| Sl. No. | Item Description |
| 1 | Medical Gas Supply System |
| 2 | Supply, Installation, Testing & Commissioning of Solid drawn, seamless, deoxidised, non- arsenical, half hard, tempered and degreased copper pipes as per specification icluding painting.22mm OD X 1 mm thick |
| 3 | Supply, Installation, Testing & Commissioning of Solid drawn, seamless, deoxidised, non- arsenical, half hard, tempered and degreased copper pipes as per specification icluding painting.15mm OD X 1 mm thick |
| 4 | Supply, Installation, Testing & Commissioning of Medical Vacuum terminal outlet with Probe, DIN type, complete as per specification |
| 5 | Supply, Installation, Testing & Commissioning of Vacuum regulator (0 -760 mmHg) with ON/OFF switch, 600 ml autoclavable collection jar, safety trap, bacterial filter, wall bracket, complete with DIN probe as per specification. |
| 6 | Supply, Installation, Testing & Commissioning of Oxygen flow meter with humidifier bottle (0 - 10 LPM), brass chrome plated body, polycarbonate tube, SS inlet filter, autoclavable bottle (121/134deg.C), complete with matching DIN probe |
| 7 | AREA VALVE SERVICE UNIT (WITH VALVES): Supply,Installation, Testing and Commissioning of Area Valve Service Unit. as per specification Valve Box - 3 Gas Service with NIST Connection |
| 8 | Ward Vacuum Unit with suction jar : Supply, installation, testing and commissiong of Ward VacuumUnit with 600ml suction jar as per specification. |
| 9 | LINE ISOLATION VALVES: Supply, Installation, testing and commissioning of Line Isolation Valves as per specification,12 mm ball valve |
| 10 | LINE ISOLATION VALVES: Supply, Installation, testing and commissioning of Line Isolation Valves as per specification,28 mm ball valve |
| 11 | LINE ISOLATION VALVES: Supply, Installation, testing and commissioning of Line Isolation Valves as per specification,22 mm ball valve |
| 12 | LINE ISOLATION VALVES: Supply, Installation, testing and commissioning of Line Isolation Valves as per specification,15 mm ball valve |
| 13 | Supply, installation, testing and commissioning of Medical gas hose assemblies as per standard followed as per specification |
| 14 | Supply & installation of Bed Head Panel 5ft (1500 mm, Horizontal/Vertical) unit made out of High strength extruded Aluminum Panel of minimum 2.5 mm thickness with powder coated to make it aesthetically appealing and long lasting, with - Oxygen 02 Nos, Vacuum 01 No, Medical Air 01 No, 6/16ASocket 6 Nos, RJ-45 socket 01 No & provision for nurse call switch 01 No. |
| 15 | Supply, Installation, Testing & Commissioning of Solid drawn, seamless, deoxidised,non- arsenical, half hard, tempered and degreased copper pipes as per specification icluding painting.28mm OD X 1.2 mm thick |
| 16 | Supply, Installation, Testing & Commissioning of Solid drawn, seamless, deoxidised, non- arsenical, half hard, tempered and degreased copper pipes as per specification icluding painting.12mm OD X 1 mm thick |
| 17 | MEDICAL GAS ALARM PANEL: Supply, Installation, testing and commissioning of Medical Gas Alarm Panel (digital) as per specification ,Medical Gas Area Alarm for 3 services (Oxygen, MA 4 bar and Vacuum) |
| 18 | Supply, Installation, Testing & Commissioning of Medical Air terminal outlet with Probe, DIN type, complete as per specification |
| 19 | Supply, Installation, Testing & Commissioning of Oxygen outlet with Probe, DIN type, complete as per specification |
| 20 | Supply, Installation, Testing and Commissioning of Air Handling Unit with redundant unit with additional blower/chilled water coil , filters and supported accessories : Doubleskin,45mm PUF panels made of pre-coated sheets with aluminum sectional frames-thermal break profile, 6-Row copper cooling coil of capacity 10.5TR,pre-filters,bypass arrangement etc. to achieve ISO class 7 cleanliness, Capacity:Not less than 7000 cfm Motor-Blower: High Static blower with back ward curved,balanced,impeller of Krugermake(Imported), with heavy duty Motor, drive package etc |
| 21 | Supply, Installation, Testing & Commissioning of Prefilters for particles in the range of 10 microns & fine filter 3 microns - HDPE protection both side non-wovenfabric ,cleanable media with aluminium support mesh to match AHU capacity |
