| 1 | DISMANTLING, UNLOADING, SHIFTING OF OLD DG SET 1010 KVA | DISMANTLING, UNLOADING, SHIFTING OF OLD DG SET 1010 KVA |
| 2 | DISMANTLING & REASSEMBLING OF OTHER SYSTEM | DISMANTLING & REASSEMBLING OF OTHER SYSTEM |
| 3 | MANNUAL SHIFTING AT OUTSIDE | MANNUAL SHIFTING AT OUTSIDE |
| 4 | MS PIPE, SILENCER, COOLING PIPE, ETC DISMANTLING | MS PIPE, SILENCER, COOLING PIPE, ETC DISMANTLING |
| 5 | BUS DUCT, EARTHING, CONTROL CABLE ETC DISMANTLING | BUS DUCT, EARTHING, CONTROL CABLE ETC DISMANTLING |
| 6 | SUPPLY OF DIESEL ENGINE SET of 1010 KVA CAQM CERTIFIED ALONGWITH HEAT EXCHANGER AND OTHER ASSOCIATED ITEMS ETC. DETAILS AS GIVEN IN THE BID. | SUPPLY OF DIESEL ENGINE SET of 1010 KVA CAQM CERTIFIED ALONGWITH HEAT EXCHANGER AND OTHER ASSOCIATED ITEMS ETC. DETAILS AS GIVEN IN THE BID. |
| 7 | UNLOADING AND SHIFTING OF DG SET 1010 KVA ALONGWITH THE ALL OTHER ASSOCIATED ITEMS AT THE GROUND FLOOR | UNLOADING AND SHIFTING OF DG SET 1010 KVA ALONGWITH THE ALL OTHER ASSOCIATED ITEMS AT THE GROUND FLOOR |
| 8 | REASSEMBLING OF OTHER ASSOCIATED SYSTEMS OF THE DG SET IN THE DG ROOM | REASSEMBLING OF OTHER ASSOCIATED SYSTEMS OF THE DG SET IN THE DG ROOM |
| 9 | MECHANICAL OR MANUAL SHIFTING OF THE DG SET AT FOUNDATIONS OR BLOCKS, ETC., AS PER THE SITE REQUIREMENT. | MECHANICAL OR MANUAL SHIFTING OF THE DG SET AT FOUNDATIONS OR BLOCKS, ETC., AS PER THE SITE REQUIREMENT. |
| 10 | BUSDUCT, EARTHING, CONTROL CABLE ETC CONNECTION ETC AS PER SITE REQUIREMENT | BUSDUCT, EARTHING, CONTROL CABLE ETC CONNECTION ETC AS PER SITE REQUIREMENT |
| 11 | DG ROOM MAINGATE DISMANTLING & FIXING ETC AS PER SITE REQUIREMENT | DG ROOM MAINGATE DISMANTLING & FIXING ETC AS PER SITE REQUIREMENT |
| 12 | SITC OF ANTI-VIBRATION PAD SUITABLE FOR THE DG SET, IN ACCORDANCE WITH THE OEM STANDARD | SITC OF ANTI-VIBRATION PAD SUITABLE FOR THE DG SET, IN ACCORDANCE WITH THE OEM STANDARD |
| 13 | SITC OF HEAVY DUTY ‘C’ CLASS MS PIPE 250 MM DIA. WITH ALLUMINIUM CLADDING INCLUDING RECKWOLL INSULATION AS PER OEM STANDARD, ETC. AS PER SITE REQUIREMENT. | SITC OF HEAVY DUTY ‘C’ CLASS MS PIPE 250 MM DIA. WITH ALLUMINIUM CLADDING INCLUDING RECKWOLL INSULATION AS PER OEM STANDARD, ETC. AS PER SITE REQUIREMENT. |
| 14 | SITC SILENCER CLADING IS COMPLETE IN ALL RESPECTS. | SITC SILENCER CLADING IS COMPLETE IN ALL RESPECTS. |
| 15 | Providing & fixing in position the following MS Pipe 'C' class cut to required lengths and installed with all ER welded joints, including providing and fixing in position with fittings like elbows, tees and reducers, sockets, clamps, painting, marking, etc. as required. | Providing & fixing in position the following MS Pipe 'C' class cut to required lengths and installed with all ER welded joints, including providing and fixing in position with fittings like elbows, tees and reducers, sockets, clamps, painting, marking, etc. as required. |
| 16 | Supply and fixing of Butterfly Valves with nut-bolts, gas kits, etc., complete in all respects. | Supply and fixing of Butterfly Valves with nut-bolts, gas kits, etc., complete in all respects. |
| 17 | Supply and fixing of NRV with nut-bolts, gas kits etc complete in all respects | Supply and fixing of NRV with nut-bolts, gas kits etc complete in all respects |
| 18 | Supply and installation of Secondary Water Pumps for DG Sets (Flow requirement minimum 900LPM) - Monoblock Type with suitable size of incomer aluminium cable and copper cable for the pumps etc on the existing cable tray. | Supply and installation of Secondary Water Pumps for DG Sets (Flow requirement minimum 900LPM) - Monoblock Type with suitable size of incomer aluminium cable and copper cable for the pumps etc on the existing cable tray. |
| 19 | Supply and fixing of Pr. Gauges with u-bend, SS valve, etc., industrial type complete in all respects. | Supply and fixing of Pr. Gauges with u-bend, SS valve, etc., industrial type complete in all respects. |
| 20 | Supply and fixing of Temp. Gauges with u-bend, SS valve, etc., industrial type complete in all respects. | Supply and fixing of Temp. Gauges with u-bend, SS valve, etc., industrial type complete in all respects. |
| 21 | Supply & Fixing of miscellaneous MS support for horizontal/vertical water piping, including fabrication, hardware, and painting & pressure testing, etc., complete in all respects. | Supply & Fixing of miscellaneous MS support for horizontal/vertical water piping, including fabrication, hardware, and painting & pressure testing, etc., complete in all respects. |
