| 1 | Supply and fixing in replacement LT Panel board outdoor type fabricated out of 3.15mm thick CRCA Sheet steel factory made vermin proof duly painted with two coat of synthetic enamelled paint over a coat of red oxide primer or powder coated, double door, water proof dust and vermin proof hinged and lockable doors inlcuding rain protection cover on top and complete with interconnections, with copper wires, tapes, opening from both sides with cable entry from bottom, with cable alley and bus bar chamber, bonding to earth and painting, including angle iron frame of size minimum 40x40x6mm having 4 legs 0.60 mtr long including grouting in PCC 1:4:8, to the reqd depth including under mentioned Items all as specified and directed by Engineer-in-Charge. (CC Wing Panel No 1)INCOMING(a) MCCB 300 amps 4 pole 25 KA thermal Adjustable and fixed magnetic type - 01 NoBusbar : - Aluminium busbar 3 phase 4 wire of 600 Amps supported with ebonite insulators -1setOUTGOING(a) MCCB 200 Amps 4 pole 16 KA thermal Adjustable and fixed magnetic type – 07 Nos(b) Multifuction meter suitable to display voltage, current, frequency, power factor and other relavent parameters for three phase 4 wire 415 Volts System including three nos CTs of appropriate ratio – 01 No(c) LED indicator RYB – 03 Nos. |
| 2 | Supply and fixing in replacement LT Panel board outdoor type fabricated out of 3.15mm thick CRCA Sheet steel factory made vermin proof duly painted with two coat of synthetic enamelled paint over a coat of red oxide primer or powder coated, double door, water proof dust and vermin proof hinged and lockable doors inlcuding rain protection cover on top and complete with interconnections, with copper wires, tapes, opening from both sides with cable entry from bottom, with cable alley and bus bar chamber, bonding to earth and painting, including angle iron frame of size minimum 40x40x6mm having 4 legs 0.60 mtr long including grouting in PCC 1:4:8, to the reqd depth including under mentioned Items all as specified and directed by Engineer-in-Charge. (CC Wing Panel No 2)INCOMING(a) MCCB 300 amps 4 pole 25 KA thermal Adjustable and fixed magnetic type - 01 NoBusbar : - Aluminium busbar 3 phase 4 wire of 600 Amps supported with ebonite insulators -1setOUTGOING(a) MCCB 200 Amps 4 pole 16 KA thermal Adjustable and fixed magnetic type – 04 Nos(b) Multifuction meter suitable to display voltage, current, frequency, power factor and other relavent parameters for three phase 4 wire 415 Volts System including three nos CTs of appropriate ratio – 01 No(c) LED indicator RYB – 03 Nos. |
| 3 | Supply and fixing in replacement LT Panel board outdoor type fabricated out of 3.15mm thick CRCA Sheet steel factory made vermin proof duly painted with two coat of synthetic enamelled paint over a coat of red oxide primer or powder coated, double door, water proof dust and vermin proof hinged and lockable doors inlcuding rain protection cover on top and complete with interconnections, with copper wires, tapes, opening from both sides with cable entry from bottom, with cable alley and bus bar chamber, bonding to earth and painting, including angle iron frame of size minimum 40x40x6mm having 4 legs 0.60 mtr long including grouting in PCC 1:4:8, to the reqd depth including under mentioned Items all as specified and directed by Engineer-in-Charge. (559 Main Panel)INCOMING(a) MCCB 300 amps 4 pole 25 KA thermal Adjustable and fixed magnetic type - 01 NoBusbar : - Aluminium busbar 3 phase 4 wire of 600 Amps supported with ebonite insulators -1setOUTGOING(a) MCCB 125 Amps 4 pole 16 KA thermal Adjustable and fixed magnetic type – 04 Nos(b) MCCB 100 Amps 4 Pole 16 KA thermal Adjustable and fixed magnetic type - 01 Nos(c) MCB TPN 63 Amp - 03 Nos (d) MCB TPN 32 Amp - 03 Nos (e) Multifuction meter suitable to display voltage, current, frequency, power factor and other relavent parameters for three phase 4 wire 415 Volts System including three nos CTs of appropriate ratio – 01 No(f) LED indicator RYB – 03 Nos. |
| 4 | Supply and fixing in replacement LT Feeder pillar Panel board outdoor type fabricated out of 3.15mm thick CRCA Sheet steel with breadth 0.6mm and width of panel not less than 0.40 mtrs factory made vermin proof duly painted with two coat of synthetic enamelled paint over a coat of red oxide primer or powder coated, double door, water proof dust and vermin proof hinged and lockable doors inlcuding rain protection cover on top and complete with interconnections, with copper wires, tapes, opening from both sides with cable entry from bottom, with Aluminum bus bar chamber three phase four wire 415 Volts type of rating 150 Amps, length of each bus bar not less than 0.60 mtr including MCCB of rating 160 Amps, thermal adjustable, 25 kA, 3 Pole bonding to earth and painting, including angle iron frame of size minimum 40x40x6mm having 4 legs 0.60 mtr long including grouting in PCC 1:4:8, to the reqd depth including under mentioned Items all as specified and directed by Engineer-in-Charge. |
| 5 | S&F in replacement of MCCB 3/4 pole as reqd 415 volt thermal adjustable and fixed magnetic type of capacity 250 Amps with breaking capacity 25 KA Complete all as specified and as directed by Engr-In-Charge. |
| 6 | S&F in replacement of MCCB 3/4 pole as reqd 415 volt thermal adjustable and fixed type of capacity 160 Amps with breaking capacity 16 KA Complete all as specified and as directed by Engr-In-Charge. |
| 7 | Excavation in trenches in soft /loose soil not exceeding 1.5 M wide and not exceeding 1.5 M in depth for laying of UG cables etc and getting out complete all as specified and as directed by Engr-In-Charge. |
| 8 | Returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25 cms in any type of soil complete all as specified and as directed by Engr-In-Charge. |
| 9 | Removing excavated soil to a distance not exceeding 50 mtrs and depositing where directed at a level not exceeding 1.5 M above the starting point all as directed. |
| 10 | M&L for sand cushioning in trenches for bricks of u/g cable with coarse sand laid dry in trenches with uniform thickness complete all as specified and as directed by Engr-In-Charge. |
| 11 | Supply and lay burnt bricks of sub class 'B' laid dry across in trenches for cable protection all as specified and directed Complete all as specified and as directed by Engr - In - Charge. Please Enable Macros to View BoQ information |
| 12 | Supply and lay burnt bricks of sub class 'B' laid dry across in trenches for cable protection all as specified and directed Complete all as specified and as directed by Engr - In - Charge. Please Enable Macros to View BoQ information |