| 22 | Supply, Installation, Testing & Commissioning of Air Handling Unit: Double skin, 45mm PUF panels made of pre-coated sheets with aluminum section alframes-thermal break profile , 6-Row copper cooling coil of capacity 5TR, pre-filters , by pass arrangement etc. to achieve ISO class 8 cleanliness, Capacity:Not less than 1800 cfm Motor-Blower:High Static blower with backward curved,balanced ,impeller of Kruger make (Imported), with heavy duty Motor, drive package etc |
| 23 | Supply, Installation, Testing & Commissioning of Prefilters for particles in the range of 10 microns & fine filter 3 microns – HDPE protection both side non-wovenfabric ,cleanable media with aluminium support mesh to match AHU capacity. |
| 24 | Chilled Water Pipeline & associated |
| 25 | Supply, fixing, testing & commissioning of suitable size Butterfly Valve for the chilld water manifold as per standard. |
| 26 | Supply, fixing, testing & commissioning of suitable size Balancing Valve for the chilld water manifold as per standard. |
| 27 | Supply, fixing, testing & commissioning of suitable size Y-strainer for the chilld water manifold as per standard. |
| 28 | Supply, fixing, testing & commissioning of suitable size 3way Valve for the chilld water manifold as per standard. |
| 29 | Supply, fixing, testing & commissioning of suitable size Dial type pressure gauge for the chilld water manifold as per standard. |
| 30 | Supply, fixing, testing & commissioning of suitable temperature gauge for the chilld water manifold as per standard. |
| 31 | Supply, fixing, testing & commissioning of suitable size drain valve with MS C class 6mm thick pipe for the chilld water manifold as per standard. |
| 32 | Supply, Installation, Testing & Commissioning of Chilled Water Pipe of required size for the AHU as per standard.50NB |
| 33 | Supply, Installation, Testing & Commissioning of Chilled Water Pipe of required size for the AHU as per the standard.25NB |
| 34 | Supply & Installation of all required accessories - Bends, Rubber Bellows, MS Flanges, Bolts , Nuts, Seal Gaskets, Flow meter, Supports and PUF saddles. |
| 35 | Ducting & Dampers for AHU |
| 36 | Ducting works at varying stages to be completed as required. Supply, Installation, Testing and Commissioning of fabricated 22 G Aluminum sheet metal ducting in L section as per IS 635 standards with class VIII sheet MS ducts, supports, suspended rods with complete paint with Silicon sealent for duct joints. Leak Testing, Leak rectification. |
| 37 | Ducting works at varying stages to be completed as required. Supply, Installation, Testing and Commissioning of fabricated 20 G Aluminum sheet metal ducting in L section as per IS 635 standards with class VIII sheet MS ducts, supports, suspended rods with complete paint with Silicon sealent for duct joints. Leak Testing, Leak rectification. |
| 38 | Supply, Installation, Testing & Commissioning of Duct insulation chemically Cross linked close cell Polyethyelve CLASS 1 insulation with metalic foil with tape and addicive. 13 mm thick for Supply air duct |
| 39 | Supply, Installation, Testing & Commissionning of Duct insulation chemically Cross linked close cell Polyethyelve CLASS 1 insulation with metalic foil with tape and addicive. 9 mm thick for return air duct. |
| 40 | Supply, Installation, Testing & Commissioning of Volume control (Extruded Aluminium) duct Dampers - manual with handle with gradation markings and lock |
| 41 | Supply, Installation, Testing & Commissioning of Fire Dampers (GI - 18G) with a melting fuse link to shut air supply through duct in case of fire and limit switch to switch Off AHU in case of fire. |
| 42 | Supply, Installation, Testing & Commission of Return Air Risers embedded within wall panels with Powdercoated SS Grill for low level pickup with volume control damper with pre filter. |
| 43 | Supply, Installation, Testing & Commissioning of HEPA Filter housing with gear operated damper from room side, DOP port, pressure sensing port suitable for fixing gel seal type HEPA Filters with HEPA filters 0.3micron & larger particles at >99.99% efficiency installed at teminal 610 x 610 x 150 mm. |
| 44 | Supply, Installation, Testing & Commissioning of HEPA filters with GMP housing and SS perforated gril to filter 0.3micron & larger particles at >99.99% efficiency installed at teminal in a specially design leak proof Hood / HEPA housing with volume control damper 610 x 305 x 150 mm |
