| 1 | S & F in repair, the existing panel board outdoor/indoor, fixed to the wall / platform / pole etc by replacement of old unserviceable items i.e. MCCB / MCB / Voltmeter / Ammeter / PT / CT / Indicators etc from panel and making new electric connections with multistandard copper cable of suitable size with lugs, welding of broken portion of panel, providing of new hinges after removing old broken hinges, handle including painting of outdoor/ indoor any type, any size and any make of panel with one coat of synthetic enamel paint of approved colour to external surface of panels complete etc all as specified and directed by Engineer in Charge. Note : Replacement of unserviceable items i.e. MCCB / MCB / Voltmeter / Ammeter / PT / CT / Indicators etc will be measured and paid separately. |
| 2 | Taking down MCCB 63 Amps to 400 Amps from the existing panel all as specified and as directed. |
| 3 | Supply & Fixing MCCB 200 Amps, 415 volts AC with breaking capacity 36 KA, four pole complete all as specified and directed at site |
| 4 | Supply & Fixing MCCB 400 Amps, 415 volts AC with breaking capacity 36 KA, four pole complete all as specified and directed at site |
| 5 | Supply & Fixing MCCB 250 Amps, 415 volts AC with breaking capacity 36 KA, four pole complete all as specified and directed at site |
| 6 | Supply & Fixing MCCB 100 Amps, 415 volts AC with breaking capacity 16 KA, four pole complete all as specified and directed at site |
| 7 | Supply & Fixing MCCB 63 Amps, 415 volts AC with breaking capacity 16 KA, four pole complete all as specified and directed at site |
| 8 | Taking down old unserviceable LT cable, of size 10 sqmm x 2 core with aluminium lugs etc all as specified directed by Engineer In charge |
| 9 | All as per ser item no 8 above here in before but size of 16 sqmm x 4 core |
| 10 | All as per ser item no 8 above here in before but size of 25 sqmm x 3.5 core |
| 11 | All as per ser item no 8 above here in before but size of 50 sqmm x 3.5 core |
| 12 | All as per ser item no 8 above here in before but size of 70 sqmm x 3.5 core |
| 13 | M&L for Laying of XLPE insulate, armoured, heavy duty electric cable, aluminium conductor, 1100 volts grade of size 10 sqmm x 2 core |
| 14 | All as per ser item no 13 above herein before but size of cable 16 sqmm x 4 core |
| 15 | All as per ser item no 13 above herein before but size of cable 25 sqmm x 3.5 core |
| 16 | All as per ser item no 13 above herein before but size of cable 50 sqmm x 3.5 core |
| 17 | All as per ser item no 13 above herein before but size of cable 70 sqmm x 3.5 core |
| 18 | S&F Aluminium sector lugs-long barrel of size up to 25Sqmm complete all as specified and as directed by engr-in-charge |
| 19 | S&F Aluminium sector lugs-long barrel of size from 25 Sqmm to 50 Sqmm complete all as specified and as directed by engr-in-charge |
| 20 | S&F Aluminium sector lugs-long barrel of size up from 50 Sqmm to 70 Sqmm complete all as specified and as directed by engr-in-charge |
| 21 | Excavation in trenches not exc 1.5m wide and n. exc 1.5M deep for fdn / trenches and getting out for hard/dense soil |
| 22 | Removing excavated material any type n exc 50m and depositing at a level n.exc 1.5M above ground. |
| 23 | Returning/filling in layers, spreading leveling, watering and well ramming in layers n.exc 25m in sof/loose soil. |
| 24 | M&L for sand cushioning to PVC cable with tibba sand and punning to provide required cover all as directed. |
| 25 | Supply and laying Jodhpur stone patti for cable protection of lenth between 55 to 60 cm but width between 25 to 30 cm thicknes not less than 5 cm complete as per site requirement incl removing old unsv patti and direction of engineer in charge. |
| 26 | M & L for Cutting, trimming and vending tree branches falling on overhead head lines( HT/LT) after arranging electrical shutdown from department or RSEB including taking all precautions while working on lines. [Note:- (i) The length of span between two poles shall be measured in which trees are falling on overhead electric conductors. (ii) Required T & P will be arranged by the contractor at his own cost. |
| 27 | Supply and fix LT 1100V pin type porcelain/ vitreous china, white, brown, or green insulator hight 100 mm, 65mm dia, 1100 V grade incl. one galvanised mild steel spindle, two galvanised iron washer and one GI nut complete [ISI marked]. Make : BHEL, Modern. |
| 28 | Supply and fix LT 1100V shackle type porcelain/ vitreous white, 75mm height 90mm dia incl. one galvanised mild steel spindle, washer insulator bolt & GI nut complete [ISI marked]. Make : BHEL, Modern. |
| 29 | M&L repair for prestressed cement concrete pole 9 metre long, 102mm x 172mm at top and 102mm x 279mm at bottom (or nearest higher size as approved by State Electricity Board), Class-10 conforming to IS-1678-1998, over and including marking alternate white and black strips 30 cm height (Total 5 Nos), with two coats of synthetic enamel paint over a coat of primer & Pole nos. complete all as specified & directed by Engineer-in-charge. |
| 30 | M&L for PCC 1:4:8 type D-2 using 40mm grade stone aggregate in foundation of pole all as specified & directed by engr-in-charge |
| 31 | M&L for PCC 1:3:6 type C-2 using 40mm grade stone aggregate in foundation of stay all as specified & directed by engr-in-charge |
| 32 | M&L for PCC 1:3:6 type C-1 using 20mm grade stone aggregate for pole coping incl necessary form work & finishing concrete surface even & smooth without using extra cement all as specified & directed by engr-in-charge |
| 33 | Supply and fix in repair stay assembly complete comprising of MS galvanized stay plate 23cm x23cmx6mm, MS galvanised stay rod 16 mm dia with nut 215 cm long, MS galvanised stay bow 40cm long with 2 Nos galvanized thimbles with and including all fittings all as specified in SSR 1991 Part I. (Excavation, PCC for foundation, loop type insulator to be measured and paid seperately). |
| 34 | Supply and fix insulator, loop type, porcelain vitreous, white or brown with overall dimensions of 65 x 90 mm clearance of hole 16 mm complete all as specified |
| 35 | M&L for galvanised stay strand 7/2.24mm size complete all as specified & directed by Engr-in-Charge Please Enable Macros to View BoQ information |
| 36 | M&L for galvanised stay strand 7/2.24mm size complete all as specified & directed by Engr-in-Charge Please Enable Macros to View BoQ information |