| 22 | Supply and fixing of HE flexible 100mm dia | Supply and fixing of HE flexible 100mm dia |
| 23 | MCC panel for cooling tower and pumps with a main incomer, aluminium bus-bar, multifunctional meter, selector switch, and a suitable starter for pumps & cooling tower etc as per site requirement | MCC panel for cooling tower and pumps with a main incomer, aluminium bus-bar, multifunctional meter, selector switch, and a suitable starter for pumps & cooling tower etc as per site requirement |
| 24 | Supply of 2000amp., 4pole copper sandwich bus duct with bend, tee, jointer, termination etc (Straight Length 50kA for 1 sec - IP66 Outdoor Type with 1.2mm GI Canopy including 90 degree Bends, Copper Flexible, Adaptor Box, Flange End and Rubber Below at DG side - for 1 route only) | Supply of 2000amp., 4pole copper sandwich bus duct with bend, tee, jointer, termination etc (Straight Length 50kA for 1 sec - IP66 Outdoor Type with 1.2mm GI Canopy including 90 degree Bends, Copper Flexible, Adaptor Box, Flange End and Rubber Below at DG side - for 1 route only) |
| 25 | Straight Length 50kA for 1 sec - IP55 Indoor Type, including 90 degree Bends, Copper Flexible, Adaptor Box, Flange End and Rubber Below at DG side - for 1 route only | Straight Length 50kA for 1 sec - IP55 Indoor Type, including 90 degree Bends, Copper Flexible, Adaptor Box, Flange End and Rubber Below at DG side - for 1 route only |
| 26 | SITC of AMF panel with in-built master PLC controller, 2500amp. 4-pole microprocessor-based ACBs for incomer and outgoing; suitable size of copper control cable to connect other load-side breakers, old AMF breakers, charger, etc.; complete as per site requirements. The design and features are as per the client's requirement, and it must include all features, but not least, the features available in the existing AMF panel. | SITC of AMF panel with in-built master PLC controller, 2500amp. 4-pole microprocessor-based ACBs for incomer and outgoing; suitable size of copper control cable to connect other load-side breakers, old AMF breakers, charger, etc.; complete as per site requirements. The design and features are as per the client's requirement, and it must include all features, but not least, the features available in the existing AMF panel. |
| 27 | Scaffolding Charges | Scaffolding Charges |
| 28 | S/L of 50x6 CU strip | S/L of 50x6 CU strip |
| 29 | S/L of 50x6 GI strip | S/L of 50x6 GI strip |
| 30 | S/L of 25x5 GI strip | S/L of 25x5 GI strip |
| 31 | 8 SWG GI Wire | 8 SWG GI Wire |
| 32 | Stadd Analysis | Stadd Analysis |
| 33 | Supply & fixing of Lighting protection System complete with Aviation light, Lightning Mast, Earthing Pit, Strip, & Down conductor. | Supply & fixing of Lighting protection System complete with Aviation light, Lightning Mast, Earthing Pit, Strip, & Down conductor. |
| 34 | Obtaining approval for running DG Sets from CEIG for 1x1010 KVA DG Installation. (The Govt. fee will be in Customer's scope). | Obtaining approval for running DG Sets from CEIG for 1x1010 KVA DG Installation. (The Govt. fee will be in Customer's scope). |
| 35 | SITC of Clean Agent-Based Tube Fire Suppression System 2 kg 10 mtr. heat-sensing UL Listed | SITC of Clean Agent-Based Tube Fire Suppression System 2 kg 10 mtr. heat-sensing UL Listed |
| 36 | Photo luminescent non toxic, non – radio active maintenance free self glowing signs comprising | Photo luminescent non toxic, non – radio active maintenance free self glowing signs comprising |
| 37 | Painting of pipe structure and other parts of the DG set, etc., with an approved shed with two coats of enamel paint after one coat of primer. | Painting of pipe structure and other parts of the DG set, etc., with an approved shed with two coats of enamel paint after one coat of primer. |
| 38 | Minor Civil- wall breaking and repairing, foundation block etc related to the installation of DG set and other associated items | Minor Civil- wall breaking and repairing, foundation block etc related to the installation of DG set and other associated items |
| 39 | SITC of the induced draft cooling tower suitable for the 1010 KVA DG set complete in all respect i.e motor, copper cable, cable tray, base frame, PVC fills, eliminator, PVC pipe, nozzles etc | SITC of the induced draft cooling tower suitable for the 1010 KVA DG set complete in all respect i.e motor, copper cable, cable tray, base frame, PVC fills, eliminator, PVC pipe, nozzles etc |