| 45 | Instruments |
| 46 | Supply & Installation of Room Pressure Magnehelic Gauge with fixture - 50 to 50 pascals. |
| 47 | Supply & Installation of suitable Temperature & RH Display. |
| 48 | Supply & Installation of suitable Return Duct Temperature & RH sensor. |
| 49 | Control panel for AHU |
| 50 | Supply, Installation, Testing & Commissioning of Control panel complete with Starter,Contactors,OLRs,MCB,VFD ( HVAC VFD with temperature and RH control) etc,power cabling from our Starter to the AHU including control max6mtrs), Thermostat,3KWHeaters,Humidistat wiring(Incoming wiring with Earthing upto our Control Panel, client scope) |
| 51 | Validation |
| 52 | Validation including NABL traceable certificates, Drawings, OEM Test Certificates, DQ-IQ-OQ documentation which shall include ACPH/3 days particle count / Area recovery / Filter intergrity test / Microbial count. |
| 53 | Clean Room Panels |
| 54 | Supply & Installation of Modular, PUF Insulated Clean Room Wall/Partition Panels (80mm thick) with both sides 0.5mm thick PCGI with provision for concealed wiring, Doors & View Panels (Including cutouts for sockets, view panels, passbox etc). |
| 55 | Supply & Installation of Modular,PUF Insulated Clean Room Ceiling Panels (50mmthick) with both sides PCGI 0.5 mm thick (Including cutouts for Light Fittings, Filter Plenum etc). |
| 56 | Coving: Aluminium sections to round off 90º joints between wall- ceiling-floor. |
| 57 | Corner Coving: Die cast aluminium coving for corners. |
| 58 | Supply & Installation of Clean Room Single Doors: Metallic powder coated with double glazed, SS ball bearing hinges,Viewpanel,doorcloser,SShandle etc Size: 0.9 m X 2.1 m |
| 59 | Supply & Installation of Clean Room Double Doors: Metallic powder coated with double glazed, SS ball bearing hinges,Viewpanel,doorcloser,SShandle etc Size:1.4 m x 2.1m |
| 60 | Supply & Installation of Emergency Exit Doors: Metallic powder coated with double glazed view panel, SS ball bearing hinges, door closer, SS handle etc. Size:1.4 m x2.1m |
| 61 | Supply & Installation of Epoxy flooring: Self leveling, seamless floor with suitable preparation, 2mm total thickness |
| 62 | Supply & Installation of View Panels: Double glazed, with flush mounting; Size: 900 x 900mm |
| 63 | Clean Room Equipments |
| 64 | Supply & Installation of DynamicPassbox : SS304 construction ,twin doors with tough end glass view panel,SS base,UV lamp,LED lighting,electromagnetic interlocking, HEPA filtration, Inner Size: 24”X24”X 24” |
| 65 | Supply & Installation of Air Shower - GI powder coated construction, complete with Blowers, HEPA filters, doors, SS adjustable nozzles, EM lock with interlock control circuit; Inner area 900 X 900 X 1950mm & Overall size 1700 X 1000 X 2250mm. |
| 66 | Supply & Installation of Electro-mechanical Double leaf door - two room interlocking system with necessary wiring as required. |
| 67 | Supply & Installation of Electro-mechanical single leaf door- two room interlock system with required accessories and wiring. |
| 68 | Supply & Installation of Cross Over Bench: SS304 Size: 2.4m x 0.4m X 0.5m (or to suit change room width) |
| 69 | Supply & Installation of SS storage cupboard 1200 (L) x 1500 (H) x 450 (D) , 240 x 383 - 15 locks (3 x 5 configuration) |
| 70 | Supply & Installation of Garment Storage Cabinet with HEPA filtration & UV lamp & provision for footwear at bottom, Fully SS304 Inner Size: 36\\" X 20\\" X 48\\" (Clean Room footwear Cabinet). |
| 71 | Supply & Installation of SS polished mirror of size 1850x650mm. |
| 72 | Supply & Installation of suitable SS Hand & Leg wash equipment with necessary fixtures/water connections, drain as required. |
| 73 | Demolishing |
| 74 | Demolishing brick work manually / by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-Charge.In cement mortar |
| 75 | Dismantling wooden boardings in lining of walls and partitions, excluding supporting members but including stacking with in 50 metres lead:Thickness above 10mm upto 25 mm |
| 76 | Dismantling tile work in floors and roofs laid in cement mortar including stacking material within 50 metres lead.For thickness of tiles 10 mm to 25 mm |
| 77 | Dismantling aluminium / Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable material and stacking of serviceable material with in 50 metres lead as directed by Engineer - in-Charge |
