| 1 | Supply and fix in replacement power contactors installed at ATS panel/Timer panel after dismatling existing contactors from panel /ATS and connecting new contactors and making connection with incoming and outgoing MCCB/MCB complete all as specified and as directed for following ratings . Note: Minimum of 10 % Variation in Amp rating shall be allowed as per Make approved , The minimum rating is as follows . Make: L & K /Indo Asian/Legrand/ Havell's |
| 2 | 4 pole power contactors Type MCX of rating up to 50/55 Amp |
| 3 | 4 pole power contactors Type MCX of rating 63 Amp |
| 4 | 4 pole power contactors Type MCX of rating 100/105 Amp |
| 5 | Supply and fix in replacement Astronomical time switch (Timer for 24 hrs) after dismatling existing Timer from panel and connecting new timer and making connection with existing contactors / panel complete all as specified and as directed. Make: GIC /Indo Asian /Legrand |
| 6 | Supply,install,test and commissioning of Outdoor type L T street light timer panel double door made out of 3.0 mm thick CRCA sheet out door type totally enclosed weather dust and vermin proof as per IS , made through CPRI Approved Manufature with front opening suitable locking arrangement having Auminium bus bar of 100 Amps capacity for RYB and neutral and insulated with insulators, including connecting incoming and outgoing cables necessary PCC 1:3:6 in foundation and made out of 35 x 35 x 5 mm angle iron grouted at ground above 30 cm from ground level with necessary provision of Auto manual operation of contactor/Out going supply by two way selector switch with necessary wiring from contactor and timer including taking out old unserviceble Time switch box complete all as specified and as directed by the engineer - in-charge with the following: Note: Cost in cluding necessary internal wiring.MCB/ HRC fuse fro control wiring , Bus bar to MCB connections , Contractor has to fabricate the Panel from CPRI Approved Manufature and get it approved from Accepting officer before commencement of work/Fabrication. IncomingMCB 63 Amp 4 pole , 10 kA -01 NosOutgoingMCB 4 pole 32 AMP , 10 KA - 04 NosMCB DP 32 Amp,10 KA - 04 Nos4 pole power contactor type MCX 40 Amp - 02 Nos Make: L & K /Indo Asian/Legrand/ Havell'sAstronomical time switch - 02 Nos : Make: L & K /Indo Asian/Legrand/ Havell'sLED type Indicator for ON/Off for Each contractor - 04 Nos3 way selector switch for Auto Manual Operation - 02 Nos |
| 7 | Excavation in trenches not exceeding 1.5 metre wide and not exc 1.5 metre in depth for foundation of pole / stay, or cable trenches and getting out in hand /Disintegrated rock complete all as specified and as directed by the Engineer in charge |
| 8 | Returning filling in incl spreading, leveling watering and well ramming in layers not exceeding 25 cm in soft loose soil complete all as specified and as directed by the Engineer in charge |
| 9 | Removing excavated materials to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 metre above the starting point all as specified and as directed by the engineer –in- charge. |
| 10 | Supply and laying double walled corrugated (DWC) HDPE duct pipe of size 50 mm Outer Dia conforming to IS, approved colour complete with fittings for cable protection. Note: The inner /Outer dia of Pipes may varies asper Make Approval /Market availability contractor has to supply the size of pipe not less than menstioned below) |
| 11 | M & L XLPE insulated, armoured, heavy duty electric cable with aluminum conductor, 1100 Volts grade, in trenches/fixed on wall for following size complete. Note: Rate include necessary lugs , gland packing and excluding the earth work and cable protection pipe |
| 12 | 25 Sq mm 3.5 Core |
| 13 | 16 Sq mm 4.0 Core |
| 14 | 10 Sq mm 4.0 Core |
| 15 | M&L for earthing complete with galvanised steel earth plate electrode 600 x 600 x 6.0 mm thick burried directly in gorund (earth pit not less than 2.25 Mtr normal ground level),and top edge of earth plate not less than 1.5 mtr below normal ground level,using galvanised iron strip 25×4mm as earthing lead with bolts, nuts & check nuts, and washers of galvanised iron protection pipe light grade of 40 mm dia and watering pipe medium grade of 20 mm dia and filled with alternate layer of charcoal and common salt, watering funnel with wire mesh, earth pit chamber and cover CI frame PCC 1:3:6 type C-2 all as shown in electrical plate No-3 of SSR part-I of 2009 connected to earthing test point all as specified and indicated including all earth work excavation, returning filling and disposal of surplus soil and testing on completion. |
