 volts, 50 Hz AC power supply, automatic battery charger, 24 volts sealed maintenance free lead acid batteries sufficient for 2 hours normal working and then be capable of operating the system for 30 minutes during an emergency / fault conditions along with battery stand as required. The panel shall have facility for seamless integration with PA system (For Giving triger Signal to Start pre-recorded Digital Voice Evacuation from PA system in case of fire ). The panel shall be compatible for Building Management System with open protocol BACNET / MODBUS etc. as per specification, complete as required.(Approved Makes : APOLLO/ AUTRONOCA (UTC)/ EDWARDS (UTC)/ SIEMENS/ BOSCH/ NOTIFIRE/ SYSTEM SENSOR/ MORLEY IAS/ GROUP4/ MATHER & PLATT/ MINIMAX). |
| 12 | Supplying & laying of 2x1.5 sqmm fire survival armouredcable, 600/1000V rated with annealed copper conductorhaving glass mica fire barrier tape covered by an extrudedlayer of Cross Linkable Ethylene Propylene Rubber (EPR)insulation and LSZH inner bedding, steel wire armouring &LSZH outer sheath complete as required.(Approved Makes : CMI/ KEI/ BONTON/ POLYCAB/BATRA HENLAY/ RR CABLE/ WAREXHAM). | Supplying & laying of 2x1.5 sqmm fire survival armouredcable, 600/1000V rated with annealed copper conductorhaving glass mica fire barrier tape covered by an extrudedlayer of Cross Linkable Ethylene Propylene Rubber (EPR)insulation and LSZH inner bedding, steel wire armouring &LSZH outer sheath complete as required.(Approved Makes : CMI/ KEI/ BONTON/ POLYCAB/BATRA HENLAY/ RR CABLE/ WAREXHAM). |
| 13 | Supply of 63mm dia., 15mtr. long RRL hose pipe (ISI Marked) with necessary male and female gun metal / SS couplings duly binded with GI wire, rivets etc. conforming to IS- 636 (Type-A) complete as required.(Approved Makes : FIRESHIELD/MINIMAX/NEWAGE/SAFEX). | Supply of 63mm dia., 15mtr. long RRL hose pipe (ISI Marked) with necessary male and female gun metal / SS couplings duly binded with GI wire, rivets etc. conforming to IS- 636 (Type-A) complete as required.(Approved Makes : FIRESHIELD/MINIMAX/NEWAGE/SAFEX). |
| 14 | Supply of standard short sized branch pipe constructed from SS material of 63mm dia.and be complete with male instantaneous spring lock type coupling for connection to the end of hose pipe,Externally threaded to receive nozzle,conforming to IS:903 etc. complete as required.(Approved Makes : FIRESHIELD/MINIMAX/NEWAGE/SAFEX). | Supply of standard short sized branch pipe constructed from SS material of 63mm dia.and be complete with male instantaneous spring lock type coupling for connection to the end of hose pipe,Externally threaded to receive nozzle,conforming to IS:903 etc. complete as required.(Approved Makes : FIRESHIELD/MINIMAX/NEWAGE/SAFEX). |
| 15 | supply of nozzle,20mm inner diamter,made of SS,screw threads at the inlet connection to match with the threading of 63mm dia branch pipe with inlet end of hexagonal head to facilitate screwing conforming to IS 903 etc. as required.(Approved Makes : FIRESHIELD/MINIMAX/NEWAGE/SAFEX). | supply of nozzle,20mm inner diamter,made of SS,screw threads at the inlet connection to match with the threading of 63mm dia branch pipe with inlet end of hexagonal head to facilitate screwing conforming to IS 903 etc. as required.(Approved Makes : FIRESHIELD/MINIMAX/NEWAGE/SAFEX). |