| 78 | Demolishing R.C.C. work manually / by mechanical means including stacking of steel bars and disposal of unserviceable material with in 50 metres lead as per direction of Engineer -in-Charge. |
| 79 | Removing of existing damaged floor carpet/vinyl flooring with cleaning the surface for further process as per direction of engineer in charge. |
| 80 | Civil Works |
| 81 | Reinforced cement concrete work in beams, suspended floors, roofs, having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases up to floor five level excluding the cost of centering, shuttering, finishing and reinforcement, with1:1.5:3 (1 cement : 1.5 coarse sand (Zone III) derived from natural sources: 3 graded stone aggregate 20 mm nominal size derived from natural sources). |
| 82 | Centering and shuttering including strutting, etc. and removal of form for:Suspended floors, roofs, landings, balconies and access platform |
| 83 | Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete above plinth level.Thermo - Mechanically Treated bars of grade Fe-500D or more |
| 84 | Providing and fixing 18 mm thick gang saw cut, mirror, polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations, of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 ( 1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.Area of slab over 0.50 sqm |
| 85 | Extra for providing opening or required size & shape for wash basin/kitchen sink in kitchen platform, vanity counter and similar location in marble/granite/ stone work, including necessary holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete. |
| 86 | Providing and fixing non lit Signages made of CNC Cut Stainless Steel projected letters and fixing it at site with all necessary fitting arrangements and accessories as per the design and requirement on instructions of the engineer in charge. SQM 15000 |
| 87 | Lab work bench -The work bench top made up of 18mm thick granite top edge moulded over 18 mm thick marine plywood and GI Powder coated frame work of section size not less than 50x50x1.5mm. The width of the table shall be 750mm and height shall be 850mm. The frame provided with level adjusting screws fixing accessories ,carriage of material all complete as per the approved drawings and direction of Engineer in charge.Note Only length of the table shall be measured for making payment. |
| 88 | Joinery |
| 89 | Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & double acting hydraulic floor spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-in-charge ( Door handle, lock and stopper etc to be paid separately) |
| 90 | Providing and fixing 12 mm thick frameless toughened glass partition of approved brand and manufacture, including top & bottom fixing arrangement and making necessary holes etc. for fixing required fittings, all complete as per direction of Engineer-in-charge. |
| 91 | Providing and fixing 3M Fasara frosted etching film of thickness 25 microns self- adhesive of approved colour, shade, and quality with cutting as per approved design and pattern, including cleaning of glass and making surface smooth for fixing of film to the surface, all completed as per the direction of the engineer in charge. |
| 92 | Providing and fixing of glass door SS Patch Lock with out handle in toughened glass door including all necessary screws etc. complete |
| 93 | Providing and fixing SS H handle having min 30cm length in toughed glass door including all necessary screws etc. complete |
| 94 | Providing and fixing factory made uPVC white colour casement/casement cum fixed glazed windows comprising of uPVC multi-chambered frame, sash and mullion (where ever required) extruded profiles duly reinforced with 1.60 +/- 0.2mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), uPVC extruded glazing beads of appropriate dimension, EPDM gasket, stainless steel (SS 304 grade) friction hinges, zinc alloy (white powder coated) casement handles, G.I fasteners 100 x 8 mm size for fixing frame to finished wall, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame & sash shall be mitred cut and fusion welded at all corners, mullion (if required) shall be also fusion welded including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes and silicon sealant shall be paid separately)Note: For uPVC frame, sash and mullion extruded profiles minus 5% tolerancein dimension i.e. in depth & width of profile shall be acceptable.Casement window double panels with top fixed with S.S. friction hinges (350 x 19 x 1.9 mm) made of (small series) frame 47 x 50 mm, sash 47 x 68 mm & mullion 47 x 68 mm all having wall thickness of 1.9 ± 0.2 mm and single glazing bead of appropriate dimension. ( Area of window upto 2.50 sqm). |
