| 1 | Excavation in trenches not exc 1.5 mtr wide and n.exc 1.5 mtr in deep and getting out in Hard/Dense soil laying of cables etc. |
| 2 | Returning filling in including spreading, leveling watering and well ramming in layers n.exc 25cm thick using excavated soil |
| 3 | Removing excavated surplus soil to a distance n.exc 50 mtr and depositing where directed at a level n.exc 1.5mtr above from the starting point |
| 4 | Supply and laying Jodhpur stone patti for cable protection of lenth between 55 to 60 cm but width between 25 to 30 cm thicknes not less than 5 cm complete as per site requirement incl removing old unsv patti and direction of engineer in charge. |
| 5 | Supply and spread approved dry river sand for foundations/Cable duct including watering and consolidation, cushioning of cable laid in trenches complete all as directed by Engineer-in-Charge Note:- Punned thickness will be measured for payment purpose |
| 6 | M & L road cutting of size 30 cm width x 45 cm depth for laying of cables incl making good the road with necessary returning fillingand bituminious portion with concret and bituminious mixture and cemented portion with PCC in 1:2:4 , 15 cm thick from top and matching the surfaces with existing all as directed. |
| 7 | Supplying and laying GI pipe Light grade (ISI marked) 100mm bore with connecting accessories, laid under road/ drain/fixed on wall etc for protection of cables complete all as specified and directed |
| 8 | Supplying and laying GI pipe Light grade (ISI marked) 50mm bore with connecting accessories, laid under road/ drain/fixed on wall etc for protection of cables complete all as specified and directed |
| 9 | Supplying, laying, testing and Commissioning cable XLPE insulated aluminium conductor,stranded, armoured, PVC sheathed, LT 1100 volt grade, heavy duty as per IS-7098 and providing suitable lugs and cable glands, laid in trenches/ ducts/fixed to wall/ roof/ poles including taking down existing cables complete all as specified and directed of following sizes. 120 sqmm, 3.5 core |
| 10 | ditto as item 9.1 but 95qmm, 3.5 core |
| 11 | ditto as item 9.1 but 50 sqmm, 3.5 core |
| 12 | ditto as item 9.1 but 35 sqmm, 3.5 core |
| 13 | ditto as item 9.1 but 25 sqmm, 3.5 core |
| 14 | ditto as item 9.1 but 16 sqmm, 4 core |
| 15 | Taking down old unserviceable LT panel and Supply, installing, testing and commissioning of out door type LT feeder piller box of suitable size, padestal mounted, CPRI approved factory made totally enclosed, dust and vermin proof, shutter in front and in rear side made of 3.15 mm thick CRCA sheet, duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted to both internal and external surfaces with powder coating paint in heat process of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system, fully compartmentalized design with 4 nos aluminium bus bar suitable for 150 amps mounting on insulator,pre wired with suitable size of copper wire short circuit rating 50 KA(arms)for one second including suitable aluminium earth strip (not less than 20x3mm)for internal connection to the switches/MCCBs all as specified and comprising with and including following accessories and mounted on PCC Plat form made out of PCC 1:3:6, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in :INCOMING :- (i) MCCB four pole 100 amps,25 KA breaking capacity, adjustable thermal magnetic, 440 volt AC module, shunt trip and earth fault relay=01 no (in coming)(ii) Digital Voltmeter 0 - 500 Volt with in built selector switch - 01 No. (iii) Digital Ammeter 0 - 250 Amp with in built selector switch - 01 No.(iv) Indicator Lamps (LED type) & bakelite fuse showing R,Y, B phase - 01 set(v) Digital frequency meter 40-60 Hz - 01 No.BUSBAR :- (vi) 150 Amps rated aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round) insulators of suitable size and good insulation resistanceOUT GOING(vii) MCCB four pole 63 amps,16 KA breaking capacity, adjustable thermal magnetic, 440 volt AC module=03 nos (out going)(viii) MCB TPN 63 amps,16 KA breaking capacity,440 volt AC module=01 nos (out going)(ix) MCB SPN 40 amps,10 KA breaking capacity,240 volt AC module =02 nos (out going) |
| 16 | Taking down old unserviceable LT panel and Supply, installing, testing and commissioning of out door type LT feeder piller box of suitable size, padestal mounted, CPRI approved factory made totally enclosed, dust and vermin proof, shutter in front and in rear side made of 3.15 mm thick CRCA sheet, duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted to both internal and external surfaces with powder coating paint in heat process of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system, fully compartmentalized design with 4 nos aluminium bus bar suitable for 400 amps mounting on insulator,pre wired with suitable size of copper wire short circuit rating 50 KA(arms)for one second including suitable aluminium earth strip (not less than 20x3mm)for internal connection to the switches/MCCBs all as specified and comprising with and including following accessories and mounted on PCC Plat form made out of PCC 1:3:6, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in :INCOMING :- (i) MCCB four pole 250 amps,36 KA breaking capacity, adjustable thermal magnetic, 440 volt AC module, shunt trip =01 no (in coming)(ii) Digital Voltmeter 0 - 500 Volt with in built selector switch - 01 No. (iii) Digital Ammeter 0 - 250 Amp with in built selector switch - 01 No.(iv) Indicator Lamps (LED type) & bakelite fuse showing R,Y, B phase - 01 set(v) Digital frequency meter 40-60 Hz - 01 No.BUSBAR :- (vi) 400 Amps rated aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round) insulators of suitable size and good insulation resistanceOUT GOING(vii) MCCB four pole 160 amps,25 KA breaking capacity, adjustable thermal magnetic, 440 volt AC module=01 nos (out going)(viii) MCCB four pole 125 amps,16 KA breaking capacity, adjustable thermal magnetic, 440 volt AC module=01 nos (out going)(ix) MCCB four pole 63 amps,25 KA breaking capacity, adjustable thermal magnetic, 440 volt AC module=02 nos (out going) (x) MCB TPN 63 Amps, adjustable Thermal Magnetic relay with breaking capacity 10 KA at 415 volts = 01 nos(outgoing) (xi) MCB SPN 40 amps,10 KA breaking capacity,240 volt AC module=02 nos (out going) |