| 16 | Supply and fix in replacement MCCB DB 8 way, IP- 43 Degree Protection suitable for fixing 125/160 AMP MCCB 4 Pole as incommer and MCB TP/SP as outgoing complete including taking down existing MCCB DB from Wall Concealed or surface and Fix the the MCCB DB on wall concealed or Surface on wall as per site , Making good to disturbed surface of wall apply 2 coat of cement based paint on wall to match with existing complete all as specified and as directed.Make L & K Cat part No -DEVTH008DD/Equivalent in Legrand /ABBNote : MCCB for incomer and MCB TP/SP for out going connections shall be measured and paid seperately under respective items in shedule. |
| 17 | Supply and fix in replacement power line SPD single pole + NPE of voltage rage Uc 320 V , 1 P +NPE complete with eclosure for fixing the SPD on wall including wiring using 4.0 SQ mm Single core multi stranded copper conductor with existing DB placed adjesent on wall comple all as specified and as directed. |
| 18 | Supply and fix in replacement power line SPD 4 pole of voltage rage Uc 550 V ,4 pole complete with eclosure for fixing the SPD on wall including wiring using 4.0 SQ mm Single core multi stranded copper conductor with existing DB placed adjesent on wall comple all as specified and as directed. |
| 19 | Supply and fixing 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of single poles and current carrying capacity 6 to 32 AMP, in the MCB DB Complete with connection testing and commissioning Make : Indo Asian/Legrand /L & T / Standard/ Havell's/L & K . |
| 20 | Supply and fix MCB 63 Amp 4 Pole ,10 KA complete all as specified and as directed Make : Indo Asian/Legrand /L & T / Standard/ Havell's/L & K . |
| 21 | Supply and fix MCCB 125/160 Amp 4 Pole ,16 KA complete all as specified and as directed Make : Indo Asian/Legrand /L & T / Standard/ Havell's/L & K . |
| 22 | M&L, for apply two coat of cement base paint on RCC Poles of Height up to 9.0 Mtrs and Its copping after necessary scrubbing, cleaning thoroughly including removing the old paints, creaper on poles and complete cleaning the surface pole surface including painting the GI bracket with synthetic enamal paint complete all as specified and as directed. Note: Pattern of paint /Shade |
| 23 | M & L for preperation of old painted surface of steel tubular pole of height up to 9.0 Mtrs including painting the GI bracket complete by apply two coat of synthetic enamal paint after preperation of existing old painted surfaces complete all as specified and as directed. |
| 24 | M & L for preperation of old painted surface of steel tubular pole of height up to 3/4 Mtrs including painting the GI bracket complete by apply two coat of synthetic enamal paint after preperation of existing old painted surfaces complete all as specified and as directed. |
| 25 | M & L for laying graded aggregate of size 20 mm in E/M installation all as directed by EIC. |
| 26 | M & L for laying graded aggregate of size 12.5 mm in E/M installation all as directed by EIC. |
| 27 | Supply and fix fire retardant insulated synthetic mat for LT , 1100 Volt of 2.0 mm thick +/- 10% conforming to IS , tested for breakdown strength, ageing properties, insulation resistance, effect of acid,Alkaline, Diesel & transformer oil ,leakage current test,fire test etc having the width of 1000mm +/-20mm complete as required sutable and using adhasive and alied chemical and scaling of all part s of all joints and border ends and fixing tape making good as paste near LT panel boards complete all as specified and as directed. Make: Vardhaman/Jyothi/Cease fire/Qquivalent as approved by GE. |
| 28 | M & L for laying of weed control mat sorrounding area of Over Head Tank /UG Sump , insid ethe Water supply Installations of Size thickness less than 100 GSM ans Size 1.0/1.2 X 100 Mtrs of roll laid in level surface with 7 inch (18 cm) High Quality PVC Nails for firm hold for Weed Mat at earth surfaces in regular intervals ( In Between 5 Mtrs) complete all as specified and as directed. |
| 29 | M& L for surface excavation at E/M installations and store yards not exceeding 30 cm deep and averaging 15 cm deep and getting out soft / loose soil removing shrubs, small trees height up to 1.0 Mtrs , removing the grass from route as directed , Note : (i) Rate includes removing all waste material and grass not excceding 50 Mtrs distance from installation ,depositing where directed at a level not exceeding 1.5 Mtrs above the starting point and cleaning of yard , Complete all as specified and directed by EIC. |
| 30 | Note: An amount of Rs 15790.00 on account of Credit Schedule for Schedule A Part II shall be deducted from the total amount of BOQ to arrive at Contract Sum. Please Enable Macros to View BoQ information |