| 95 | Providing and fixing panelling or panelling and glazing in panelled or panelled and glazed shutters for doors, windows and clerestory windows (Area of opening for panel inserts excluding portion inside grooves or rebates to be measured), Panelling for panelled or panelled and glazed shutters 25 mm to 40 mm thick:5.0 mm thick glass panes (weight not less than 12.50 kg/sqm). |
| 96 | Providing and fixing M.S. Grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete.Fixed to steel windows by welding |
| 97 | Plumbing and sanitary fitting |
| 98 | Providing and fixing floor mounted, white vitreous china single piece, double traps syphonic water closet of approved brand/make, shape, size and pattern including integrated white vitreous china cistern of capacity 10 litres with dual flushing system, including all fittings and fixtures with seat cover, cistern fittings, nuts, bolts and gasket etc including making connection with the existing P/S trap, complete in all respect as per directions of Engineer-in-Charge. |
| 99 | Supplying and fixing CP Health faucet good quality including cost of materials and labour charges etc. complete as per the direction of site engineer-in-charge. |
| 100 | Providing and fixing C.P. brass shower rose with 15 or 20 mm inlet:100 mm diameter |
| 101 | Providing and fixing counter top wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require: White Vitreous counter top wash basin of minimum size 485x310x130mm. |
| 102 | Flexible pipe32 mm dia |
| 103 | Providing and fixing uplasticised PVC connection pipe with brass unions: 30 cm length15 mm nominal bore |
| 104 | Providing and fixing C.P brass stop cock ( concealed) of standard design and of approved make conforming to IS: 893115 mm nominal bore |
| 105 | Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS: 893115 mm nominal bore |
| 106 | Providing and fixing SS grating of approved quality and colour. Rectangular type with openable lid150 mm nominal size square 100 mm diameter of the inner hinged grating. |
| 107 | Supplying and fixing PVC Floor Trap 100mmx75mm size without Jali including cutting open, boring through RCC slabs and making good the damages. |
| 108 | Supplying and fixing CP Towel rod 45cm or nearest available length including cost of materials and labour charges etc complete as per the direction of site Engineer-in- charge. |
| 109 | Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms.15 mm nominal bore |
| 110 | Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS 13983 with C.I. brackets and stainless steel plug 40 mm,with swan neck faucet with pipe in let and drain provision, including painting of fittings and brackets, cutting and making good the walls wherever required:Kitchen sink with drain board510x1040 mm bowl depth 250 mm |
| 111 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.20 mm nominal dia pipes |
| 112 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall32 mm nominal dia pipes |
| 113 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.25 mm nominal dia pipes |
| 114 | Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 50 mm dia 10 Kfg/cm - Internal work- Exposed on wall |
| 115 | Providing and fixing PVC pipes including fixing the pipe with clamps/ clip at 1.00 m spacing . This includes jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 63 mm dia 6 Kgf/cm2 - External work - Exposed on wall |
| 116 | Providing and fixing PVC pipes including fixing the pipe with clamps/clips at 1.00 m spacing. This included jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 75 mm dia 6Kgf/cm2 - External work- Exposed on wall |
| 117 | Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 63 mm dia Elbow |
| 118 | Providing and fixing PVC moulded fittings/accessories for Rigid PVC pipes including jointing with PVC solvent cement - 63x63x63 mm dia Tee |