| 17 | S & F in repair, the existing panel board outdoor/indoor, fixed to the wall/platform/pole etc by replacement of old unserviceable items i.e. MCCB / MCB / Voltmeter / Ampemeter / PT/CT/ Indicators etc from panel and making new electric connections with multistandard copper cable of suitable size with lugs, welding of broken portion of panel, providing of new hinges after removing old broken hinges, handle including painting of outdoor/ indoor any type, any size and any make of panel with one coat of synthetic enamel paint of approved colour to external surface of panels complete etc all as specified and directed by Engineer in Charge. Note : Replacement of unserviceable items i.e. MCCB/MCB/ Voltmeter/ Ammeter/PT/CT/Indicators etc will be measured and paid separately. |
| 18 | Supply and fix MCCB 400 Amps 3 pole, 36 KA, 415 V, 50 Hz with thermal setting between 70% to 100% and connecting up in the existing panel location. |
| 19 | Supply and fix MCCB 250 Amps 3 pole, 36 KA, 415 V, 50 Hz with thermal setting between 70% to 100% and connecting up in the existing panel location. |
| 20 | Supply and fix MCCB 200 Amps 3 pole, 25 KA, 415 V, 50 Hz with Thermal setting between 70% to 100% and connecting up in the existing panel location. |
| 21 | Supply and fix MCCB 160 Amps 3pole, 16 KA, 415 V, 50 Hz with thermal setting between 70% to 100% and connecting up in the existing panel location. |
| 22 | Supply and fix MCCB 100 Amps 3 pole, 16 KA, 415 V, 50 Hz with thermal setting between 70% to 100% and connecting up in the existing panel location. |
| 23 | Supply and fix MCCB 63 Amps 3 pole, 16 KA, 415 V, 50 Hz with thermal setting between 70% to 100% and connecting up in the existing panel location. |
| 24 | S&F Aluminium sector lugs-long barrel of size up to 50 sqmm complete all as specified and as directed by engr-in-charge |
| 25 | S&F Aluminium sector lugs-long barrel of size up from 70 Sqmm to 120 sqmm complete all as specified and as directed by engr-in-charge |
| 26 | Supply and fixing LED Digital type Voltmeter, 415 V, 3Phase, 50Hz |
| 27 | Supply and fixing Digital type Ammeter, 415V, 3 Phase, 50Hz |
| 28 | Supply and fixing in repairs push buttons / rotary switches as per existing complete all as specified and directed by Engineer-in-Charge |
| 29 | Supply and fixing in repairs LED indication lamp R/Y/B as per sample complete all as specified and directed by Engineer-in-Charge. |
| 30 | M & L for scrapping down rusted, fallen paint from the Electrical LT pannel situated at 44WING/TXR Area including rail/channel of base using mechanical scrapers, brushes, sand paper etc and removing the old paint to the complete outer surfaces and repainting external surfaces with black/yellow (strip) colour with applying a coat of red xide zinc chrome primer on the both internal & external portion where base metal is exposed, painting spray one coat of synthetic enamel paint for outdoor type panel including MCCB's specific cabinet complete all as specified and directed. |
| 31 | Earthing with galvanised iron earth plate electrode 600 x 600 mm & 6 mm thick burried directly in ground (earth pit not less than 2.25 metre deep below normal GL) with top of earth plate not less than 1.5 metre below GL connected to GI earth strip 32 x 6 mm connected to earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel with & including ; PCC 1:3:6 C1 pit with cover of RCC 1:1.5:3 A1 40 mm thick reinforced with 3 Nos, 6 mm dia bars both way, watering arrangements with 20 mm GI medium grade pipe ISI marked, GI funnel with GI mesh, filling with mixture of common salt & charcoal in alternate layers, necessary excavation and earth works in any type of soil, including test point, testing & commissioning, complete. (Note :- GI earth strip & protection pipe with GI pipe protection shall be measured & paid separately) |
| 32 | GI strip of size 32 x 6 mm as earth continuity conductor as main earthing lead fixed to wall on batten or recessess as chases or burried in ground or drawn in pipe fixed to pole or any other indicated situation complete all as specified & directed |
| 33 | Ditto all as per item No 36 but using copper plate 60X60X3.15mm thick electrode & 20X3mm copper strip as earthing lead all as directed. |
| 34 | Ditto all as per item No 37 but of 20X3 mm Copper strip with suitable poecelain insulator connected to Earthing test point all as specified and directed on testing on completion.Note-:The strips are to be bent to shape, drilled with holes, connected with copper/brass bolts, nuts, washers. |
| 35 | Supply and fixing of mild steel enclosure 2 way double door water proof fabricated out of 3mm thick MS sheet powder coated both inside and outside for housing MCB & aluminium bus bar of size 20mm x 3mm of required length including MCB SPN 6 Amps for control of single street light fitting / post top lamp fixed on pole, enclosure to be fixed with suitable size of clamp, nut & bolt and washer fixed to pole including control cable from junction box to light point at top of the pole complete all as specified and directed by Engineer- in- charge. Please Enable Macros to View BoQ information |