| 119 | Providing and fixing PVC moulded fittings/accessories for Rigid PVC pipes, including jointing with PVC solvent cement -75 mm dia 45 degree Elbow |
| 120 | Providing and fixing PVC moulded fittings/accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 75x75x75 mm dia Door Tee |
| 121 | Providing and fixing PVC pipes includings jointing of pipes with one step pvc solvent cement, trenching , refilling & testing of joints complete as per direction of Engineer in Charge. 150 mm dia 6 Kgf/cm2 |
| 122 | Providing and fixing PVC pipes including fixing the pipe with clamps/ clips/ at 1.00 m spacing . This includes jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 110 mm dia 6 Kgf/cm2 - External work- Exposed on wall |
| 123 | Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement- 110 mm dia Bend |
| 124 | Providing and fixing PVC moulded fittings/accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 110x110x110 mm dia Door tee |
| 125 | Providing and fixing PVC moulded fittings /accessories for Rigid PVC pipes, including jointing with PVC solvent cement -110 mm dia Vent cowl |
| 126 | Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement -75 mm dia End cap |
| 127 | Block work and Finishing |
| 128 | Solid block masonry using pre cast solid blocks ( Factory made) of size 30x20x20cm or nearest available size confirming to IS 2185 Part I of 1979 for super structure up to floor two level thickness 20cm and above in: CM 1:6 ( 1 cement : 6 coarse sand) etc complete |
| 129 | Solid block masonry using pre cast solid blocks (Factory made) of size 30x20x15 cm or nearest available size confirming to IS 2185 part I of 1979 for foundation and plinth with thickness 15cm in: CM 1:6 ( 1 cement :6 coarse sand) etc complete |
| 130 | 12 mm cement plaster of mix:1:4 ( 1 cement : 4 fine sand) |
| 131 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 132 | Wall painting with premium acrylic emulsion paint of interior grade, having VOC (Volatile including applying additional coats wherever required to achieve even shade and colour.Two coats |
| 133 | Tile Work |
| 134 | Providing and laying Vitrified tiles in floor in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm including grouting the joints with white cement and matching pigments etc. The tiles must be cut with the zero chipping diamond cutter only . Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily.Glazed Vitrified tiles Matt/Antiskid finish of size Size of Tile 600 x 1200 mm |
| 135 | Providing and laying premium vitrified bathroom wall tile in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete. |
| 136 | Wiring |
| 137 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C |
| 138 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire |
| 139 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 140 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 141 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 6 Sq.mm + 1 x 6 sq.mm earth wire |
| 142 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required4 X 6 sq. mm + 2 X 6 sq. mm earth wire |
| 143 | DB and Switchgear |
| 144 | Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required. Single pole |
| 145 | Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps |
| 146 | Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.100 amps |
| 147 | Supply and Fixing of 40 A to 63 A, TP MCB (C curve), 10 kA breaking capacity in the existing MCB DB complete with connections, testing and commissioning etc. As Required. |
| 148 | Supply and fixing of existing 40A 4 pole MCB with 4 pole enclosure for 3 phase power point |
| 149 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli Amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps |
| 150 | Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps |
| 151 | Supplying and fixing TP sheet steel enclosure on surface/ recess along with 16/25/32amps 415 volts \\"C\\" curve TP MCB complete with connections, testing and commissioning etc. as required. |
| 152 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)4 Way (4+12) Double door |
| 153 | Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required8 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43) |
| 154 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)12 way, Double door |
| 155 | Providing and fixing following rating and breaking capacity MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel. making connections. etc. as required. 200 Amp, 25 KA,TPMCCB |
| 156 | Supplying and fixing Cable End Box (Loose Wire Box) (IP 43) suitable for tripple pole and neutral, sheet steel, Vertical MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required. |
| 157 | Supplying and fixing TP sheet steel enclosure on surface/ recess along with 63 amps 415 volts "C" curve TP MCB complete with connections, testing and commissioning etc. as required. |
| 158 | Supply, installation, testing, and commissioning of enclosure suitable for housing a 200A, 4 Pole MCCB, wall-mounted or floor-mounted as required, suitable for indoor/outdoor application. The enclosure shall be made of minimum 1.6 mm thick CRCA sheet, powder-coated with corrosion-resistant finish, having protection degree of IP54 (indoor) / IP65 (outdoor). It shall be suitable for accommodating 200A, 4P MCCB with proper mounting arrangement, adequate cable termination space, and tinned copper busbars with proper insulation. The enclosure shall be provided with removable gland plates for cable entry, double earthing studs, hinged door with gasket and lockable arrangement, and removable GI mounting plate. The enclosure shall conform to IS 8623 / IEC 61439 standards |
| 159 | Electrical Fixtures |
| 160 | Supplying and fixing suitable size GI box with Clean Room grade Premium modular plate and cover in front on surface or in recess, including providing and fixing premium clean room grade 6/16 amps modular socket outlet and 6/16A amps modular switch, connection etc. as required. Make: Schneider Electric Unica Pure/Crabtree Murano. |
| 161 | Supply, conveyance and Installation of compact Surface or Recess mounted, 60cm x 60cm, 36W LED luminaire suitable for Clean Room Lighting Top <br> opening or Bottom opening having SS frames with High translucent diffuser gives soft glare free, Cool White light & complete with electronic driver including all required mounting accessories, frames, along with dismantling/cutting false ceiling and making good the damages as required complete. (Philips Purespace /WIPRO Vision /Crompton or equivalent) |
| 162 | Supply, conveyance and Installation of compact Surface or Recess mounted, 30cm x 30cm, 15-25W LED luminaire suitable for Clean Room Lighting Top<br>opening or Bottom opening having SS frames with High translucent diffuser gives soft glare free, Cool White light & complete with electronic driver including all required mounting accessories, frames, along with dismantling/cutting false ceiling and making good the damages as required complete. (Philips Purespace/WIPRO Vision /Crompton or equivalent) |
| 163 | Supplying and fixing suitable size GI box with Clean Room grade Premium modular plate and cover in front on surface or in recess, including providing and fixing premium clean room grade 6 amps modular socket outlet and 6 amps modular switch, connection etc. as required. Make: Schneider Electric Unica Pure/Crabtree Murano. |
| 164 | Supplying, conveyance and Installation of 150-250 mm sweep,1350 rpm, 3 - 5 blade BLDC Exhaust Fan including frames and all mounting accessories complete.Recommended Make: Atomberg Efficio/Crompton Brisk Air |
| 165 | Network and Telephone System |
| 166 | Supplying and drawn of UTP 4 pair CAT 6A LAN cable in the existing surface/recessed steel/PVC conduit as required1 run of Cable. |
| 167 | Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor,unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required.2 Pair |
| 168 | Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required. |
| 169 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.40 mm |
| 170 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.Telephone socket outlet |
| 171 | Supply and Fixing suitable size modular GI box with cover in front on and providing and fixing 1 no RJ 45 including connections as required. |
| 172 | Supply, laying and termination of 10 pair telephone cable, 0.5mm copper PVC insulated, unarmoured telephone cable drawn in the existing cable tray |
| 173 | Supply, installation, testing, and commissioning of Telephone Krone Type Disconnection Box with 10-pair or 20-pair capacity (expandable), suitable for structured voice cabling distribution. The box shall include high-quality LSA-PLUS (Krone type) modules, a weather-resistant enclosure, and accessories. |
| 174 | Supply of analogue telephone instruments compatible with EPABX/PSTN lines. The telephone shall be DTMF type with basic features such as redial, ring indication, and volume control, suitable for wall/desk mounting. The instrument shall operate without external power and be of robust construction from a reputed make. |
| 175 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm |
| 176 | LT Cabling |
| 177 | Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 95 sq mm |
| 178 | Supply, laying and clamping of 1 No. PVC insulated single core 50 Sq.mm copper flexible cable, 1.1 kV grade, using suitable clamps with spacing not exceeding 60 cm, including dressing, clamping, making good damages, and colour washing as required. |
| 179 | Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp |
| 180 | Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 25 sq mm with factory made clamp |
| 181 | Supplying and making end termination with brass compression gland and aluminium lugs forfollowing size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KVgrade as required.3 1/2X 95 sq. mm (45mm) |
| 182 | Supplying and making end termination with brass compression gland and aluminium lugs forfollowing size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KVgrade as required.4 X 16 sq. mm (28mm) |
| 183 | Supplying and making end termination with brass compression gland and aluminium lugs forfollowing size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KVgrade as required.4 X 25 sq. mm (28mm) |
| 184 | Earthing |
| 185 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 186 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 187 | Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.75 mm copper conductor (6 SWG) |
| 188 | Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 8 SWG) |
| 189 | Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.00 mm (8 SWG) |
| 190 | Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.75 mm (6 SWG) |
| 191 | Fire Alarm System |
| 192 | Supplying, Installation, Testing & Commissioning of Conventional Fire Alarm Control Panel (2 Zone) - Providing and fixing microprocessor-based conventional fire alarm control panel (2 zone) conforming to IS:15908:2011, complete with 16x2 LCD display, LED indications for fire/fault, tactile keypad, SMPS power supply, modular construction, standby battery backup with inbuilt charger, battery protection features, relay outputs for fire and fault, zone-wise isolation and walk test facility, compatible with all conventional detectors, including all necessary accessories, wiring, testing and commissioning complete as required. The panel shall operate on 220V AC supply with provision for 24V DC backup using 2 Nos. 12V, 7Ah sealed lead acid batteries, including all interconnections, mounting, and making the system fully functional. |
| 193 | CABLING & WIRING Supplying & laying of 2x1.5 sq mm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required. |
| 194 | Supply, installation, testing & commissioning of Battery Unit : 24 VDC (2nos of 12VDC), 7/10 AMPS. |
| 195 | Remove the existing detectors on the false ceiling and re-install it on the true ceiling with required screws/fasteners as required as per the direction of Engineer-in-Charge. |
| 196 | Remove & Re-install the Response indicator as per the direction of Engineer-in- Charge at site. |
| 197 | FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL) Supplying, installation, testing & commissioning of smoke detector with built-in LED and mounting base complete with all connections etc. as required. |
| 198 | FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL) Supplying, installation, testing & commissioning of manual call box of ABS type in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required. |
| 199 | FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL) Supplying, installation, testing & commissioning response indicator on surface/ recess MS box having two LEDs metallic cover complete with all connections etc. as required. |
| 200 | FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL) Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in A.B.S. box with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required. Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail